SLPOWER RMX-350

350 WATTS
POWER FACTOR CORRECTED
MULTIPLE OUTPUT, HOT SWAP
RMX-350
Featuring:
• Diode isolated outputs for hot swap
• ÒZero wireÓ slope program current
sharing for redundancy
• Self-aligning connector with solid
metal machined contacts
• Universal AC input
• 0.99 typical power factor
• Dual converter design eliminates
interaction between logic and
auxiliary outputs
• Low ripple and noise on all outputs
• DC power good and AC power fail
signals
• True remote inhibit
• Monotonic turn-on and turn-off
STANDARD RMX SERIES
MODEL
PWR
OUTPUT #1
RMX-353-0512
RMX-354-1205
RMX-354-1212
RMX-354-1224
RMX-354-1512
RMX-354-1524
350
350
350
350
350
350
+5V
+5V
+5V
+5V
+5V
+5V
@
@
@
@
@
@
50A
50A
50A
50A
50A
50A
OUTPUT #2
+12V @ 8/12A pk
+12V @ 8/12A pk
+12V @ 8/12A pk
+12V @ 8/12A pk
+15V @ 4A
+15V @ 4A
OUTPUT #3
OUTPUT #4
-12V
-12V
-12V
-12V
-15V
-15V
5.2V @ 5A
12V @ 5A
24V @ 3A
12V @ 5A
24V @ 3A
@
@
@
@
@
@
4A
4A
4A
4A
4A
4A
Maximum power from outputs #2, #3 and #4 to be less than 170W
RMX Series 350-watt power supplies
provide new and increased flexibility for
configuring redundant Òhot swappableÓ
power systems using a standard
product. The RMX-350 Series eliminates
the need for external sheet metal sleds,
OR-ing diodes, and a high current interface. These switching power supplies are
power factor corrected, multiple-output
units which contain built-in Schottky ORing diodes and a high current connector
interface.
SEE
50T
3
X
RM DC INPUT
FOR IVALEN
EQU
Condor D.C. Power Supplies, Inc., A subsidiary of SL Industries, Inc. 805-486-4565 ¥ (800) 235-5929 Fax: (805) 487-8911 http://www.condorpower.com
350 WATTS
10.75”x 4.8”x 2.5”
RMX-350
RMX-350
3.5 lbs - 1.6 kgs
Dimensions:
Inches
Millimeters
SPECIFICATIONS: ALL MODELS
INPUT
AC Input: 90-264 Vac continuous range, 47 to 63 Hz. Internally fused for 7A.
Power Factor: 0.99 typical at full load. Meets EN61000-3-2.
Inrush: Cold startAC current is less than 30 A at 115 Vac and 60 A at 230 Vac. Limited by
thermistor.
Brownout Protection: Holds regulation to 85 Vac.
Holdup Time: 20 ms minimum after removal of power at full load.
Efficiency: 70% typical.
AC Power Fail: Provides TTL “0” 5 ms before output voltage goes out of regulation band
upon loss of AC power.
OUTPUT
Adjustability: Outputs #1 and 2, and 4 factory adjusted to nominal ±0.2%. Output #3 tracks
#2; initial accuracy ±3%.
Line & Load Reg: Outputs #1, 2, and 4 hold ±2% over AC input range and 0 to 100% load
change (preprogrammed slope). Output #3 requires 20% minimum load on outputs #2
and 3 to hold ±5%.
Ripple & Noise: 1% p-p or 100 mV, whichever is greater.
Remote Sense (Output #1): Compensates for 250 mV total line drop. Preprogrammed slope
remains under ±3 worst case. Open sense lead protection.
Temperature Coefficient (Outputs #1, 2, and 4):0.03% per degree C.
Stability: 0.1% over 8 hours after 30 minutes warm-up.
Transient Response (Outputs #1, 2, and 4): Output voltage returns to within 1% in less than
500 µs for a 50% load change (measured with rise time and fall time of 200µs). Peak
transient does not exceed 5%.
Overload Protection: All outputs are protected against overload and shortcircuit. Automatic
recovery upon removal of fault.
Overvoltage Protection (Outputs #1 and 2): Protects load against power supply induced overvoltage. Trip point is factory set so that output voltage cannot exceed 136% of nominal.
Peak Output Current: Dual current ratings define continuous and peak currents. The peak
current shown can be delivered for a maximum period of 30 seconds.
Remote Enable: Contact closure to common turns on DC outputs (recessed pin for “make
last, break first” connection).
Remote Inhibit: Contact closure to the negative sense line or a TTL level “0” turns off DC
outputs.
DC Power Good: Provides a TTL “1” open collector when output #1 is above 4.6 V nominal.
Redundancy: Built-in OR-ing diodes, slope program current sharing on all outputs, and self
aligning connector provide “hot swap” and “N+1” capabilities. Current sharing remains
within 10% of the unit’s full output rating while units are in thermal equilibrium.
Reverse Voltage: Protected against reverse voltage up to supply current rating.
ENVIRONMENTAL
Thermal Protection: Shuts down power supply if overheated. Automatic recovery.
Temperature Range: 0°to 50°C at full ratings.
Safety Agencies: Most models are approved to UL1950; CSA 22.2 #234; IEC 950 and TÜV
EN60950, Class 1 SELV., CE 72/23/EEC/93/68EEC (low voltage directive).
Conducted RFI: Meets FCC Part 15, Subpart J, Class A; EN55022 Class B; CISPR 22 Class B.
Output Isolation: Isolated from ground 50 Vdc.
Cooling: Self-cooled by internal ball-bearing fan.
OPTIONS
Consult factory for available options.
AC INPUT (90-264 VAC Continuous Range)
FUNCTION
J1-21
J1-23
J1-25
115 VAC
Line
Neutral
Safety Ground
230 VAC
Line 1
Line 2
Safety Ground
LOCATION
J1- 10, 20, 30
J1 - 9, 19, 29
J1-2
J1-3
J1-4
J1-3
J1-5
NOTES
Main Output
Rtn (Common)
CONNECTOR
See below
DC OUTPUT
FUNCTION
Output #1
Output #2
Output #3
Output #4
J1-6
Rtn (Common)
Rtn (Common)
(+) Floating
Output
(–) Floating
Output
CONNECTOR
Positronics #
PLC30M400A1-168.3
Mates with panel
mounted
PLC30F1000
connector using
crimp contacts
FC114N2
(14 to 16 AWG)
STATUS AND CONTROL
FUNCTION
Remote Sense
DC Power Good
LOCATION
J1-18
J1-8
J1-7
NOTES
CONNECTOR
Output #1 Sense
Output #1 Sense Rtn
Reference to Common
when #1 Sense Rtn
See above
isterminated
Enable
Inhibit
AC Power Fail
J1-16
J1-27
J1-17
Reference
to Common