Safety relay OA / OW 5669 • according to EN 50 205, IEC/EN 60 255, IEC 60 664-1 • with positively driven contacts • wash proof model as option • double and reinforced insultaion between contact sets according to EN 50 178 • low rated power consumption • high mechanical service life • compact size, small height • Approvals: UL, CSA, TÜV approval: R 9012316 Applications: ZH1/457 press controls Switchgear for safety technology OA / OW 5669 Technical data Relay type 1. 0 Relay coil 1. 1 Nominal voltage 1. 2 Nominal consumption OA 5669 DC V W 5, 6, 12, 20, 24, 48, 60, 110 0,7 2. 0 Contacts 2. 1 Contact arrangement 2. 2 Contact material 2. 3 Rated insulation voltage AC V Switching voltage min./max. V 2. 4 Limiting continuous current A Switching current min./max. A 2. 5 Switching power min./max. VA Switching power min./max. W 2. 6 Switching capacity to IEC/EN 60 947-5-1 AC 15 AC V/A DC 13 DC V/A 2. 7 Electrical life 2) AC 230 V 6 A cos ϕ = 1 switching cycles 2. 8 Switching frequency max. switching cycles / s 2. 9 Response time / Release time ms 2.10 Contact force NO / NC cN 3. 3. 3. 3. 3. 3. 3. 3. 1) 0 1 2 3 4 5 6 8 1 NC / 1NO 2 changeover contacts, 1 No and 1 changeover contact AgCdO + 0,2 µm Au; AgNi 10 + 0,2 µm Au optionally + 5 µm Au 250 AC/DC 10 / DC 250, AC 400 (AC/DC 100 mV / 60 V) 1) 2 x 5 (see operating voltage limit curve) 10mA3) / 8 (1 mA / 0,3 A)1) 3 / 2 000 (1 mVA / 7 VA)1) 3 / 200 (1 mW / 7 W) 1) (s. limit curve for arc-free operation) Other Mechanical life switching cycles Temperature range °C Degree of protection, housing Housing Vibration resistance Climate resistance Insolation according to IEC 60 664-1, EN 50 178 Rated insulation voltage AC V Contamination level Overvoltage category Values for AgNi 10-contacts + 5 µm Au 2) NC: 230 / 1 NC: 24 / 2 at 1 s On, 1 s Off > 1 x 105 AgNi 10 10 ≤ 15 / ≤ 12 ≥ 10 / ≥ 8 ≥ 50 x 106 - 40 ... + 60 mounted without distance (Ith = 2 x 5 A) IP40 / IP67 IEC/EN 60 529 wash proof Thermoplast GF, PA 10 ... 55 Hz; 0,35 mm amplitude; 5 g max. IEC/EN 60 068-2-6 40 / 060 / 04 (climate category); A/B/D IEC/EN 60 068-1 double and reinforced insulation 250 2 III 10 A total current at t = 20°C and coil voltage UN All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time. NO: 230 / 3 NO: 24 / 2 (s. contacts service life) > 2 x 105 AgCdO 3) Typical values OA/ OW 5669 / 25.02.03 d Technical data 3. 8 Test voltage contact-coil (1 min) AC kV eff. contact-contact (1 min) AC kV eff. Transient volt. contact-coil (1,2 - 50 µs) kV Clearance and creepage distances as per IEC/EN 60 730, IEC/EN 60 335 contact-coil mm contact-contact: mm 3. 9 Weight g Standard variants ≥4 ≥4 ≥6 ≥8 ≥ 5,5 15 Ordering example UN Voltage Resistance Design version DC range at 20°C OA / OW V DC V Ω .16 .16 .12 5 4,0...8,0 36 461 991 980 6 4,8...9,6 50 462 992 981 12 9,6...19,2 210 463 993 982 20 16,0...32,0 580 468 998 987 24 19,2...38,4 820 464 994 983 48 38,4...76,8 3 200 465 995 984 60 48,0...96,0 5 200 466 996 985 110 88,0...176 18 000 467 997 986 O 5669.16 / Design version Contact arrangement .16 1 NC / 1 NO .12 2 changeover contacts .20 1 NO /1changeover contact Degree of protection A = IP 40 (solder line proof) W = IP 67 (wash proof) Characteristics 4 U B max. without load 1,4 M2870 M2869 1,6 2 10 7 1,2 U B max. at 8A load 1,0 Switching cycles UB UN 10 8 6 0,8 U B min. 0 20 40 60 6 4 2 AgCdO 10 6 6 4 AgNi10 80°C 2 Ambient temperature 10 5 0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 Switching capacity P [ kVA ] 0,6 Reduction factor F Contact material AgNi 260 Switching voltage U [ M2642 1,0 0,9 0,8 0,7 0,5 0,4 0,3 M2871 Contact service life (at tu = 20°C) V] Operating voltage limit curve 220 180 140 100 60 0,2 0,2 0,4 0,6 0,8 Power factor (cos ) Number of cycles = Number of cycles (ohmic) x reduction factor F Reduction factor for inductive loads 20 0 1 0,2 0,4 0,7 2 4 Switching current I [ A ] safe switch-off, no standing arc arc max. 1 switching cycle / s Limit curve for arc-free operation (at tu = 20°C) 6 8 10 Dimensions, pin configuration, connection diagrams Connection for basic grid divensions 2,5 mm as well as 2,54 mm according to IEC/EN 60 097 and IEC 60 326 average Dimensions, pin configuration, connection diagrams Connection for basic grid divensions 2,5 mm as well as 2,54 mm according to IEC/EN 60 097 and IEC 60 326 average Accessories 34 32 M2980 Fixing clip Function modul 4 10 Relay socket 1 x 0,5 2x5 20,1 max. 31,5 7,5 max. 13 Socket ET 1415.021 ANR 0034 769 Fixing clip ET 1415.025 ANR 0034 770 Wire Fixing clip ET 1415.026 ANR 0047 726 Plastic Relay socket ET 1415.041 ANR 0055571 with fixing clip WN 1415.902.790 Function modul ET 1415.911 ANR 0055909 - DC, with free-wheeling diode and red LED Function modul ET 1415.912 ANR 0055910 - AC/DC with green LED E. DOLD & SÖHNE KG • D-78114 Furtwangen Postf. 1251 • Tel. (07723) 6540 • Fax (07723) 654356 • e-mail [email protected] • internet http: //www.dold.com