ETC EUKCT23

Current and Voltage Controls
1-Phase Over/Under Voltage
Type EUK
• AC monitoring relay for over/under
voltage control (closed circuit)
• Measures if power supply is within set limits
• Measures on own power supply
• 3-position rotary switch for selection of measuring range
• Measuring range: 24-115-230, ±13% VAC (RMS)
• Upper and lower limits separately adjustable
• Adjustable time function (0.1-10 s)
• Output: 5 A SPDT
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 45 mm Euronorm housing
• LED-indication for power supply ON
• Two LED's indicating fault and/or status of the relay
output (flashing when timing)
Product Description
Ordering Key
EUK is a single-phase monitoring relay for separate over
and under voltage control.
Built-in time function 0.1-10
s. Often used in applications
where it is essential to moni-
tor that the fluctuation of the
delivered power is kept within
set limits so that the connected equipment will not be damaged.
Housing
Function
Type
Output
Power supply
EUK C T23
Type Selection
Mounting
Output
Measuring ranges
Supply: 24/115/230 VAC
For DIN-rail
SPDT
24,115 or 230 VAC
EUK C T23
Input Specifications
Supply Specifications
Input
Through terminals A1 & A2
Measuring ranges
Selectable by rotary switch
24 VAC
115 VAC
230 VAC
Power supply
Rated operational voltage
Through term. A1 & A2 T23
Hysteresis
Measures on own supply
Upper level Lower level
-10%-13%
-13%-10%
21.6-27.1 V 20.9-26.4 V
103.5-130 V 100-126.5 V
207-260 V
200-253 V
measuring range equals
rms value of a sinusoidal
voltage
< 2%
Output Specifications
Output
Rated insulation voltage
Contact ratings (AgCdO)
AC 1
Resistive loads
DC 1
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Through term. A1 &A2 T23
(Interconnec. term. A1 & A3)
Voltage interruption
Dielectric voltage
Rated impulse withstand
voltage
Rated operational current
Overvoltage cat. III (IEC 60664)
(IEC 60038)
115-230 VAC, ±15%
50/60 Hz, -5/+5 Hz
24 VAC, ±15%
50/60 Hz, -5/+5 Hz
≤ 40 ms
None
4 kV (1.2/50 µs)
55 mA @ 24 VAC
25 mA @ 115 VAC
50 mA @ 230 VAC
SPDT relay
250 VAC (contact/elect.)
µ (micro gap)
5 A, 250 VAC
5 A, 24 VDC
2 A, 250 VAC
3 A, 24 VDC
≥ 40 x 106 operations
≥ 105 operations
(at max. load)
≤ 7200 operations/h
Operating frequency
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (26.10.99)
1
EUK
General Specifications
Mode of Operation
Power ON delay
Reaction time
EUK measures the rms value
of its own sinusoidal power
supply.
<2s
τ < 200 ms,
worst case reaction time
may be up to 5 x τ
adjustable delay on release
built-in (0.1-10 s)
Accuracy
Input
OFF-delay
±5%
10 s, -1/+3 s on max.
≤ 0.1 s on min.
≤ 0.2%/°C (≤ 0.11%/°F)
Temperature drift
Indication for
Power supply ON
Output ON
LED, green
2 LED's, yellow (indicating
upper/lower level)
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Screw terminals
Tightening torque
Approvals
The relay operates and both
yellow LED's are ON as long
as the measured voltage is
within the upper and lower
limits.
The relay releases after an adjustable time delay of 0.1-10 s
when the measured voltage is
above the upper level or below the lower level.
The yellow LED indicating
upper/lower level is flashing
until the time delay has expired.
When the relay has released,
the flashing LED is switched
OFF.
EUK has a power-up delay of
approx. 2 s to prevent the relay from operating if the measured voltage is above/below
the set limits when power supply is applied.
IP 20
3
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
165 g
Max. 0.5 Nm acc. to IEC 60947
UL, CSA
Wiring Diagram
Range/Level/Time Setting
115-230 V ~
24 V ~
L
µ
Level setting
Upper left knob :
Setting of upper limit on relative scale in % (-10 to +13%).
Range setting
Upper right knob:
Setting of voltage measuring
range on rotary switch.
Lower left knob:
Setting of lower limit on relative scale in % (-13 to +10%).
Time setting
Lower right knob:
Setting of time delay on absolute scale (0.1-10 s).
N
Operation Diagram
Upper level
Hysteresis
Lower level
Hysteresis
Power supply
Relay ON
2
Specifications are subject to change without notice (26.10.99)