SCHURTER FMBD-B92A-2512

FMBD NEO
3-Phase Filters
www.schurter.com/pg80
2-stage filter for 3-phase systems with neutral conductor
Description
Applications
-Terminals for three phases, neutral conductor and ground
-Very high symmetrical and asymmetrical attenuation loss
-In the frequency range from 10kHz up to 300MHz
-Voltage rating 520 VAC for world wide acceptance
-Protection against interference voltage from the mains
-Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
Standards
-IEC 60939
-UL 1283, Edition 5, CSA 22.2 No. 8-M1986, @ Ta 75 °C
References
Approvals
Weblinks
Technical Data
Rated Current
Rated voltage
Approval for
Mounting Terminal
Operating Temperature [°C]
Climatic Category
Degree of Protection
Protection Class
General Product Information
Approvals, RoHS, CHINA-RoHS, Distributor-Stock-Check
-VDE License Number: pending
-UL License Number: E72928
8 - 200 A
300/520 VAC, 50/60 Hz
8 - 200 A @ 50 (75) °C / 300/520 VAC;
50/60 Hz
Overload Current
1.5 x Ir
Dielectric Strength for 520 VAC 2.25 kVDC between L-L
1.7 kVDC between L-N
2.75 kVDC between L-PE
2.75 kVDC between N-PE
Test voltage 2 sec
Number of Filter Stages
2
Weight
1.1 - 8.6 kg
Material: Housing
Metal Sealing Compound
UL 94V-0 MTBF
EMC Products
Screw-on mounting on chassis Screw Clamp -25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
IP 20 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
> 200'000 h acc. to MIL-HB-217 F
FMBD NEO
3-Phase Filters
www.schurter.com/pg80
Dimensions
Case 2A
max. 155
max. 115
3x11.5=(34.5)
35
max. 80
M6x14; 3-4 Nm
54.5
(120)
14
80 ±0.3
6.5±0.3
(4x)
0
127.5–2
max. 145
4mm 2 ; 0.5-0.6 Nm
1)
2)
1) Line
2) Load
Case 2B
3x23=(69)
89
max. 125
(130)
max. 115
max. 165
50
M6x14; 3-4 Nm
14
90 ±0.3
6.5
(4x)
0
137.5 –2
max. 155
10mm 2 ; 1.5-1.8 Nm
1)
2)
1) Line
2) Load
EMC Products
FMBD NEO
3-Phase Filters
www.schurter.com/pg80
Case 2C
3x25=(75)
94
max. 125
(160)
max. 125
max. 220
55
M10; 10-17 Nm
18
100 ±0.3
6.5 ±0.3
(4x)
0
137.5 –2
max. 155
25mm 2 ; 2-2.2 Nm
1)
2)
1) Line
2) Load
Case 2D
max. 135
(230)
3x28=(84)
40
83
max. 125
max. 315
M10; 10-17 Nm
24
120 ±0.3
6.5 ±0.3
(4x)
0
147.5 –2
max. 165
50mm2 ; 2.2-2.5 Nm
1)
2)
1) Line
2) Load
EMC Products
FMBD NEO
3-Phase Filters
www.schurter.com/pg80
Case 2E
3x30=(90)
max. 140
max. 140
(250)
98
max. 335
55
M10; 10-17 Nm
18
200 ±0.3
6.5 ±0.3
(4x)
0
152.5 –2
max. 170
50mm 2 ; 2.2-2.5 Nm
1)
2)
1) Line
2) Load
Case 2F
max. 140
(280)
3x30=(90)
106.5
max. 170
max. 380
45
M10; 10-17 Nm
24
230 ±0.3
6.5 ±0.3
(4x)
0
152.5 –2
max. 170
95mm 2 ; 15-20 Nm
1)
2)
1) Line
2) Load
EMC Products
FMBD NEO
3-Phase Filters
www.schurter.com/pg80
Technical data to the filter components
Rated Current @ Ta 50°C (75°C) [A]
L1
[mH]
L2
[μH]
C1 [μF]
C2 [μF]
C3 [μF]
R1 [MΩ] R2 [MΩ] R3 [MΩ]
8 (5)
2
4
2.2
2.2
3.4
-
1
2
16 (11)
1.3
12
2.2
2.2
3.4
-
1
2
25 (16)
1.6
12
4.7
4.7
3.4
1
1
2
36 (21)
1
12
4.7
4.7
3.4
1
1
2
64 (40)
0.7
7.5
4.7
4.7
3.4
1
1
2
80 (50)
0.6
9
8.2
8.2
3.4
1
1
2
120 (96)
0.6
9
13.6
13.6
3.4
0.5
0.5
2
160 (100)
0.4
9
13.6
13.6
3.4
0.5
0.5
2
200 (140)
0.3
9
13.6
13.6
3.4
0.5
0.5
2
C1/R1
L1
C2/R2
L2
Diagrams
L1
L2
1) L3
C1/R1
C2/R2
C1/R1
L1'
L2'
C2/R2
L3' 2)
N'
N
PE
PE
C3/R3
1) Line
2) Load
Admissible operating current in %
of In
Derating Curves
Permissible Working Current as a Function of Ambient Temperature
100
80
60
UL Listet
40
20
0
0
20
40
60
75
100
Ambient air temperature Ta °C
EMC Products
FMBD NEO
3-Phase Filters
www.schurter.com/pg80
Attenuation Loss
........ 01/100 differential mode . . . . 100/0.1 differential mode - - - - differential mode _____ common mode
Industrial Version
7A
16A
25A
36A
64A
80A
120A
160A
200A
Variants
Rated Current @ Ta 50°C (75°C) [A]
8 (5)
Tripped Power Dissipation [W]
Contact Resistance
[mΩ]
Leakage Current
[mA] 1)
Weight
[kg]
Screw
clamps
[mm2] 2)
Housing
Packaging
unit [PCS]
Order Number
3.2
12.5
<1
1.1
4
2A
2
FMBD-B92A-0812
16 (11)
7
6.8
<1
1.2
4
2A
2
FMBD-B92A-1612
25 (16)
9.5
3.8
<1
1.8
10
2B
2
FMBD-B92A-2512
36 (21)
12.5
2.4
<1
2
10
2B
2
FMBD-B92B-3612
64 (40)
21.3
1.3
<1
2.8
25
2C
1
FMBD-B92C-6412
80 (50)
22.6
0.88
<1
5.7
50
2D
1
FMBD-B92D-8012
120 (96)
43.2
0.75
<1
6.3
50
2E
1
FMBD-B92E-J212
160 (100)
37.9
0.37
<1
8
95
2F
1
FMBD-B92F-J612
200 (140)
41.6
0.26
<1
8.6
95
2F
1
FMBD-B92F-K012
1) Maximum leakage current under normal operating conditions, assuming that all three phases and the neutral conductor are connected to the supply and the consumer.
Under this condition, the current will mainly return through the neutral line, not as earth leakage.
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the general product information www.schurter.
com/emc_info
The
specifications,
descriptions and illustrations indicated in this document are based on
EMC
Products
current information. All content is subject to modifications and amendments.