ETC GMQ-5

Bussmann®
Specialty Fuse
GMQ
& HLQ
Time-Delay, Rejection Style
Dimensional Data
FUSE
0.63"
(15.9mm)
FUSE AND CARRIER
57.15
2.250
Catalog Symbol: GMQ (Fuse) HLQ (Fuseholder)
Time-Delay
Rejection Style Fuse
Ampere Rating: ⁄Ω™ to 6⁄Ω¢ Amperes
Voltage Rating: 300 Volts AC or less
Interrupting Rating: 10,000 Amperes
Agency Approvals:
Fuse:
U.L. Listed, Guide JDYX, File E19180
CSA Certified, Class 1422-01, File 53787
Fuseholder:
U.L. Recognized, Guide IZLT2, File E14853
CSA Certified, Class 6225-01, File 47235
18.29
.720
21.59
.850
22.10
.870
Knockout Hole
Carrier
Fuse
Carrier
GMQ-⁄Ω™
HLQ-⁄Ω™
GMQ-2⁄Ω™
HLQ-3¤Ω¡º
GMQ-flꭧ
HLQ-1flꭧ
GMQ-3
HLQ-3¤Ω¡º
GMQ-°Ω¡º
HLQ-1flꭧ
GMQ-3¤Ω¡º
HLQ-3¤Ω¡º
GMQ-1
HLQ-1flꭧ
GMQ-4
HLQ-5
GMQ-1⁄Ω¢
HLQ-1flꭧ
GMQ-5
HLQ-5
GMQ-1flꭧ
HLQ-1flꭧ
GMQ-6⁄Ω¢
HLQ-8
GMQ-2
HLQ-3¤Ω¡º
—
—
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
6.48
.255
16.13
.635
18.80
.740
Fuse
Rev. A
C
L
MOUNTING HOLE
Electrical Ratings for Type GMQ Fuses and
Rejection Style Carriers
12-18-98
SB98107
21.59
.850
10.41
.410
Keyhole Punch
General Information:
• HLQ carrier comes with 6∑ of #18 red insulated solid copper
wire attached to the line side.
• Customer inserts a #18 insulated solid copper wire into load
side receptacle.
• Size of type GMQ fuses varies with ampere ratings.
• Mounts in type HLQ size rejection (size limiting) carrier
(prevents overfusing).
• Fuse and knob are an integral one-piece unit. There are no
replacement knobs (caps).
• Units can be panel-mounted with a separate steel clip
(BK/A-104).
Form No. GMQ
Page 1 of 2
BIF Doc #2030
Bussmann®
Specialty Fuse
GMQ
& HLQ
Time-Delay, Rejection Style
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
100
AMPERE
RATING
10
200
.1
1
CURRENT IN AMPERES
200
.01
100
.01
10
.1
.1
.1
100
1
10
1
1
TIME IN SECONDS
10
TIME IN SECONDS
5
7
3
3.2
4
1
1.6
2
.5
.3
100
.2
Time-Current Characteristic Curves–Average Melt
CURRENT IN AMPERES
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-18-98
SB98107
Rev. A
Form No. GMQ
Page 2 of 2
BIF Doc #2030