CRYDOM DR10D12

SeriesOne DR Series
• Ratings of 6 & 12 Amps
• Load voltage ratings of 1-60VDC, 1-100VDC, 24-280VAC and 48-600VAC
• Fits standard 35mm DIN-RAIL
• LED input status indicator
• AC or DC control
• Zero-crossing (resistive loads) or random turn-on (inductive loads) output
• UL and cUL Listed, HP Rated CE & RoHS Compliant
• UL 508 Endurance Rating for Enhanced Reliability
PRODUCT SELECTION
Description
4-32 VDC Control
90-140 VAC Control
200-265 VAC Control
18-36 VAC Control
280V, 6A
280V, 12A
600V, 6A
600V, 12A
60V, 6A
60V, 12A
100V, 6A
100V, 12A
DR24D06
DR24B06
DR24A06
DR24D12
DR24B12
DR24A12
DR48D06
DR48D12
DR48B12
DR48A12
DR06D06
DR06D12
DR10D06
DR10D12
DR24E06
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS AC Output (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Load Current, resistive [Arms] (2)
Minimum Load Current [Arms]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3)
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec]
HP Rating UL 508/IEC60947 [HP (KW)] @ 240V
HP Rating UL 508/IEC60947 [HP (KW)] @ 380V
HP Rating UL 508/IEC60947 [HP (KW)] @ 480V
Minimum Power Factor (with Maximum Load)
Min/Max stranded wire
Min/Max solid wire
Weight (typical)
DR24x06
DR24x12
DR48X06
DR48x12
24-280
600
6
0.15
0.1
500
1.3
285/300
410/375
1/2 (.37)
1 (.75)
2 (1.5)
0.5
22/14 AWG
22/14 AWG
1.76 oz. (50g)
24-280
600
12
0.15
0.1
500
1.3
715/750
2560/2330
1 (.75)
2 (1.5)
3 (2.2)
0.5
22/14 AWG
22/14 AWG
3.17 oz. (90g)
48-600
1200
6
0.15
0.1
500
1.3
285/300
410/375
1/2 (.37)
1 (.75)
2 (1.5)
0.5
22/14 AWG
22/14 AWG
1.76 oz. (50g)
48-600
1200
12
0.15
0.2
500
1.3
715/750
2560/2330
1 (.75)
2 (1.5)
3 (2.2)
0.5
22/14 AWG
22/14 AWG
3.17 oz. (90g)
OUTPUT SPECIFICATIONS DC Output (1)
Description
DR06D06
DR10D06
DR06D12
DR10D12
Operating Voltage [VDC]
Maximum Load Current [Adc] (2)
Minimum Load Current [mAdc]
Maximum Off-State Leakage Current @ Rated Voltage [mA]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum Surge Current (10ms) [Apk]
On-State resistance at rated current [Ohms]
Min/Max stranded wire
Min/Max solid wire
Weight (typical)
1-60
6
2.5
0.1
0.6
60
0.1
22/14 AWG
22/14 AWG
1.76 oz. (50g)
1-100
6
2.5
0.1
0.6
60
0.1
22/14 AWG
22/14 AWG
1.76oz. (50g)
1-60
12
2.5
0.1
0.5
100
0.045
22/14 AWG
22/14 AWG
3.17 oz. (90g)
1-100
12
2.5
0.1
0.5
100
0.045
22/14 AWG
22/14 AWG
3.17 oz. (90g)
Description
DRxxDxx
DRxxBxx
DRxxAxx
DRxxExx
Control Voltage Range (4)
Minimum Turn-On Voltage
Minimum Turn-Off Voltage
Minimum Input Current [mA] (5)
Maximum Input Current [mA] (5)
Maximum Turn-On Time (6) (7)
Maximum Turn-Off Time (8)
Min/Max stranded/solid wire
4.0-32 VDC
4.0 VDC
1.0 VDC
9
11
1/2 Cycle
1/2 Cycle
22/16 AWG
90-140 Vrms
90 Vrms
10 Vrms
3
5
20 msec
30 msec
22/16 AWG
200-265 Vrms
200 Vrms
90 Vrms
2.5
3.3
20 msec
30 msec
22/16 AWG
18-36 Vrms
18 Vrms
4 Vrms
3.5
8
20 msec
30 msec
22/16 AWG
INPUT SPECIFICATIONS (1)
GENERAL SPECIFICATIONS (1)
Description
Dielectric Strength, Input to Output (50/60Hz)
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Recommended Terminal Screw Torque Range:
Parameters
4000Vrms (9)
109 Ohms
10 pF
-30ºC to 80ºC
-30ºC to 100ºC
4.4-7.0 in lb (0.5-0.8 Nm)
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) See Derating Curves
3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
4) DC control includes reverse polarity protection.
5) Input circuitry incorporates active current limiter.
6) Turn-on time for DC control random turn-on versions is 0.1 msec
7) Turn-on time for DC output 600µsec
8) Turn-off time for DC output 300µsec
9) 2500Vrms for DC output
Standards of Compliance
IEC 62314
LC A, Resistive or Slightly Inductive Load Ratings: 12A @ 40C ambient for DR24x12, 12A @ 40C ambient for DR48x12
LC A, Resistive or Slightly Inductive Load Ratings: 6A @ 40C ambient for DR24x06, 6A @ 40C ambient for DR48x06
LC A, Resistive or Slightly Inductive Load Ratings: 6A per channel @ 40C ambient for DRD24D06, 6A per channel @ 40C ambient for DRD48D06
LC B, Motor Loads Ratings: 0.75KW @ 240VAC for DR24x12 and 2.2KW @ 480VAC DR48x12
LC B, Motor Loads Ratings: 0.375KW @ 240VAC for DR24x06 and 1.5KW @ 480VAC DR48x06
LC B, Motor Loads Ratings: 0.375KW @ 240VAC for DRD24x06 and 1.5KW @ 480VAC DRD48x06
Shock and Vibration (Applies to all part numbers)
Vibration Resistance according to IEC 60068-2-6: 0.35mm and 0.75mm Amplitude over 10-55 Hz
Shock Resistance according to IEC 60068-2-27: 15g/11ms
EMC (Applies to all part numbers)
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
MECHANICAL SPECIFICATIONS
WIRING DIAGRAM
THERMAL DERATE INFORMATION
AGENCY APPROVALS
E116949
Rev 030813
ACCESSORIES