MEANWELL MDR-10-15

10W Single Output Industrial DIN Rail Power Supply
MDR-10
series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
NEC class 2 / LPS compliant
Built in DC OK active signal
LED indicator for power on
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
OUTPUT
MDR-10-5
MDR-10-12
MDR-10-15
MDR-10-24
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
2A
0.84A
0.67A
0.42A
CURRENT RANGE
0 ~ 2A
0 ~ 0.84A
0 ~ 0.67A
0 ~ 0.42A
RATED POWER
10W
RIPPLE & NOISE (max.) Note.2 80mVp-p
10W
10W
120mVp-p
150mVp-p
VOLTAGE TOLERANCE Note.3
5.0%
3.0%
3.0%
2.0%
LINE REGULATION
1.0%
1.0%
1.0%
1.0%
LOAD REGULATION
5.0%
3.0%
3.0%
2.0%
SETUP, RISE TIME
INPUT
10W
120mVp-p
Note.5 500ms, 30ms/230VAC
HOLD UP TIME (Typ.)
120ms/230VAC
VOLTAGE RANGE
85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
1000ms, 30ms/115VAC at full load
25ms/115VAC at full load
120 ~ 370VDC
EFFICIENCY (Typ.)
77%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
0.33A/115VAC
0.21A/230VAC
COLD START 35A/115VAC
70A/230VAC
<1mA / 240VAC
LEAKAGE CURRENT
OVERLOAD
PROTECTION
81%
81%
Above 105% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
13.8 ~ 16.2V
17.25 ~ 20.25V
5.75 ~ 6.75V
84%
27.6 ~ 32.4V
OVER VOLTAGE
FUNCTION
Protection type : Shut down o/p voltage, re-power on to recover
9 ~ 13.5V / 40mA
DC OK ACTIVE SIGNAL (max.) 3.75 ~ 6V / 50mA
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
11.5 ~ 16.5V / 40mA
18 ~ 27V / 20mA
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant
SAFETY &
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
OTHERS
DIMENSION
PACKING
NOTE
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A
584K hrs min. MIL-HDBK-217F (25
22.5*90*100mm (W*H*D)
0.17Kg; 72pcs/13.2Kg/0.91CUFT
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-10-SPEC 2011-05-24
MDR-10
10W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
Case No. 956
series
Unit:mm
100
22.5
5 5
35
+V -V DC
OK
90
DC OK
N L
Install DIN rail TS35/7.5 or TS35/15
5 5
Block Diagram
fosc : 60KHz
DC OK
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
DC OK
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
CONTROL
O.V.P.
Application of DC OK Active Signal
(a) 5V signal
(b) LED
DC OK
Model
5V
12V
15V
24V
R
5.1V
(c) Relay
DC OK
R
200
1.5K
2K
3.9K
R
Model
5V
12V
15V
24V
DC OK
R
1K
2.4K
3K
4.7K
Relay
RL
RL
120
700
700
1.2K
V-
V-
V-
Model
5V
12V
15V
24V
Output Derating VS Input Voltage
Derating Curve
Ta=25
100
100
Others
90
80
80
5V
70
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
60
50
40
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
File Name:MDR-10-SPEC 2011-05-24