BRAIN DAC51CM24

Timers
Star Delta Timer
Type DAC51
Product Description
Star-delta control relay with two adjustable time ranges:
Star function (0.1 to 600 s) and star to delta function
(50 to 130 ms).
Housing 17.5 mm wide suitable for DIN-rail mounting.
Property
• Time range (Star): 0.1 to 600 s
• Time range (Star to Delta): 50 to 130 ms
• Knob selection of star time range
• Knob adjustable time setting
• Automatic start
• Repeatability: ≤ 0.2%
• Output: 5 A SPDT relay with neutral centre position
• For mounting on DIN-rail in accordance with DIN/EN
50 022
• 17.5mm DIN-rail housing(DIN 43880)
• LED indication for relay status and power supply ON
Type Selection
Mounting
Output
Housing
Supply: 24 to 240 VAC/DC
For DIN-rail
SPDT relay
with neutral
centre position
Mini-D
DAC 51 C M24
Time Specifications
Time ranges (star)
Knob selectable
Star to delta delay
Neutral centre position
Setting accuracy
Repeatability
Time variation
Within rated power supply
Within ambient temperature
Reset
Time and relay
Output Specifications
Output
0.1 to 1 s
1 to 10 s
6 to 60 s
60 to 600s
50 to 130 ms
between star and delta
position
≤ 5%
≤ 0.2%
≤ 0.05%
≤ 0.2%
Power supply interruption
≥ 200 ms
Rated insulation voltage
Contact Ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand
voltage
SPDT relay with neutral
centre position
250 VAC (RMS)
μ
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
< 7200 operations/h
2 kVAC (RMS)
4 kV (1.2/50μs)
Supply Specifications
Power supply
Rated operational voltage
through terminals A1 and A2
M24:
Voltage interruption
Overvoltage cat. III
(IEC 60664, IEC 60038)
Rated operational power
AC Supply
DC Supply
5 VA
1.5 W
24 to 240 VAC/DC
+10% -15%, 45 to 65 Hz
≤ 10 ms
www.dold-relay.com
1
DA#51
General Specifications
Power ON delay
Power OFF delay
Indication for
Power supply ON
Output relays ON
≤ 100 ms
≤ 100 ms
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
LED, green
LED, yellow (flashing when
timing)
(EN 60529)
IP 20
3 (IEC 60664)
-20 to 60 °C, R.H. < 95%
-30 to 80 °C, R.H. < 95%
Timer Specifications
According to EN 61812-1
Housing
Dimensions
Material
Weight
Screw terminals
Tightening torque
17.5 x 81 x 67.2 mm
PA66
85 g
Max 0.5 Nm according to
IEC EN 60947
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
Approval
CE Marking
EMC
Immunity
Emission
Mode of Operation
Time Setting
The output relay is normally in the neutral position.
When the power supply is applied,the relay switches to
star position(pin 16), and the star period starts.
At the end of the set time period,the relay returns to the
neutral center position and the set delay between star
and delta period starts.
At the end of the star to delta delay(adjustable from 50 to
130 ms), the relay switches in delta position(pin 18) and
does not release until the power supply is interrupted for
at least 200ms.
If the power supply is interrupted for more than 200ms
before the star time period has expired,the relay does not
operate and the time circuit is set to zero. The relay is
ready for a new time period.
Upper knob:
Setting of star time range
Centre knob:
Star time setting on relative
scale: 1 to 10 with respect
to the chosen range.
Lower knob:
Star to delta time setting (50
to 130 ms)
Operation Diagram
≤ 10 ms
ON
OFF
ON
OFF
Wiring Diagram
Dimensions
67.2
17.5
18.7
2
16 18 A2
2
www.dold-relay.com
45
3 5.5
81
A1 15 Y1