HITRON HVP600

H HiTRON
UNIVERSAL INPUT HARMONIC CORRECTION(PFC)
AC-DC N+1 REDUNDANCY AND LOAD SHARING
INTERNAL 1U RACK SWITCHING POWER SUPPLIES
600 WATTS DUAL OUTPUT HVP600 SERIES
FEATURES:

1U HEIGHT RACK POWER SUPPLY

BUILT-IN ACTIVE PFC FUNCTION

INTERNAL OR-ING DIODES FOR
N+1 REDUNDANCY

HOT-SWAPPABLE

HIGH EFFICIENCY & DENSITY

PMBus COMMUNICATION

CE MARKING COMPLIANT
SPECIFICATION
INPUT SPECIFICATION
OUTPUT SPECIFICATION
Input Voltage: Typ. 90-264Vac.
Power Factor: Meet Harmonic Correction IEC 61000-3-2.
Power Factor typ. 0.98.
Input Connector: IEC320-C14 3prong.
Input Frequency: 47-63Hz.
Inrush Current: 11A(rms) at 230Vac;
35A (peak) at 230Vac.
Input Current: 5.8A at 115Vac / 2.8A at 230Vac.
Dielectric Withstand: Meet IEC 60950-1 regulation.
EMI: Meet EN 55022 FCC Class B.
Hold-up Time: Typ. 10mS at 115Vac.
Remote ON/OFF: Available.
Power Fail Signal: Available.
Over Temperature Protection (OTP): Installed NTC and
thermostat.
Leakage Current: Typ. 1mA at 230Vac.
No-Load Power: Typ. 9Watt at 115Vac & 230Vac.
Output Voltage: See Ratings Chart.
Output Current: See Ratings Chart.
Output Power: Total continuous 600W.
Output Connector: ALLTOP C24501-128H1-Y.
Line Regulation: VO1/2 typ. ±1%.
Load Regulation: VO1/2 typ. ±2%.
Total Regulation: VO1/2 typ. ±3%.
Noise & Ripple: Typ. 1% peak-peak.
OVP: Built-in at all outputs.
Adjustability: Available for all outputs.
Hot-Swap: Available.
N+1 Redundancy: Installed with internal OR-ing diodes
at all outputs and third-wire current sharing method for
N+1 redundancy operation.
Current Sharing: Available for all outputs.
DC OK Signal: Available for all outputs.
Over Current Protection (OCP): Built-in.
Overload Protection (OLP): Fully protected against output
overload or short circuit. OLP set at about 120-130%
rating output wattage. Consult the factory for OLP setting.
GENERAL SPECIFICATION
Efficiency: Typ. 92% at 230Vac.
Switching Frequency: 85-100KHz.
Circuit Topology: Half-bridge circuit ZVS circuit.
Transient Response: Peak transient less than 280mV and
recover within 3mS at 25% load-change.
Safety Standard: IEC 60950-1 Class I.
Construction: 1U Rack Format.
Operating Temperature: -10 °C to +70 °C(refer to derating chart).
Storage Temperature: -40°C to +85 °C.
Cooling: Built-in one internal DC ball bearing fan
with smart fan speed control.
Power Density: Typ. 11 Watts/ cubic inch.
PMBus: Built-in.
NOTE: (1)All measurement are at nominal input, full load and +25°C unless otherwise specifications.
(2)Due to requests in market and advances in technology, specifications subject to change without notification.
Hitron Electronics Corporation. B4-11, P.O. Box 26-110 Kaohsiung Export Processing Zone Kaohsiung 806 Taiwan
TEL: 886-7-8210410/FAX: 886-7-8419917, 886-7-8210511/E-mail: [email protected] /Web-site: www.hitron-e.com
1
OUTPUT VOLTAGE / CURRENT RATINGS CHART
DUAL OUTPUT
MAIN +VO1 @★≡⊙
MODEL NO.
HVP600-D560I
AUX +VO2 @★≡⊙
Min.
Typ.
Volt.
Max.
Peak
Min.
Typ.
Volt.
Max.
Peak
0A
7.2A
+56V
7.2A
7.2A
0A
16.6A
+12V
16.6A
16.6A
Symbol: "★" OVP built-in. "@" Adjustable. "≡" Load Sharing. "⊙" Installed with Or-ing diode.
Remark: Maximum Output Power <=600 Watt
WEIGHT: 1.24kgs (2.74lb)
MECHANICAL DIMENSIONS: MM [INCHES]
DERATING CHART
INPUT & OUTPUT CONNECTORS PIN ASSIGNMENT
CNT1
CNT2
L
N
G
P1
P2
LINE
NEUTRAL
GND
VO2
COM
D1
Alert
C1
PS_PRNT
B1
12V_CS
A1
SCL
D2
D3
D4
D5
A2
DGND
5VSB
N/A
C2
C3
C4
C5
A1
PS_EN_IN DCOK_12V_L N/A
B2
B3
B4
B5
A0 PS_EN_OUT DCOK_56V_L N/A
A2
A3
A4
A5
SDA
AC_FAIL
FAN_FAL
N/A
D6
56V_CS
C6
N/A
B6
N/A
A6
N/A
Hitron Electronics Corporation. B4-11, P.O. Box 26-110 Kaohsiung Export Processing Zone Kaohsiung 806 Taiwan
TEL: 886-7-8210410/FAX: 886-7-8419917, 886-7-8210511/E-mail: [email protected] /Web-site: www.hitron-e.com
P3
P4
VO1
RTN
VO1
2