BRAIN 三相交流固态继电器3PSS60A75

Solid State Relays
Industrial, 3-Phase SS
• 3-phase Solid State Relay
• Zero switching
• Rated operational current: 3 x 75 AMPS
• Rated operational voltage: 600 VAC
• Control voltage 24-50 VDC/24-275 VAC
• Integral snubber network
• Built-in varistor
• IP 10 back-of-hand protection
• LED indication of control input
• Heat Sink and 24 VDC Fan Included
Optional 120 VAC Fan (Add -120 to P/N)
Example (3PSS60A75 S-120)
|
E 62767
Thermal Specifications
Operating temperature
Storage temperature
Product Description
A Solid State Relay family
designed to switch various
loads such as heating elements, motors and transformers. The relay is capable of
switching high voltages up to
600 VAC rms.
The built-in varistor for heavy
industrial applications. For
higher reliability and load
cycle capability three semiconductor power units are
bonded directly to the substrate.
3 Pole 50 AMP @ 480 VAC @ -30°C to 50°C 3-Phase
2 Pole 75 AMP @ 480 VAC @ -30°C to 50°C 3-Phase *
51°C to 80°C derates @ 10 AMPS per decade
*For 2 Pole usage, use L1 & L3
General Specifications
Rated isolation voltage
Input to output
Output to case
≥ 4000 VAC rms
≥ 4000 VAC rms
Control voltage range
Pick-up voltage
Drop-out voltage
Input current
Response time pick-up
Power output = 50 Hz
Response time drop-out
Power output = 50 Hz
24-275 VAC/24-50 VDC
18 VAC/20 VDC
9 VAC/DC
≤ 15 mA
20 ms
30 ms
All data specified at Ta=25°C
42-660 VAC
1600 Vp
45 to 65 Hz
III
3
1.4 WATTS & 58 mA
3.6 WATTS & 55 mA
|
Output Specifications
Rated operational current
AC51 @ Ta=25°C
AC53a @ Ta=25°C
Minimum operational current
Rep. overload current t=1 s
Non-rep. surge current t = 10 ms
Off-state leakage current
I2t for fusing t = 10 ms
On-state voltage drop
Critical dV/dt off-state
Isolation
Input Specifications
Tested and Approved
Operational voltage range
Blocking voltage
Operational frequency range
Overvoltage category
Pollution degree
Heat Sink Fan 24 VDC Standard
Heat Sink Fan 120 VAC Optional
Markings
-30° to 80°C (-22° to 158°F)
-40° to 100°C (-40° to 212°F)
75 AMPS rms
20 AMPS rms
400 mA rms
< 150 A rms
1150 Ap
< 3 mA rms
6600 A2s
≤ 1.6 V rms
≥ 500 V/µs
Total Weight
Grams
Ounces
S
R
1,370
48.3
1,473
52
Housing Specifications
Material
Base plate
Potting compound
Power terminal
Mounting screws
Mounting torque
Wire size
Relay
Mounting screws
Mounting torque
Control terminal
Mounting screws
Mounting torque
Wire size
Noryl
Copper, nickel-plated
Polyurethane
Max.
Min.
M5
≤ 2.5 Nm (22 in lbs)
2 x 6 mm 2 (AWG 8)
2 x 1 mm 2
M5
≤ 1.5 Nm (13 in lbs)
Max.
Min.
M4
≤ 0.5 Nm (5 in lbs)
2 x 2.5 mm 2 (AWG 14)
2 x 1 mm 2
www.dold-relay.com
Dimensions
Model S
4.425
3.550
4.754
.477
.198
3.550
.166 X .190 (2 HOLES)
ALIGNS W/SLOTS BELOW
L1
L2
3PSS60A75
AC51: 75A 600 VAC
4.694
L3
L1 L2 L3 A1
A1
~
T1 T2 T3 A2
VCC: 24-275 VAC
24-50 VDC
A2
~
AC53a: 20A 600 VAC
E 62767
T1
FAN
.173
.504
|
T2
M5 TH’D
2 PLACES
T3
3.653
FAN
.166
3.550
3.550
Model R
4.410
Includes Retro-Fit Back Plate
3.125
.205 X .402 DIA.
KEYHOLE (2 REQ.)
For direct replacement with
standard 2 & 3 pole Mercury
Relays. Using the same mounting
holes.
1.938
2.690
Bracket adds 3/16” to depth
.205
BOTH SIDES
www.dold-relay.com