ETC EBACT231M

Timers
Interval
Type EBA
•
•
•
•
•
•
•
•
Time range 0.1 s to 10 h
Automatic start
Knob-adjustable time setting
Knob selection of time range
Oscillator-controlled time circuit
Repeatability deviation: ≤ 0.2%
Output: 5A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 22.5 mm Euronorm housing
• LED-indication for relay and power supply ON
• Combined AC and DC power supply
Product Description
Ordering Key
Mono-function timer with selectable time ranges within
0,1 s to 1 m or 1 m to 10 h. For
mounting on DIN-rail. Often
used e.g. to empty a conveyor belt of items.
Housing
Function
Type
Output
Power supply
Time range
EBA C T23 1M
Type Selection
Mounting
Output
Time range
Supply: 24 VAC/DC & 115-230 VAC
For DIN-rail
SPDT
SPDT
0.1 s - 1 m
1 m - 10 h
EBA C T23 1M
EBA C T23 10H
Time Specifications
Output Specifications
Time ranges
Type 1 M
Selectable by rotary switch
Output
Rated insulation voltage
Contact ratings (AgCdO)
AC 1
Resistive loads
DC 1
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Type 10 H
Selectable by rotary switch
Time range accuracy
Repeatability deviation
Time variation
Within rated power supply
and ambient temperature
Reset
Time and relay
0.1 s - 1 s
1 s - 10 s
0,1 m - 1 m
1 m - 10 m
0.1 h - 1 h
1 h - 10 h
±10% on max.
min. actual time
≤ min. set time
(range 0,1s - 1 ≤ 0,15s)
≤ 0.2%
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
SPDT relay
250 VAC (contact/elect.)
µ (micro gap)
5 A, 250 VAC
5 A, 24 VDC
2 A, 250 VAC
3 A, 24 VDC
≥ 40 x 106 operations
≥ 105 operations
(at max. load)
≤ 7200 operations/h
2 kVAC (rms)
4 kV (1.2/50 µs)
≤ 0.05%/V
≤ 0.2%/°C
Power supply interruption
≥ 200 ms
Specifications are subject to change without notice (09.01.00)
1
EBA
Supply Specifications
General Specifications
Overvoltage cat. III (IEC 60664)
(IEC 60038)
115-230 VAC, -10/+15%
50/60 Hz, -5/+5 Hz
24 VAC/DC, -10/+15%
50/60 Hz, -5/+5 Hz
≤ 40 ms
None
Power supply
Rated operational voltage
through term. A1 & A2 T23
frequency
through term. A2 & A3 T23
frequency
Voltage interruption
Dielectric voltage
Rated impulse withstand
voltage
Rated operational current
4 kV (1.2/50 µs)
20 mA @ 24 VDC
40 mA @ 24 VAC
20 mA @115 VAC
40 mA @ 230 VAC
EMC
Immunity
Power ON delay
Power OFF delay
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Screw terminals
Tightening torque
Approvals
CE-marking
Electromagnetic
Compatibility
Acc. to IEC 60801-4
Acc. to IEC 60801-5
≤ 200 ms
≥ 200 ms
LED, green
LED, yellow
IP 20
3
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
125 g
Max. 0.5 Nm acc. to IEC 947
UL, CSA
Yes
Mode of Operation
The relay operates and the
time period starts when power
supply is applied.
At the end of the set time
period, the relay releases and
will not operate again until
power supply is interrupted
for at least 200 ms.
Wiring Diagram
If power supply is interrupted
for at least 200 ms before the
time period has expired, the
relay releases and the time cir-
Time Setting
Selection of time ranges
Upper knob:
3-position rotary switch.
115-230 V
cuit is reset to zero. The relay is
ready for a new time period.
~
24 V
L
~
Time setting
Lower knob:
Knob-adjustable on relative
scale 1-10.
µ
N
Operation Diagram
Power supply
Relay ON
2