LEM LA55

Current Transducer LA 55-TP
IPN =
50 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16016
Electrical data
IPN
IP
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring resistance @
with ± 12 V
with ± 15 V
ISN
KN
VC
IC
50
0 .. ± 70
TA = 70°C
TA = 85°C
RM min RM max RM min RM max
@ ± 50 A max
@ ± 70 A max
@ ± 50 A max
@ ± 70 A max
10
10
50
50
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
100
50
160
90
60 95
60 1) 60 1)
135 155
135 2) 135 2)
A
A
ε
Accuracy @ IPN , TA = 25°C
Ω
Ω
Ω
Ω
50
mA
1 : 1000
± 12 .. 15
V
10 (@ ± 15 V) + IS mA
@ ± 15 V (± 5 %)
@ ± 12 .. 15 V (± 5 %)
Linearity error
L
± 0.65
± 0.90
< 0.15
Typ
%
%
%
Max
± 0.2
± 0.3
± 0.5
± 0.6
IO
IOM
IOT
Offset current @ IP = 0, TA = 25°C
Residual current 3) @ IP = 0, after an overload of 3 x IPN
Thermal drift of IO
0°C .. + 70°C
- 25°C .. + 85°C
± 0.1
± 0.1
tra
tr
di/dt
f
Reaction time @ 10 % of IP max
Response time 4) @ 90 % of IP max
di/dt accurately followed
Frequency bandwidth @ 30A (- 3 dB)
< 500
< 2.5
> 200
DC .. 100
mA
mA
mA
mA
ns
µs
A/µs
kHz
General data
TA
TS
RS
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @
m
Mass
Standards
Notes :
1)
2)
3)
4)
TA = 70°C
TA = 85°C
• Closed loop (compensated) current
transducer using the Hall effect
Accuracy - Dynamic performance data
X
Features
- 25 .. + 85
°C
- 40 .. + 90
°C
80
Ω
85
Ω
24
g
EN 50178 : 1997
• Printed circuit board mounting
• Insulated plastic case recognized
according to UL 94-V0.
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Application Domain
• Industrial
Measuring range limited to ± 60 A max
Measuring range limited to ± 55 A max
Result of the coercive field of the magnetic circuit
With a di/dt of 100 A/µs.
060126/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 1/3
w w w .lem.com
Current Transducer LA 55-TP
Isolation characteristics
Vd
Vb
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
R.m.s. rated voltage
2.5
600
kV
V
dCp
dCl
CTI
Creepage distance
Clearance distance
Comparative Tracking Index (Group IIIa)
Min
6.9
6.1
175
mm
mm
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions :
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
600 V
600 V
Reinforced isolation
300 V
300 V
dCp, dCI
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the following
manufacturer's operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
060126/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/3
w w w .lem.com
Dimensions LA 55-TP
(in mm. 1 mm = 0.0394 inch)
Bottom view
Left view
Connection
Standard 00
or N° SP..
Year Week
Front view
Mechanical characteristics
• General tolerance
• Fastening & connection of primary
Recommended PCB hole
• Fastening & connection of secondary
Recommended PCB hole
Remarks
± 0.2 mm
bus bar
6.4 x 1.6 mm
3.8 mm
3 pins
0.63 x 0.56 mm
0.9 mm
• IS is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
90°C.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
060126/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 3/3
w w w .lem.com