ETC G24-1

9
Replacement Relays for I/O Blocks and Bases
Use Relays to Fill I/O Bases and to Replace Relays Supplied with I/O Blocks
3 RELAY SERIES COMPATIBILITY WITH I/O BLOCKS AND BASES
Relay series
Applicable I/O blocks and bases
G2R electromechanical
G70A output base, G730-RID and G730-ROC04 I/O modules
G3R solid state
G70A output base, G730-RIA I/O modules
G3RZ power MOSFET relay
G730-ZIA, G730-ZID and G730-ZOM I/O modules
G7T electromechanical
P7TF relay bases, G7TC relay blocks
G3TA solid state
P7TF relay bases, G7TC relay blocks
G6D electromechanical
G70D and G70D-R6-B7A relay blocks, SRT2-ROC08/-ROC16 output modules, G730
G3DZ power MOSFET relay
G70D and G70D-R6-B7A relay blocks, SRT2-ROF output modules, G730-AOM/-ZIM/-ZOM I/O modules
G2R Power PCB Relay
3 ORDERING INFORMATION
Applicable block base
G70A relayy output base,,
G730 RID and
G730-RID
d G730-ROC04
G730 ROC04 I/O
modules (Refer to G70A and G730-R
data sheets for specific
s ecific models)
Classification
Applicable load
Rated input voltage
Part number
Input relay
21.8 mA at 24 VDC
24 VDC
Output relayy
10 A at 250 VAC/30 VDC
24 VDC
G2R-1-SND DC24
12 VDC
G2R-1-SND DC12
G2R-1A3-SND DC24V
G2R-13-SND DC24V
3 INPUT RELAYS G2R-1A3-SND AND G2R-13-SND
Coil Ratings
230 VAC
12 VDC
24 VDC
50 Hz
3.7 mA
43.6 mA
21.8 mA
60 Hz
3.1 mA
1,100 ˆ
Rated voltage
Rated current
Coil resistance
30,000 ˆ
275 ˆ
Must operate voltage
80% max. of rated voltage
70% max. of rated voltage
Must release voltage
30% min. of rated voltage
15% min. of rated voltage
Max. voltage
110% of rated voltage
Power consumption
Approx. 0.7 W (60 Hz)
Approx. 0.53 W
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of +15%/ --20% (AC rated current) or .10% (DC coil resistance).
2. LEDs are used for the built-in operation indicator. For models equipped with these indications, the VAC rated current must be
increased by approximately 1 mA; the VDC rated current, by approximately 4 mA.
Replacement Relays
Replacement Relays
3 OUTPUT RELAYS G2R-1-S AND G2R-1-SN
Coil Ratings
Rated voltage
24 VDC
Rated current (50/60 Hz)
21.8 mA
Coil resistance
1,100 ˆ
Coil inductance
Armature OFF
4.27
(H) (ref. value)
Armature ON
8.55
Must operate voltage
70% min. of rated voltage
Must release voltage
15% min. of rated voltage
Max. voltage
110% of rated voltage
Power consumption
Approx. 0.53 W
Contact Ratings
Also refer to Ratings/Characteristics of G70A-ZIM16-5.
Number of poles
1 pole
Load
Resistive load (p.f. = 1)
Inductive load (p.f. = 0.4; L/R = 7 ms)
Rated load
10 A at 250 VAC; 10 A at 30 VDC
7.5 A at 250 VAC; 5 A at 30 VDC
Rated carry current
10 A
Max. operating voltage
380 VAC, 125 VDC
Max. operating current
10 A
Max. switching capacity
2,500 VA, 300 W
Min. permissible load
100 mA at 5 VDC
1,875 VA, 150 W
G3R Solid State Relay
3 ORDERING INFORMATION
Input Relays
Applicable
pp
block
b
base
G70A relayy input
b
base,
G730-RIA
G730 RIA I/O
modules (Refer to
G730 R
G70A and G730-R
data sheets for
specific models)
Isolation
Photocoupler
l
Indicator
Yes
Response
p
speed
d
-----High-speed
g
Logic level
Supply
voltage
4 to
32 VDC
Low-speed
Supply
current
0.1 to
100 mA
A
Rated input
p
voltage
lt
Part number
100 to 240 VAC
G3R-IAZR1SN AC100-240
5 VDC
G3R-IDZR1SN DC5
12 to 24 VDC
G3R-IDZR1SN DC12-24
5 VDC
G3R-IDZR1SN-1 DC5
12 to 24 VDC
G3R-IDZR1SN-1 DC12-24
Output Relays
Applicable block base
G70A relayy output base,,
G730 RIA I/O modules
G730-RIA
d l
(Refer to G70A and
G730-R
G730
R data sheets for
specific models)
2
Isolation
Phototriac
Indicator
Yes
Zero cross
function
Yes
Applicable
output load
Rated
input
2 A at 75 to 264 VAC
5 to
24 VDC
No
Photocoupler
------
Part number
G3R-OA202SZN DC5-24
G3R-OA202SLN DC5-24
2 A at 4 to 60 VDC
G3R-ODX02SN DC5-24
1 A at 40 to 200 VDC
G3R-OD201SN DC5-24
Replacement Relays
Replacement Relays
3 RATINGS
Input Relays
Input Ratings
Rated voltage
Part number
Operating voltage
Input current
Must operate
voltage
Must release
voltage
G3R-IAZR1SN
100 to 240 VAC
60 to 264 VAC
15 mA max.
60 VAC max.
20 VAC min.
G3R-IDZR1SN
5 VDC
4 to 6 VDC
8 mA max.
4 VDC max.
1 VDC min.
12 to 24 VDC
6.6 to 32 VDC
6.6 VDC max.
3.6 VDC min.
5 VDC
4 to 6 VDC
4 VDC max.
1 VDC min.
12 to 24 VDC
6.6 to 32 VDC
6.6 VDC max.
3.6 VDC min.
G3R-IDZR1SN-1
Output Ratings
Part number
Logic level supply voltage
G3R-IAZR1SN
Logic level supply current
4 to 32 VDC
0.1 to 100 mA
G3R-IDZR1SN
G3R-IDZR1SN-1
Output Relays
Input Ratings
Part number
G3R-OA202SZN
Rated voltage
Operating voltage
5 to 24 VDC
4 to 32 VDC
G3R-OA202SLN
G3R-ODX02SN
Input current
15 mA max.
( t 25°C)
(at
Must operate
voltage
Must release
voltage
4 VDC max.
1 VDC min.
8 mA max.
G3R-OD201SN
Output Ratings
Part number
G3R-OA202SZN
Load voltage
Load current (See Note)
Inrush current
75 to 264 VAC
0.05 to 2 A
30 A (60 Hz, 1 cycle)
G3R-ODX02SN
4 to 60 VDC
0.01 to 2 A
8 A (10 ms)
G3R-OD201SN
40 to 200 VDC
0.01 to 1.5 A
8 A (10 ms)
G3R-OA202SLN
Note: The minimum current value is measured at 10°C min.
3 CHARACTERISTICS
Input Relays
Item
G3R-IAZR1SN
G3R-IDZR1SN
G3R-IDZR1SN-1
Operate time
20 ms max.
0.1 ms max.
15 ms max.
Release time
20 ms max.
0.1 ms max.
15 ms max.
Response frequency
10 Hz
1 kHz
10 Hz
Output ON voltage drop
1.6 V max.
Leakage current
5 µA max.
Insulation resistance
100 MΩ min. between input and output
Dielectric strength
4,000 VAC for 1 min between input and output
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude
Shock resistance
1,000 m/s2 (approx. 100G)
Ambient temperature
Operating: --30°C to 80°C (--22°F to 176°F) with no icing
Storage: --30°C to 100°C (--22°F to 212°F) with no icing
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 18 g
3
Replacement Relays
Replacement Relays
Output Relays
Item
G3R-OA202SZN
G3R-OA202SLN
G3R-ODX02SN
Operate time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
2 ms max.
Response frequency
20 Hz
100 kHz
Output ON voltage drop
1.6 V max.
Leakage current
1.5 mA max.
Insulation resistance
100 MΩ min. between input and output
Dielectric strength
4,000 VAC for 1 min between input and output
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude
Shock resistance
1,000 m/s2 (approx. 100G)
Ambient temperature
Operating: --30 to 80 °C (--22°F to 176°F) with no icing
Storage: --30 to 100 °C (--22°F to 212°F) with no icing
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 18 g
G3R-OA201SN
2.5 V max.
1 mA max.
3 ENGINEERING DATA
Load Current vs. Ambient Temperature
Characteristics
Four points mounted
G730-ZOM04 + G3R-OD201SN
(40 to 200 VDC)
Load current (A)
Four points mounted
G730-ZOM04 + G3R-ODX02SN
(4 to 60 VDC)
Load current (A)
Load current (A)
G730-ZOM04 + G3R-OA202SPN
Ambient temperature (°C)
Ambient temperature (°C)
Four points mounted
Ambient temperature (°C)
Note: The above data are for a G730 mounted with four G3Rs.
Inrush Current Resistivity
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
Energizing time (ms)
4
G3R-OD201SN
Inrush current (A. Peak)
G3R-ODX02SN
Inrush current (A. Peak)
Inrush current (A. Peak)
G3R-OA202SPN
Energizing time (ms)
Energizing time (ms)
Replacement Relays
Replacement Relays
G3RZ Power MOSFET Relay
3 ORDERING INFORMATION
Input/Output Relays
Applicable block base
G730-ZIA, G730-ZID and
G730 ZOM I/O bases
G730-ZOM
b
(Refer to G730-R data
sheets for specific models)
Classification
Insulation
method
Indicator
Zero
cross
function
Input relayy or
output
t t relay
l
Photodiode
array
Yes
No
Applicable
output
load
1.0 A at
3 tto 264 VAC/
3 to 125 VDC
Rated
input
voltage
Part number
5 VDC
G3RZ-201SLN DC5
12 VDC
G3RZ-201SLN DC12
24 VDC
G3RZ-201SLN DC24
3 RATINGS
Input/Output Relays
Input Ratings
Part number
G3RZ-201SLN
Rated voltage
Operating voltage
Input impedance
Must operate
voltage
5 VDC
4 to 6 VDC
400 Ω ±20%
4 VDC max.
12 VDC
9.6 to 14.4 VDC
1.1 kΩ ±20%
9.6 VDC max.
24 VDC
19.2 to 28.8 VDC
2.2 kΩ ±20%
19.2 VDC max.
Must release
voltage
1 VDC min.
Output Ratings
Load voltage
3 to 264 VAC, 3 to 125 VDC
Load current
100 µA to 1.0 A
Inrush current
10 A (10 ms)
3 CHARACTERISTICS
Input/Output Relays
Item
G3RZ-201SLN
Operate time
6 ms max.
Release time
10 ms max.
Output ON-resistance
2.4 Ω max.
Leakage current
10 µA max. at 125 VDC
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude
Shock resistance
1,000 m/s2 (approx. 100G)
Ambient temperature
Operating: --30°C to 85°C (--22°F to 185°F) with no icing
Storage: --30°C to 100°C (--22°F to 212°F) with no icing
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 20 g
5
Replacement Relays
Replacement Relays
3 REFERENCE DATA
Load Current vs. Ambient Temperature
Characteristics
Inrush Current Resistivity
Non-repetitive (Keep the inrush current to half the rated
value if it occurs repetitively.)
G3RZ-201SLN
Load current (A)
Inrush current (A. Peak)
G3RZ-201SLN
Ambient temperature (°C)
Energizing time (ms)
Note: The above data are for a G730 mounted with four G3RZs.
G7T Power Relay
3 ORDERING INFORMATION
Applicable block base
Classification
Applicable load
P7TF bases and G7TC I/O blocks
Input relay,
y, AC coil
10 to 100 mA
(Refer to G7TC data sheet for
s ecific models)
specific
Input relay, DC coil
10 to 100 mA
Output relay,
y, DC coil
5A
Rated input voltage
Part number
110/120 VAC
G7T-1122S AC110/120 V
200/220 VAC
G7T-1122S AC200/220V
24 VDC
G7T-1122S DC24V
12 VDC
G7T-1112S DC12V
24 VDC
G7T-1112S DC24V
3 RATINGS
Input/Output Relays
Coil Ratings (Common to Input/Output per Relay)
Rated voltage (V)
Rated current (mA)
50 Hz
60 Hz
Coil
resistance
(S Note
(See
N
1)
Must
operate
Must
release
Maximum
voltage
Percent of rated voltage
Power consumption
per Relay
per 16 Relays
80% max.
30% min.
110%
0.7 VA
11 VA
42
13,000 Ω
48,300 Ω
290 Ω
80% max.
10% min.
110%
0.5 W
8W
21
1,150 Ω
80% max.
10% min.
110%
0.5 W
8W
AC
110/120
220/240
7.5/—
3.7/—
DC
12
DC
24
6.4/7.0
3.2/3.5
Note: 1. The rated current and coil resistance are measured at a coil temperature of +23°C with a tolerance of +15%/--20% for AC rated
current and ±15% for coil resistance.
2. Approx. 4 mA flows into each LED indicator. To calculate the power supply capacity, add the current value of each indicator.
6
Replacement Relays
Replacement Relays
Contact Ratings (Common to Input/Output per Relay)
For input
Classification
For output
Resistive load
(cosϕ=1)
Inductive load (cosϕ=0.4
L/R=7 ms)
Resistive load
(cosϕ=1)
Inductive load (cosϕ=0.4
L/R=7 ms)
Carry current
1A
5A
Switching voltage
250 VAC, 125 VDC
Switching current
1A
0.5 A
5A
2A
Switching power
DC 24 W
DC 12 W
DC 120 W
AC 440 VA
DC 48 W
AC 220 VA
Min. permissible load
100 µA at 1 V
Electrical life
10,000,000 operations
(at 10 mA)
50,000 operations
(at 1 A)
Mechanical life
50,000,000 operations
10 mA at 5 V
2,500,000 operations
(at 10 mA)
20,000 operations
(at 1 A)
1,000,000 operations (under rated load)
3 CHARACTERISTICS: G7T RELAYS
Part number
G7TC-IA16
(Input, AC coil)
G7TC-ID16
(Input, DC coil)
G7TC-OC16 (-1)
(output, DC coil)
LED color
Red
Green
Green
Case color
Transparent red
Transparent green
Transparent
Contact resistance
50 mΩ max.
Operate time
15 ms max.
Release time
15 ms max.
Max. operating
p
g
f
frequency
Mechanical limit
18,000 operations/hour
At rated load
1,800 operations/hour
Insulation resistance
100 MΩ at 500 VDC
Dielectric
strength
t
th
Between coil and contact
2,000 VAC, 50/60 Hz for 1 minute
Between same polarity
contacts
1,000 VAC, 50/60 Hz for 1 minute
Between paired connectors
250 VAC, 50/60 Hz for 1 minute
G7TC-OC08 (-1)
(output, DC coil)
Malfunction vibration
10 to 55 Hz with 1.0-mm double amplitude
Malfunction shock
200 m/s2
Noise immunity
Noise level: 1.5 kV; pulse width: 100 ns to 1 µs
Rated voltage between positive and negative
terminal blocks
Rated voltage of controller’s (PLC or
other) input circuit
24 VDC ±5%
Rated current between positive and negative
terminal blocks
Input circuit current of controller (PLC or
other) x number of ON points
24 VDC: 25 mA x number of ON points
Cable length
g
To controller
5 m max. (reference value)
To I/O devices
50 m max. (reference value, for 2-mm2
CVV cable)
Ambient operating temperature
0°C to 55°C (32°F to 131°F)
Ambient operating humidity
35% to 85%
I/O terminal tightening torque
8 to 12 kg : cm
Coil surge absorber
Variable resistor
Diode (1 A, 400 V)
Weight
Approx. 640 g
Approx. 630 g
Dependent on load
Approx. 670 g
Approx. 350 g
UL and CSA Standards
Standard G7TC I/O Blocks, except for the G7TC-OC16-1 and the G7TC-OC08(-1), have met UL and CSA standards (UL file no. E41643; CSA
file no. LR31928).
Note that the following UL- and CSA-qualifying ratings differ from the performance characteristics of the individual models:
Model
Coil ratings
Contact ratings
G7TC-ID16, G7TC-IA16
10 mA/point, 24 VDC
250 VAC max.
G7TC-OC16
Coil drive current, 24 VDC
Inductive load: 10 A, 250 VAC
Resistive load: 10 A, 30 VDC
Rated horsepower: 1/2 HP, 240 VAC
7
Replacement Relays
Replacement Relays
3 ENGINEERING DATA
G7T Relays
G3TA Solid State Relay
3 ORDERING INFORMATION
Applicable block base
Classification
P7TF bases and G7TC I/O blocks
(R f tto G7TC data
(Refer
d t sheet
h t for
f specific
ifi
models)
Applicable
load
Rated input
voltage
Part number
Input relay,
relay AC coil
25 mA
100-240 VAC
G3TA-IAZR02S AC100/240V
Input relay, DC coil
25 mA
5-24 VDC
G3TA-IDZR02S DC5-24V
Output relay,
y, DC coil
2A
12 VDC
G3TA-ODX02S 12VDC
2A
24 VDC
G3TA-ODX02S DC24V
1A
24 VDC
G3TA-OD201S DC24V
Operating
p
g
voltage
lt
Input current
3 RATINGS: G3TA SOLID STATE RELAYS
Input Relay
Input Ratings
Part number
Rated voltage
G3TA-IAZR02S AC100/240V
100 to 240 VAC
80 to 264 VDC
G3TA-IDZR02S DC5-24V
5 to 24 VDC
4 to 32 VDC
Voltage level
Must operate
voltage
5 mA max.
Must release
voltage
80 VAC max.
10 VAC min.
4 VDC max.
1 VDC min.
Output Ratings
Part number
G3TA-IAZR02S AC100/240V
G3TA-IDZR02S DC5-24V
8
Logic level supply
voltage
4 to 32 VDC
Output breakdown
voltage
32 VDC max.
Output current
25 mA max.
Output current
(load current)
0.1 to 25 mA
Replacement Relays
Replacement Relays
Output Relay
Input Ratings
Part number
Rated voltage
Operating
p
g
voltage
lt
Voltage level
Input
p
iimpedance
d
Must operate
voltage
G3TA-OA202SZ DC12V
12 VDC
9.6 to 13.2 VDC
0.9 kΩ±20%
9.6 VDC max.
G3TA-OA202SZ DC24V
24 VDC
19.2 to 26.4 VDC
1.7 kΩ±20%
19.2 VDC max.
G3TA-ODX02S DC24V
12 VDC
9.6 to 13.2 VDC
3.5 kΩ±20%
9.6 VDC max.
24 VDC
19.2 to 26.4 VDC
6.5 kΩ±20%
19.2 VDC max.
24 VDC
19.2 to 26.4 VDC
6.4 kΩ±20%
19.2 VDC max.
G3TA-OD201S DC24V
Must release
voltage
2 VDC min.
Output Ratings
Part number
Applicable load
Rated load voltage
Load voltage
G3TA-OA202SZ
100 to 240 VAC
75 to 264 VAC
G3TA-OA202SL
100 to 240 VAC
75 to 264 VAC
G3TA-ODX02S
5 to 48 VDC
G3TA-OD201S
48 to 200 VDC
Load current (See Note)
Inrush current
0.05 to 2 A
30 A (60 Hz, 1 cycle)
4 to 60 VDC
0.01 to 2 A
12 A (10 ms)
40 to 200 VDC
0.01 to 1 A
6 A (10 ms)
Note: The minimum current value is measured at 10°C min.
3 CHARACTERISTICS: G3TA SOLID STATE RELAYS
Input Relay
Item
G3TA-IAZR02S
G3TA-IDZR02S
Operate time
20 ms max.
0.5 ms max.
Release time
20 ms max.
0.5 ms max.
Output ON voltage drop
1.6 V max.
Leakage current
5 µA max.
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance
Malfunction: 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance
Malfunction: 1,000 m/s2 {approx. 100G}
Ambient temperature
Operating: --30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage: --30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient humidity
Operating: 45% to 85%
Approved standards
UL508 file No. E64562/CSA C22.2 (No. 0, No. 14) file No. LR35535
Weight
Approx. 16 g
Output Relay
Item
G3TA-OA202SZ
G3TA-ODX02S
G3TA-OD201S
Operate time
1/2 of load power source cycle + 1 ms max.
0.5 ms max.
2 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
2 ms max.
2 ms max.
Output ON voltage drop
1.6 V max.
Leakage current
5 mA max. at 200 VAC
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance
Malfunction: 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance
Malfunction: 1,000 m/s2 {approx. 100G}
Ambient temperature
Operating: --30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage: --30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient humidity
Operating: 45% to 85%
Approved standards
UL508 file No. E64562, CSA C22.2 (No. 14) file No. LR3553
Weight
Approx. 23 g
2.5 V max.
1 mA max.
9
Replacement Relays
Replacement Relays
3 MIXING G3TA WITH G7T RELAYS IN THE SAME I/O BLOCK
With up to four G3TA SSRs mounted before
G7T Relays, 2-A loads can be switched.
G3TA
With G3TA SSRs mounted before every other
G7T Relays, 2-A loads can be switched.
G3TA
G7T
G7T
3 ENGINEERING DATA
Load Current vs. Ambient Temperature Characteristics
Single-point mounting
16-point mounting
G3TA-OD201S
Load current (A)
Load current (A)
G3TA-OA202SZ/OA202SL/ODX02S
Single-point mounting
16-point mounting
Ambient temperature (°C)
Ambient temperature (°C)
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
Inrush current (A. Peak)
Inrush current (A. Peak)
Energizing time (ms)
10
G3TA-OD201S
Inrush current (A. Peak)
G3TA-ODX02S
G3TA-OA202SZ
Energizing time (ms)
Energizing time (ms)
Replacement Relays
Replacement Relays
G6D Power Relay
3 ORDERING INFORMATION
Applicable block base
G70D and G70D-R6-B7A output bases, SRT2-ROC08/-ROC16
output
t t modules
d l and
d G730 modules.
d l
(Refer to G70D, G70D-R6-B7A, SRT†-R and G730-R data
sheets for specific models)
Classification
Applicable
load
Rated coil
voltage
Part number
Output relay
5A
5 VDC
G6D-1A DC5
12 VDC
G6D-1A DC12
24 VDC
G6D-1A DC24
3 RATINGS
Coil Ratings
Rated voltage
5 VDC
12 VDC
24 VDC
Rated current
40 mA
16.7 mA
8.3 mA
Coil resistance
125 Ω
720 Ω
2,880 Ω
Must operate voltage (See Note 1)
70% max. of rated voltage
Must release voltage
10% min. of rated voltage
Max. voltage
130% of rated voltage
Power consumption
Approx. 200 mW
Note: 1.
2.
3.
4.
The must operate voltage is 75% or less of the rated voltage if the relay is mounted upside down.
Rated current and coil resistance were measured at a coil temperature of 23EC with a tolerance of á10%.
Operating characteristics were measured at a coil temperature of 23EC.
The maximum allowable voltage is the maximum value of the allowable voltage range for the relay coil operating power supply.
There is no continuous allowance.
Contact Ratings
Load classification
Resistive load (p.f. = 1)
Inductive load (p.f. = 0.40, L/R = 7 ms
Rated load
5 A at 250 VAC, 30 VDC
2 A at 50 VAC, 30 vDC
Carry current
5A
Max. operating voltage
250 VAC, 30 VDC
Max. operating current
5A
Max. switching capacity
1250 VA, 150 W
Min. permissible load
10 mA at 5 VDC
Life expectancy
Mechanical: 20,000,000 operations min. (at 18,000 operations/hr)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load)
100,000 operations min. (5 A at 30 VDC, resistive load)
300,000 operations min. (2 A at 250 VAC, resistive load)
300,000 operations min. (2 A at 30 VDC, resistive load)
(at 1,800 operations/hr)
500 VA, 60 W
3 CHARACTERISTICS
Contact resistance (See Note 2)
100 mΩ max.
Operate time
10 ms max.
Release time
5 ms max.
Insulation resistance
1,000 MΩ min. at 500 VDC
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between coil and contacts
750 VAC, 50/60 Hz for 1 min between contacts of same polarity
Surge withstand voltage
6,000 V, 1.2 x 50 µs between coil and contacts
Vibration resistance
Destruction: 10 to 55 Hz, 1.5-mm double amplitude
Malfunction: 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance
Destruction: 1,000 m/s2
Malfunction: 100 m/s2
Ambient temperature
Operating: --25°C to 70°C (--13°F to 158°F)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 3 g
Note: 1. The above values are initial values.
2. Measurement condition: 1 A at 5 VDC
11
Replacement Relays
Replacement Relays
3 REFERENCE DATA
Life Expectancy
Max. Switching Capacity
3,000
1,000
Switching current (A)
Life expectancy (x 10 3 operations)
5,000
250 VAC/30 VDC resistive load
500
300
100
50
250 VAC/30 VDC inductive load
(cosφ = 0.4, L/R = 7 ms)
30
AC resistive load
DC resistive load
DC inductive load
Switching current (A)
AC inductive
load
(cosφ = 0.4)
Switching voltage (V)
G3DZ Power MOSFET Relay
3 ORDERING INFORMATION
Input/Output Relays
Applicable block base
G70D and G70D-R6-B7A
output bases, SRT2-ROF
output modules and
G730-AOM/-ZIM/-ZOM I/O
modules. (Refer to G70D,
G70D R6 B7A SRT†-R
G70D-R6-B7A,
SRT R
and G730-R data sheets
for specific models)
Classification
Insulation
method
Indicator
Zero
cross
function
Input relay or
output relay
Photodiode
array
No
No
Applicable
output load
100 µA to 0.6 A
5 to 240 VAC/
5 to 100 VDC
Rated
input
voltage
Part number
5 VDC
G3DZ-2R6PL DC5
12 VDC
G3DZ-2R6PL DC12
24 VDC
G3DZ-2R6PL DC24
3 RATINGS
Output Relay
Input Ratings
Rated voltage
Operating voltage
Input impedance
Voltage level
Must operate
5 VDC
4 to 6 VDC
830 Ω ±20%
4 VDC max.
12 VDC
9.6 to 14.4 VDC
2 kΩ ±20%
9.6 VDC max.
24 VDC
19.2 to 28.8 VDC
4 kΩ ±20%
19.2 VDC max.
Must release
1 VDC min.
Output Ratings
Load voltage
3 to 264 VAC, 3 to 125 VDC
12
Load current
100 µA to 0.6 A
Inrush current
6 A (10 ms)
Replacement Relays
Replacement Relays
3 CHARACTERISTICS
Operate time
6 ms max.
Release time
10 ms max.
Output ON-resistance
2.4 Ω max.
Leakage current
10 µA max. at 125 VDC
Insulation resistance
100 mΩ max. at 500 VDC
Dielectric strength
2,500 VDC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude
Shock resistance
1,000 m/s2 (approx. 100G)
Ambient temperature
Operating: --30°C to 85°C (--22°F to185°F) with no icing
Storage: --30°C to 100°C (--22°F to 212vF) with no icing
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 3.1 g
3 ENGINEERING DATA
Load Current vs. Ambient Temperature
Characteristics
Non-repetitive (Keep the inrush current to half the rated value
if it occurs repetitively.)
G3DZ-2R6PL
Load current (A)
Inrush current (A.Peak)
G3DZ-2R6PL
Inrush Current Resistivity
Ambient temperature (°C)
Energizing time (ms)
Note: The above data are for a G730 mounted with 8 or 16 G3DZs.
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
9
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC RIO-1
04/00
Specifications subject to change without notice.