Series H12 25-90Amp • 480 Vac • AC Output • 1200 Volt Blocking High voltage relays use IC driven circuits for switching loads up to 660 VAC. All models come with 1200 Volts blocking and are available with either AC or DC input (coil) control. Types H12CA, H12CD and H12WD are snubberless (reduced leakage current). Manufactured in Crydom’s ISO 9002 Certified facility for optimum product performance and reliability. • Panel Mount • Up to 660 Vac • Zero Voltage Switching and Random Turn-On • SCR Output MODEL NUMBERS DC CONTROL H12CD4850 H12CD4890 H12WD4850 H12WD4890 A C C ONTROL H12CA4850 H12CA4890 H12D4825 H12D4850 H12D4875 H12D4890 OUTPUT SPECIFICATIONS ➀ 48-660 48-660 48-530 48-530 48-530 48-530 Max. Load Current ➂ [Arms] 50 90 25 50 75 90 Min. Load Current, [mArms] 150 150 150 150 150 150 Transient Overvoltage [Vpk] 1200 1200 1200 1200 1200 1200 Max. Surge Current, (16.6ms) [Apk] 625 1200 250 625 1000 1200 Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 1.6 1.6 1.6 Thermal Resistance Junction to Case (RθJC) [˚C/W] .63 .28 1.02 .63 .31 .28 1620 6000 260 1620 4150 6000 Max. Off-State Leakage Current @ Rated Voltage [mArms] 1.0 1.0 10 10 10 10 Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]➁ 500 500 500 500 500 500 0.5 0.5 Operating Voltage (47-63 Hz) [Vrms] Maximum I2 t for Fusing, (8.3 msec.) [A2sec] Max. Turn-On Time ➃ 1/2 Cycle (DC Control), 10.0 msec (AC Control) Max. Turn-Off Time 1/2 Cycle (DC Control), 40.0 msec (AC Control) Power Factor (Min.) with Max. Load 0.5 INPUT SPECIFICATIONS ➀ 0.5 0.5 DC CONTROL 0.5 AC CONTROL (H12CD PREFIX) (H12WD & H12D PREFIX) (H12CA PREFIX) Control Voltage Range 4-8 Vdc 4-32Vdc 90-140 Vrms (60Hz) Max. Turn-On Voltage 4.0 Vdc 4.0 Vdc 90 Vrms Min. Turn-Off Voltage 1.0 Vdc 1.0 Vdc 10.0 Vrms 220 Ohms See Note 5 8K Ohms 15 mA @ 5 Vdc ➄ 15 mA @ 120 Vrms Nominal Input Impedance Typical Input Current 15 mA @ 5 Vdc ©1998 CRYDOM CORP, Specifications subject to change without notice. GENERAL NOTES ➀ All parameters at 25ºC unless otherwise specified. ➁ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 ➂ Heat sinking required, for derating curves see page 2. ➃ Turn-on time for DC control random turn-on versions is 0.02 msec. ➄ Input circuitry incorporates active current limiter. FastFax Document No.157 SERIES H12.081898, PAGE 1 OF 3 For recommended applications and more information contact: USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: [email protected] WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 812300 • fax (44)1202 812340 Crydom International Ltd., 85, Condor Close, Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU GERMANY: (49) (0)6874 182580 • fax (49)(0)6874 182585 Crydom GmbH, Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • e-mail: [email protected] Series H12 25-90Amp • 480 Vac • AC Output GENERAL SPECIFICATIONS Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms 109 Ohm Insulation Resistance (Min.) @ 500 Vdc Max. Capacitance Input/Output 8 pF Ambient Operating Temperature Range -40 to 80ºC Ambient Storage Temperature Range -40 to 125ºC MECHANICAL SPECIFICATIONS Weight: (typical) 3.0 oz. (86.5g) Encapsulation: Terminals: Crydom Heat Sinks offer excellent thermal management and are perfectly matched to the load current ratings of Crydom panel mount relays. Request Crydom’s Heat Sink specification sheet for all the details. Thermally Conductive Epoxy Screws and Saddle Clamps Furnished, Unmounted MOUNTING HOLE/SLOT 0.17 (4.3) DIA. 1 1.87 (47.5) 1.10 (27.9) .45 (11.4) 8-32 TERMINAL (2 PLACES ) OUTPUT 2 SOLID-STATE RELAY -4 Available Options F Faston Terminals (Up to 50 Amp Models) -10 Random Turn-On Example: H12WD4850-10 6-32 TERMINAL (2 PLACES) 1.10 (27.9) .45 (11.4) MOUNTING HOLE/SLOT 0.17 (4.3) DIA. 1 Fastons: Single pair (up to 25A) Double pair* (up to 50A). *Caution: User must connect to both pairs 3 INPUT 1.00 (25.4) 1.80 (45.7) BASE PLATE .125 (3.2) Screw Torque Requirements: 6-32 Screws - 10 in./lbs., 8-32 and 10-32 Screws - 20in./lbs. (Screws dry without grease.) + OUTPUT .78 (19.8) .90 (22.9) FASTON TERMINAL .250 X .032 (2 PLCS.) .87 REF. (22.2) 2 1.87 (47.5) 2.30 (58.4) 1.70 (43.2) 4 BASE PLATE .125 (3.2) 2.30 (58.4) 1.70 (43.2) INPUT 1.00 (25.4) 1.80 (45.7) 3 FASTON TERMINAL .187 X .032 (2 PLCS.) .78 (19.8) .90 (22.9) All dimensions are in inches (millimeters) ©1998 CRYDOM CORP, Specifications subject to change without notice. APPROVALS UL E116949 CSA LR81689 VDE 10143 UG FastFax Document No.157 SERIES H12.081898, PAGE 2 OF 3 For recommended applications and more information contact: USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: [email protected] WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 812300 • fax (44)1202 812340 Crydom International Ltd., 85, Condor Close, Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU GERMANY: (49) (0)6874 182580 • fax (49)(0)6874 182585 Crydom GmbH, Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • e-mail: [email protected] Series H12 25-90Amp • 480 Vac • AC Output CURRENT DERATING CURVES 25A 50A 95 60 1ºC/W 2ºC/W 20 15 110 10 NO HEATSINK 5 Power Dissipation .5ºC/W 90 1.5ºC/W 40 100 2ºC/W 110 20 120 120 NO HEATSINK 0 5 10 15 20 25 Load Current [Arms] 20 40 60 0 80 10 Max Ambient Temp. [ºC] 20 30 40 50 Load Current [Arms] 20 40 60 90A 75A 90 120 120 100 80 1ºC/W 110 40 Power Dissipation 95 .3ºC/W .5ºC/W Base Plate Temp [ºC] .5ºC/W Power Dissipation 80 Max Ambient Temp. [ºC] .2ºC/W .4ºC/W 80 100 1ºC/W 110 40 Base Plate Temp [ºC] Power Dissipation 100 3ºC/W Base Plate Temp [ºC] 1ºC/W 25 Base Plate Temp [ºC] 30 120 120 0 0 15 30 45 60 Load Current [Arms] 75 20 40 60 80 Max Ambient Temp. [ºC] 20 40 60 80 Load Current [Arms] 0 20 40 60 80 Max Ambient Temp. [ºC] ©1998 CRYDOM CORP, Specifications subject to change without notice. FastFax Document No.157 SERIES H12.032698, PAGE 3 OF 3 For recommended applications and more information contact: USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: [email protected] WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 812300 • fax (44)1202 812340 Crydom International Ltd., 85, Condor Close, Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU GERMANY: (49) (0)6874 182580 • fax (49)(0)6874 182585 Crydom GmbH, Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • e-mail: [email protected]