MEANWELL NED-50A

NED-50
50W Dual Output Switching Power Supply
series
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
100% full load burn-in test
2 years warranty
SPECIFICATION
NED-50A
MODEL
CH1
CH2
CH1
CH2
DC VOLTAGE
5V
12V
5V
24V
RATED CURRENT
6A
2A
4A
1.4A
0.3 ~ 3A
1 ~ 6A
0.2 ~ 2A
CURRENT RANGE
Note.6 1 ~ 6A
54W
RATED POWER
OUTPUT
INPUT
RIPPLE & NOISE (max.) Note.2 80mVp-p
6.0%
200mVp-p
6.0%
0.5%
1.0%
0.5%
1.0%
LOAD REGULATION
Note.5
1.5%
3.0%
1.5%
3.0%
SETUP, RISE TIME
500ms, 30ms/230VAC
HOLD UP TIME (Typ.)
50ms/230VAC
VOLTAGE RANGE
85 ~ 264VAC
FREQUENCY RANGE
EFFICIENCY(Typ.)
47 ~ 63Hz
79%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.1A/115VAC
0.65A/230VAC
COLD START 45A
1200ms, 30ms/115VAC at full load
10ms/115VAC at full load
120 ~ 370VDC
82%
LEAKAGE CURRENT
<2mA / 240VAC
OVERLOAD
110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE
CH1: 5.75 ~ 6.75V
Protection type : Shut down o/p voltage, re-power on to recover
WORKING TEMP.
-20 ~ +60
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 45 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL60950-1, CB(IEC60950-1) approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
Compliance to EN61000-4-2, 3, 4, 5, 6, 8,11, ENV50204, EN55024, EN61000-6-1, light industry level, criteria A
DIMENSION
PACKING
NOTE
CH1: 4.75 ~ 5.5V
2.0%
Note.4
MTBF
OTHERS
80mVp-p
LINE REGULATION
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
(Note 7)
120mVp-p
CH1: 4.75 ~ 5.5V
VOLTAGE TOLERANCE Note.3 2.0%
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
EMC
53.6W
VOLTAGE ADJ. RANGE
PROTECTION
SAFETY &
NED-50B
OUTPUT NUMBER
413.3K hrs min. MIL-HDBK-217F (25
129*98*38mm (L*W*H)
0.44Kg; 45pcs/21Kg/1.24CUFT
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 20% to 100% rated load, and other output at 60% rated load.
6. Each output can work within current range. But total output power can't exceed rated output power.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:NED-50-SPEC 2010-10-18
NED-50
50W Dual Output Switching Power Supply
Mechanical Specification
Case No. 903
series
Unit:mm
31
9.5
1
3.5
7
122.5
2
2-
M
3
3
5
98
85.5
8.2
33
4
6
7
+V ADJ.
3.5
73.5
4.5
129
6.5
120
32
3
38
3.5
28.5
3-M
18
18.5
Assignment
DC OUTPUT +V2
DC OUTPUT COM
DC OUTPUT +V1
9
Pin No.
5
6
7
3.5
Assignment
Pin No.
1
AC/L
2
AC/N
3
FG
4
DC OUTPUT COM
9.5
Terminal Pin No. Assignment
77
Block Diagram
fosc : 60KHz
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V2
RECTIFIERS
&
FILTER
+V1
COM
DETECTION
CIRCUIT
FG
O.L.P.
CONTROL
O.V.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70
(HORIZONTAL)
60
50
40
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
File Name:NED-50-SPEC 2010-10-18