ETC 240A25

SOLID-STATE RELAYS
DATA SHEET
page 1/12
Form 859-990514
Overview
In 1974, Opto 22 introduced the first liquid epoxy-filled
line of power solid-state relays (SSR). This innovation in
SSR design greatly improved the reliability and reduced the
cost of manufacturing. At that time, we also incorporated
into our manufacturing process 100% testing of every relay
produced under full load conditions. By 1978, Opto 22 had
gained such a reputation for reliability that we were recognized
as the world’s leading manufacturer of solid-state relays. Through
continuous manufacturing improvements and the same 100%
testing policy established 22 years ago, Opto 22 is still recognized
today for the very high quality and reliability of its complete line
of solid-state relays.
Index
Power Series
Page
Description
Z Series
1
Introduction
2
All Models: General Specifications
3
120/240 Volt AC Power Series: General Specifications
4
120/240 Volt AC Power Series: Surge Current Data,
Thermal Data, and Dimensions
5
480/575 Volt AC Power Series: General Specifications
6
120/240 Volt AC Power Series Plastic Package
(Z Series): General Specifications
7
AC Power Printed Circuit Series: General Specifications
8
DC Switching Series: General Specifications
APPLICATION TIPS
9
Heat Sink Calculation, Duty Cycle Calculation
10
Transformer Loads, Solenoid Loads, and Lamp Loads
11
Solid-State Relays in Series, Lamp Loads, Heater Loads
12
Motor Loads
P Series
MP Series
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
DATA SHEET
SOLID-STATE RELAYS
page 2/12
Form 859-990514
Specifications
All Models
• 4,000 V optical isolation input to output
• Zero voltage turn-on
• Turn-on time: ½ cycle maximum
• Turn-off time: ½ cycle maximum
• Operating frequency: 25 to 65 Hz (operates at 400 Hz with six times off-state leakage)
• Coupling capacitance input to output: 8 pF maximum
• DV/DT Off-state: 200 volts per microsecond
• DV/DT commutating: snubbed for rated current at 0.5 power factor
• UL recognized
• CSA certified
• CE component
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 3/12
Form 859-990514
Specifications
AC Power Series - 120/240 Volt
Opto 22 provides a full range of power series relays with a wide variety of voltage
(110–575) and current options (3–45 amps). All Power Series relays feature 4,000 volts of
optical isolation and have a high PRV rating.
Model
Number
Nominal
1 cycle
Nominal Nominal
Signal
Surge
AC Line Current
Input
Rating (Amps) Resistance
Voltage (Amps)
Peak
(Ohms)
Signal
Pick-up
Voltage
Peak
Maximum Off-State Operating I2t Rating
Signal
Output
Leakage Voltage
Drop-out Repetitive
t=8.3
Voltage
Voltage
(mA)
Range
Voltage Maximum
(ms)
Drop
Maximum (Volts AC)
Isolation
Voltage
θ jc*
Dissipation
(°C/Watt) (Watts/Amp)
120D3
120
3
85
1000
3VDC
(32V allowed)
1 VDC
600
1.6 volts
2.5mA
12-140
30
4,000VRMS
11
1.7
120D10
120
10
110
1000
3VDC
(32V allowed)
1 VDC
600
1.6 volts
7 mA
12-140
50
4,000VRMS
1.3
1.6
1 VDC
600
1.6 volts
7 mA
12-140
250
4,000VRMS
1.2
1.3
120D25
120
25
250
1000
3VDC
(32V allowed)
120D45
120
45
650
1000
3VDC
(32V allowed)
1 VDC
600
1.6 volts
7 mA
12-140
1750
4,000VRMS
0.67
0.9
1 VDC
600
1.6 volts
5 mA
24-280
30
4,000VRMS
11
1.7
240D3
240
3
85
1000
3VDC
(32V allowed)
240D10
240
10
110
1000
3VDC
(32V allowed)
1 VDC
600
1.6 volts
14 mA
24-280
50
4,000VRMS
1.3
1.6
1 VDC
600
1.6 volts
14 mA
24-280
250
4,000VRMS
1.2
1.3
240D25
240
25
250
1000
3VDC
(32V allowed)
240D45
240
45
650
1000
3VDC
(32V allowed)
1 VDC
600
1.6 volts
14 mA
24-280
1750
4,000VRMS
0.67
0.9
1 VDC
800
1.6 volts
12 mA
24-420
250
4,000VRMS
1.2
1.3
380D25
380
25
250
1000
3VDC
(32V allowed)
380D45
380
45
650
1000
3VDC
(32V allowed)
1 VDC
800
1.6 volts
12 mA
24-420
1750
4,000VRMS
0.67
0.9
10 VAC
600
1.6 volts
7 mA
12-140
50
4,000VRMS
1.3
1.6
120A10
120
10
110
33K
85 VAC
(280 allowed)
120A25
120
25
250
33K
85 VAC
(280 allowed)
10 VAC
600
1.6 volts
7 mA
12-140
250
4,000VRMS
1.2
1.3
240A10
240
10
110
33K
85 VAC
(280 allowed)
10 VAC
600
1.6 volts
14 mA
24-280
50
4,000VRMS
1.3
1.6
240A25
240
25
250
33K
85 VAC
(280 allowed)
10 VAC
600
1.6 volts
14 mA
24-280
250
4,000VRMS
1.2
1.3
240A45
240
45
650
33K
85 VAC
(280 allowed)
10 VAC
600
1.6 volts
14 mA
24-280
1750
4,000VRMS
0.67
0.9
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110°C.
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 4/12
Form 859-990514
Specifications:
AC Power Series - 120/240 Volt (Continued)
Thermal Ratings
Surge Current Data
Time
Time* 3-Amp 10-Amp 25-Amp 45-Amp
Peak
Peak
Peak
Peak
(Seconds) (Cycles) Amps
Amps
Amps
Amps
0.017
1
85
110
250
650
0.050
3
66
85
175
420
0.100
6
53
70
140
320
0.200
12
45
60
112
245
0.500
30
37
50
80
175
1
60
31
40
67
134
2
120
28
33
53
119
3
180
27
32
49
98
4
240
26
31
47
95
5
300
25
30
45
91
10
600
24
28
42
84
Note: *60 HZ.
Dimensional Drawings
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 5/12
Form 859-990514
Specifications
AC Power Series - 480/575 Volt
DC SERIES: The DC Series delivers isolated DC control to large OEM customers
worldwide.
AC SERIES: The AC Series offers the ultimate in solid-state reliability. All AC power
series relays feature a built-in snubber and zero voltage turn-on. Transient proof models
offer self-protection for noisy electrical environments.
Nominal 1 cycle
Nominal
Peak
Maximum Off-State Operating
Signal
Signal
Current Surge Signal Input Pick-up Drop-out Repetitive Output
Leakage
Voltage
Rating (Amps) Resistance Voltage Voltage
Voltage
Voltage
(mA)
Range
(Amps)
Peak
(Ohms)
Maximum
Drop
Maximum (Volts AC)
I2t Rating
t=8.3
(ms)
Model
Number
Nominal
AC Line
Voltage
480D10-12
480
10
110
1000
3VDC
(32V
Allowed)
1 VDC
1200
3.2 volts
11 mA
100-530
50
4,000VRMS
1.2
2.5
480D15-12
480
15
150
1000
3VDC
(32V
Allowed)
1 VDC
1200
3.2 volts
11 mA
100-530
50
4,000VRMS
1.2
2.5
480D25-12
480
25
250
1000
3VDC
(32V
Allowed)
1 VDC
1000
1.6 volts
11 mA
100-530
250
4,000VRMS
1.3
1.3
480D45-12
480
45
650
1000
3VDC
(32V
Allowed)
1 VDC
1000
1.6 volts
11 mA
100-530
1750
4,000VRMS
0.67
0.9
575D15-12
575
15
150
1000
3VDC
(32V
Allowed)
1 VDC
1200
3.2 volts
15 mA
100-600
90
4,000VRMS
1.2
2.5
575D45-12
575
45
650
1000
3VDC
(32V
Allowed)
1 VDC
1000
1.6 volts
15 mA
100-600
1750
4,000VRMS
0.67
0.9
Isolation
θjc*
Dissipation
Voltage (°C/Watt) (Watts/Amp)
Note: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110°C.
Dimensional
Drawings
Thermal Ratings
Surge Current Data
Time Time*** 10-Amp 15-Amp 25-Amp 45-Amp
Peak
Peak
Peak
Peak
Second (Cycles) Amps
Amps
Amps
Amps
0.017
1
110
150
250
650
0.050
3
85
140
175
420
0.100
6
70
110
140
320
0.200
12
60
90
112
245
0.500
30
50
70
80
175
1
60
40
55
67
134
2
120
33
49
53
119
3
180
32
47
49
98
4
240
31
43
47
95
5
300
30
40
45
91
10
600
28
35
42
84
Note: ***60 HZ
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 6/12
Form 859-990514
Specifications
AC Power Series - 120/240 Volt
Plastic Package (z series)
The Z Series employs a unique heat transfer system that makes it possible
for Opto 22 to deliver a low-cost, 10-amp, solid-state relay in an all-plastic case.
The push-on tool-free quick-connect terminals make the Z Series ideal for highvolume OEM applications.
Model
Number
Nominal
1 cycle
Nominal Nominal
Signal
Surge
AC Line Current
Input
Voltage Rating (Amps) Resistance
(Amps) Peak
(Ohms)
Signal
Pick-up
Voltage
Signal
Drop-out
Voltage
Peak
Maximum Off-State Operating
Repetitive Output
Leakage
Voltage
Voltage
Voltage
(mA)
Range
Maximum
Drop
Maximum (Volts AC)
I2t
Rating
t=8.3
(ms)
Isolation
Voltage
θjc*
Dissipation
(°C/Watt) (Watts/Amp)
Z120D10
120
10
110
1000
3VDC
(32V
allowed)
1 VDC
600
1.6 volts
6 mA
12-140
50
4,000
VRMS
4
1
Z240D10
240
10
110
1000
3VDC
(32V
allowed)
1 VDC
600
1.6 volts
12 mA
24-280
50
4,000
VRMS
4
1
Notes: θ jc* = Thermal resistance junction to base. Maximum junction temperature is 110°C.
Dimensional Drawings
Current vs. Ambient Ratings
Surge Current Data
Time
Second
Time***
(Cycles)
Peak
Amps
0.017
1
110
0.050
3
85
0.100
6
70
0.200
12
60
0.500
30
50
1
60
40
2
120
33
3
180
32
4
240
31
5
300
30
10
600
28
Note: ***60 HZ
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 7/12
Form 859-990514
Specifications
AC Power - Printed Circuit Package (P & MP Series)
Model
Number
1 cycle
Nominal
Nominal Nominal
Current Surge Signal Input
AC Line Rating (Amps) Resistance
Voltage
Amps
Peak
(Ohms)
Signal
Pick-up
Voltage
Peak
Maximum Off-State Operating
Signal Repetitive
Output
Leakage
Voltage
Drop-out Voltage
Voltage
mA
Range
Voltage
Maximum
Drop
Maximum (Volts AC)
I2 t
Rating
t=8.3
(ms)
Isolation
Voltage
Dissipation
θjc*
°C/Watt Watts/Amp
MP120D2
or P120D2
120
2
20
1000
3VDC**
(32V
allowed)
1 VDC
600
1.6 volts
5 mA
12-140
2
4,000 VR M S
20
1.2
MP120D4
or P120D4
120
4
85
1000
3VDC**
(32V
allowed)
1 VDC
600
1.6 volts
5 mA
12-140
30
4,000 VR M S
6.5
1.2
MP240D2
or P240D2
240
2
20
1000
3VDC**
(32V
allowed)
1 VDC
600
1.6 volts
5 mA
24-280
2
4,000 VR M S
20
1.2
MP240D4
or P240D4
240
4
85
1000
3VDC**
(32V
allowed)
1 VDC
600
1.6 volts
5 mA
24-280
30
4,000 VR M S
6.5
1.2
1000
3VDC∗∗
(32V
allowed)
1 VDC
800
1.6 volts
5 mA
24-420
30
4,000 VR M S
6.5
1.2
MP380D4
380
4
85
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110°C.
** = MP Series 24 volts maximum.
Surge Current Data
2-Amp 4-Amp
Time
Time* P or MP P or MP
Second (Cycles) Peak
Peak
Amps
Amps
0.017
1
20
85
0.050
3
18
66
0.100
6
15
53
0.200
12
11
45
0.500
30
9
37
1
60
8.5
31
2
120
8
28
3
180
7.5
27
4
240
7
26
5
300
6.5
25
10
600
6
24
Model
P240D4
Model
MP240D4
Note: *60 HZ
Dimensional Drawings
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 8/12
Form 859-990514
Description
DC Switching Series
MP Series
Power Series
P Series
Specifications
DC60P or
DC60MP
DC200P or
DC200MP
DC60S-3
DC60S-5
Operating
Voltage Range
5-60 VDC
5-200 VDC
5-60 VDC
5-60 VDC
Forward Voltage
Drop
1.5 volts
at 3 amps
1.5 volts
at 1 amp
1.5 volts
at 3 amps
1.5 volts
at 5 amps
Nominal Current
Rating
3 amps
1 amp
3 amps
5 amps
Off-State
Blocking
60 VDC
250 VDC
60 VDC
60 VDC
Signal Pickup
Voltage
3 VDC
32 Volts*
allowed
3 VDC
32 Volts*
allowed
3 VDC
32 Volts
allowed
3 VDC
32 Volts
allowed
Signal Dropout
Voltage
1 VDC
1 VDC
1 VDC
1 VDC
Signal Input
Impedance
Dimensional
Drawings
1,000 ohms 1,000 ohms 1,000 ohms 1,000 ohms
1 Second Surge
5 amps
2 amps
5 amps
10 amps
Operating Temp.
Range
-40° C to
100° C
-40° C to
100° C
-40° C to
100° C
-40° C to
100° C
Isolation Voltage
Thermal Ratings
4,000 VRMS 4,000 VRMS 4,000 VRMS 4,000 VRMS
Off-state
Leakage
1 mA
maximum
1 mA
maximum
1 mA
maximum
1 mA
maximum
Package Type
P/MP
series
P/MP
series
Power
series
Power
series
Note: *MP series maximum allowed control signal 24 VDC.
Dimensional Drawings
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
DATA SHEET
SOLID-STATE RELAYS
page 9/12
Form 859-990514
Applications
Tips
Heat Sink Calculation
Like all semiconductor devices, SSR current
ratings must be based on maximum junction
temperature. All Opto 22 SSRs operate
conservatively at maximum junction temperatures
of 110° C. Determining an adequate heat sink
for a given SSR conducting a given current is
very simple.
Note: Thermally conductive grease must be used
between the relay base and the heat sink.
Sample Calculation Given:
120-Volt, 20-Amp Load
50° C Ambient Air
Choose Model 120D25 SSR.
Calculate dissipation as: 20 amps x 1.3 Watts per amp = 26 Watts
Calculate temperature rise junction to SSR base as: 26 Watts x 1.2° C per Watt = 31.2° C
Calculate allowable temperature of heat sink by subtracting 31.2° C from 110° C allowable junction temperature:
110° C-31.2 = 78.8° C
The heat sink is in a 50°C ambient, therefore, allowable temperature rise on heat sink is: 78.8° C-50° C = 28.8° C
If heat sink is allowed to rise 28.8° C above ambient, then the thermal resistance of the heat sink is simply the 28.8° C rise divided by the 26
Watt. Any heat sink having a thermal resistance less than 1.1° C per Watt will be adequate.
Duty Cycle Calculation
When solid-state relays are operated in an on/off mode, it may be advantageous to calculate the RMS value of the current through the SSR
for heat sinking or determining the proper current rating of the SSR for the given application.
IRMS = RMS value of load or SSR
T1 = Time current is on
T2 = Time current is off
ION = RMS value of load current during on period
2
IRMS =
(ION) x T1
T1 + T2
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 10/12
Form 859-990514
Applications
Tips (Continued)
Transformer Loads
Solenoid Valve and Contactor Loads
Careful consideration should be given to the selection
of the proper SSR for driving a given transformer. Transformers
are driven from positive saturation of the iron core to negative
saturation of the core each ½ cycle of the alternating
voltage. Large inrush currents can occur during the first ½ cycle
of line voltage when a zero voltage SSR happens to turn on
during the positive ½ cycle of voltage when the core is
already in positive saturation. Inrush currents greater than
10 times rated transformer current can easily occur.
The following table provides a guide for selecting the
proper SSR for a given transformer rating.
All Opto 22 SSRs are designed to drive inductive loads such as solenoid
valves and electromechanical contactors. The built-in snubber in each SSR
assures proper operation into inductive loads. The following table is a
guide in selecting an SSR to drive a solenoid or contactor.
120-Volt Transformers
SSR MODEL
TRANSFORMER
120-Volt Coils
SSR CURRENT
RATING
SOLENOID
CONTACTOR
2-Amp
1-Amp
NEMA Size 4
4-Amp
3-Amp
NEMA Size 7
240-Volt Coils
SSR CURRENT
RATING
SOLENOID
CONTACTOR
2-Amp
1-Amp
NEMA Size 7
4-Amp
3-Amp
NEMA Size 7
P or MP 120D2
100 VA
Z120D10
500 VA
120D3
100 VA
Control Current Calculation
P or MP 120D4
250 VA
120D10 or 120A10
500 VA
120D25 or 120a25
1 KVA
120D45
2 KVA
All Opto 22 DC controlled SSRs have a control circuit consisting of 1000 ohms in
series with an LED. Since 3 volts is required to turn on any SSR, the maximum current
required is (3 volt - 1 volt) divided by 1000 ohms which equals 2.0 mA. The 1 volt is subtracted
from the 3 volt signal because 1 volt is dropped across the LED. For higher control voltages,
an external resistor can be added in series with the control voltage to limit the control
current. To limit the control current to 2 mA, calculate the external resistor RC = 500 (EC- 3)
where EC = the control voltage.
240-Volt Transformers
P or MP240D2
200 VA
7240D10
1 KVA
120D3
200 VA
P or MP240D4
500 VA
240D10 or 240A10
1 KVA
240D25 or 240A25
2 KVA
240D45
4 KVA
The DC control voltage range is 3–32 VDC. To calculate the control current for any
voltage within the 3–32 VDC range, use the formula:
IC =
EC - 1
1000
where RC = zero.
480-Volt Transformers
SSR MODEL
TRANSFORMER
480D10-12
5-Amp Primary
480D15-12
5-Amp Primary
With a 5V control signal,
IC =
5-1
1000
= 4 mA.
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 11/12
Form 859-990514
Applications
Tips (Continued)
Solid-State Relays In Series
In applications requiring greater current rating at higher voltage,
two Opto 22 SSRs may be operated in series for double the
voltage rating. The built-in snubber in each SSR assures proper
voltage sharing of the two SSRs in series. In the diagram below,
two 240-volt, 45-amp SSRs are connected in series for operation
on a 480-volt line. The control is shown with a parallel hook-up
but it should be noted that a serial connection can also be
implemented.
Lamp Loads
Heater Loads
Since all Opto 22 SSRs are zero voltage switching, they
are ideal for driving incandescent lamps because the
initial inrush current into a cold filament is reduced.
The life of the lamp is increased when switched by a
zero voltage turn on SSR. The following table is a guide
to selecting an Opto 22 SSR for switching a given
incandescent lamp.
Care should be taken in selecting a SSR for driving a heater load if
the load is cycled on and off in a continuous manner as might occur in
a temperature control application. Constant cycling can cause thermal
fatigue in the thyristor chip at the point where the chip bonds to the
lead frame. Opto 22 employs a thick copper lead frame for mounting
the SCR chips in the power series SSRs to eliminate thermal fatigue
failures. In addition, Opto 22 recommends operating any SSR at 75%
rated current for cycling heater loads to ensure complete reliability.
120 Volt Lamps
SSR CURRENT RATING
LAMP RATING
2-Amp
100 Watt
4-Amp
400 Watt
10-Amp
1 Kilowatt
25-Amp
45-Amp
The following table is a guide to selecting the proper SSR for a given
heater load.
2 Kilowatt
Nominal SSR
Current Rating
Maximum
Recommended
Heater Current
3 Kilowatt
2-Amp
1½-Amp
4-Amp
2½-Amp
10-Amp
7½-Amp
240 Volt Rating
SSR CURRENT RATING
LAMP RATING
2-Amp
200 Watt
25-Amp
18-Amp
4-Amp
800 Watt
45-Amp
35-Amp
10-Amp
2 Kilowatt
10 480V
8-Amp
25-Amp
4 Kilowatt
10 480V
8-Amp
45-Amp
6 Kilowatt
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
SOLID-STATE RELAYS
DATA SHEET
page 12/12
Form 859-990514
Applications
Tips (Continued)
Single-Phase Reversing Motor Control
The circuit diagram illustrates a typical 1 Ø motor winding inductance and the phase shift
capacitor can cause twice line voltage to appear across the open SSR. A 240-volt SSR should be
used for a 120-Volt line. During the transition period when one SSR is turned on and the other
SSR is going off, both SSRs may be on. In this case, the capacitor may discharge through the
two SSRs, causing large currents to flow, which may destroy the SSRs. The addition of RL as
shown will protect the SSRs from the short circuit capacitor discharge current.
CALCULATE RL as: RL =
1.4 EAC
10 x SSR full load rating
The resistors are unnecessary if the
control circuit is designed to ensure
one SSR is off before the other SSR is
on.
EXAMPLE: 10 amp SSR
120 V AC Line
RL =
1.4 x 120
10 x 10
Three-Phase Reversing Motor Control
Three-Phase Motor Control
Three-phase motors may
be controlled by solid-state
relays as shown. A third
SSR as shown is optional,
but not necessary. The
control windings may be
connected in series or
parallel. Care should be
taken to ensure that surge
current drawn by the motor
does not exceed surge
current rating of the SSR.
240-Volt 3θ
θ Motors
SSR MODEL
= 1.7 ohm
MOTOR
Z240D25
1/3 HP
Z240D10
3/4 HP
240D10
3/4 HP
240A10
3/4 HP
240D25
2 HP
240A25
2 HP
240D45
3 HP
480-Volt 3θ
θ Motors
Three-phase reversing motor control can be implemented with four
SSRs as shown in the connection diagram. The SSRs work in pairs
with SSR1 and SSR3 operated for rotation in one direction and SSR2
and SSR4 operated for rotation in the reverse direction. The
resistor R1 as shown in the connection diagram protects against
line-to-line shorts if SSR1 and SSR4 or SSR3 and SSR2 are on at
the same time during the reversing transition period. Use the
following table as a guide to the proper selection of an SSR for
this application.
Opto 22
Relay
Motor
Full Load
Rating
3-Amp
1.25-Amp
4 ohm 50 W
8 ohm 50 W
10-Amp
5-Amp
1 ohm 100 W
2 ohm 100 W
Resistor for
120V line
Resistor for
240V line
SSR MODEL
MOTOR
25-Amp
8-Amp
.5 ohm 100 W
1 ohm 100 W
480D10-12
1-½ HP
45-Amp
16-Amp
.25 ohm 150 W
.5 ohm 150 W
480D15-12
1-½ HP
15-Amp
5-Amp
1 ohm 100 W
2 ohm 100 W
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: [email protected] • FaxBack: (800)474-OPTO
All products and/or company names throughout this datasheet are generally trademarks or registered trademarks of their respective companies.