NI NIFP-1601

Analog Input Modules for
Compact FieldPoint and FieldPoint
NEW
NI [c]FP-AI-100, NI [c]FP-AI-102,
NI [c]FP-AI-110, NI [c]FP-AI-111
• 8 or 16 voltage or current inputs
• ±120 V input range, maximum
• 0 to 20, 4 to 20 mA input ranges
• Built-in signal conditioning
• 50, 60, and 500 Hz noise rejection
• 12 and 16-bit resolution
• Software-configurable input ranges per
channel
• 2,300 Vrms bank isolation for transient
overvoltage protection
• Hot-swappable with autoconfiguration
• -40 to 70 °C operating range
Module
[c]FP-AI-100
Input Channels
8
Resolution
12 bits
[c]FP-AI-102
[c]FP-AI-110
8
8
12 bits
16 bits
[c]FP-AI-111
16
16 bits
Input Type
Voltage
Current
Voltage
Voltage
Current
Current
Input Ranges
(Software Configurable per Channel)
±1 V, ±5 V, ±15 V, ±30 V, 0 to 1 V, 0 to 5 V, 0 to 15 V, 0 to 30 V
0 to 20 mA, 4 to 20 mA, ±20 mA
±20 V, ±60 V, ±120 V, 0 to 20 V, 0 to 60 V, 0 to 120 V
±60 mV, ±300 mV, ±1 V, ±5 V, ±10 V, 0 to 1 V, 0 to 5 V, 0 to 10 V
0 to 20 mA, 4 to 20 mA, ±20 mA
0 to 20 mA, 4 to 20 mA, ±20 mA
Overview
The National Instruments [c]FP-AI-1xx devices are versatile analog
input modules for Compact FieldPoint and FieldPoint that can be
used to measure voltages ranging from the millivolt level to the
120 V high-voltage level in applications such as battery-pack
monitoring, fuel-cell testing, and general measurement from
transducers. These modules can also measure 0 to 20 or 4 to 20 mA
current loops from industrial sensors and transmitters. All the
modules include overranging and onboard diagnostics to ensure
trouble-free installation and maintenance. The modules measure and
linearize signals on-board to return scaled values to your control
or monitoring software. The [c]FP-AI-1xx modules come with
NIST-traceable calibration certificates, ensuring accurate and reliable
analog measurements.
Smart I/O Modules
With [c]FP-AI-1xx analog input modules, you can directly connect to
your industrial sensors or units under test and get high-accuracy
measurements. The I/O modules filter, calibrate, and scale raw sensor
signals to engineering units, as well as performing self-diagnostics to
50/60 Hz Noise Filter
–
All-Channel
Update Rate
360 Hz
–
✓
(software selectable)
✓
(software selectable)
360 Hz
5 Hz to 0.66 Hz
(rate varies with filter settings)
3 Hz to 0.83 Hz
(rate varies with filter settings)
look for problems with the module or the wiring. With FieldPoint
modules, your software application reads a linearized, calibrated, and
scaled value from the I/O module, eliminating the error-prone step of
converting binary values to voltage or current values. For increased
accuracy and noise rejection, the [c]FP-AI-110 and [c]FP-AI-111 use a
16-bit delta-sigma ADC with an integrated lowpass filter on each
channel, which you can configure for 50 Hz, 60 Hz, or no rejection.
With high-accuracy 12-bit ADCs or 16-bit delta-sigma ADCs on the
I/O modules, you also get instrument-quality measurements on an
industrially rugged, distributed, embedded system.
[c]FP-AI-1xx modules offer a variety of update rates to fit your
application, ranging from 0.66 to 360 Hz. These rates vary based on
the module used and on the noise filter settings selected on the
module. Overall data throughput depends on software loop speeds
and network speeds. With overranging and underranging, the
[c]FP-AI-1xx analog input modules can measure inputs or sensors
that are not calibrated to standard ranges. For example, when
configured for an input range of 4 to 20 mA, the modules actually
measure inputs from 3.5 to 21 mA.
Analog Input Modules for
Compact FieldPoint and FieldPoint
External +
Power
Supply –
External +
Power
Supply –
Isolation
[c]FP-AI-1xx modules feature optical bank isolation with 2,300 Vrms
of breakdown isolation. In addition, the [c]FP-AI-100, [c]FP-AI-102,
and [c]FP-AI-110 modules provide double insulation for up to
250 Vrms of operational isolation. Compact FieldPoint can safely be
used in applications where hazardous voltages are present with the
cFP-CB-1 connector block. FieldPoint can safely be used in
applications where hazardous voltages are present with the FP-TB-x
terminal base. These Compact FieldPoint and FieldPoint modules do
not have channel-to-channel isolation.
C
C
V
Loop-Powered
Current
Transducer
Powered
+
Voltage OUT
Transducer
–
To Analog
Input Circuitry
IIN
V
VSUP
VSUP
VIN
To Analog
Input Circuitry
Input
Impedance
Varies by
Module
100 Ω
COM
COM
To Next Channel
To Next Channel
[c]FP-AI-100/110/111
[c]FP-AI-100/102/110
Figure 2. Schematics for the AI Module Wiring
Ordering Information
Field I/O Connections
Compact FieldPoint
Compact FieldPoint and FieldPoint modules include a built-in
power distribution bus that provides multiple power connections on
the module. A field-wired power supply connected to the voltage (V)
and common (C) terminals is internally connected to a power
distribution bus that provides additional breakout terminals for
voltage supply (VSUP) and common (COM). These terminals provide
a convenient way to distribute power to field devices that require
external power.
Each input channel on the AI-100 and AI-110 has four terminals:
1. Voltage input (VIN)
2. Current input (IIN)
3. Common (COM)
4. Power connection to power field devices or loop powered
current loops (VSUP)
The AI-111 has:
• 16 current input terminals (IIN)
• 8 common terminals (COM)
• 8 power connections for field devices or current loops (VSUP)
The AI-102 module has:
• 8 voltage input terminals (VIN)
• 16 common terminals (COM)
• 8 power connections to power field devices (VSUP)
NI cFP-AI-100
NI cFP-AI-102
NI cFP-AI-110
NI cFP-AI-111
............................................................777318-100
............................................................777318-102
............................................................777318-110
............................................................777318-111
Recommended Compact FieldPoint System Products
NI cFP-2020 ..............................................................777317-2020
NI cFP-BP-4 ..................................................................778617-04
NI cFP-CB-1 ..................................................................778618-01
NI PS-5 Power Supply ..................................................778805-90
NI Developer Suite Professional Control Edition..........777906-03
FieldPoint
NI FP-AI-100
NI FP-AI-102
NI FP-AI-110
NI FP-AI-111
..............................................................777518-100
..............................................................777518-102
..............................................................777518-110
..............................................................777518-111
Recommended FieldPoint System Products
NI FP-1601 ....................................................................777792-01
NI FP-TB-1 ....................................................................777519-01
NI PS-4 Power Supply ..................................................778586-90
NI Developer Suite Standard Control Edition ............777905-03
BUY ONLINE!
Visit ni.com/info and enter cfpai100, cfpai102, cfpai110, cfpai111,
fpai100, fpai102, fpai110, and/or fpai111.
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Input Characteristics
C
C
V
VSUP
VSUP
IIN
Current
Source
To Analog
Input Circuitry
Voltage
Source
100 Ω
COM
+
–
COM
To Next Channel
[c]FP-AI-100/110/111
Figure 1. Schematics for the AI Module Wiring
2
VIN
V
To Analog
Input Circuitry
Input
Impedance
Varies by
Module
To Next Channel
[c]FP-AI-100/102/110
Number of inputs
[c]FP-AI-100, [c]FP-AI-102, [c]FP-AI-110 ....
[c]FP-AI-111................................................
ADC resolution
[c]FP-AI-110, [c]FP-AI-111 ..........................
[c]FP-AI-100, [c]FP-AI-102 ..........................
Filters
[c]FP-AI-110, [c]FP-AI-111 ..........................
[c]FP-AI-100, [c]FP-AI-102 ..........................
NMR ([c]FP-AI-110 and [c]FP-AI-111 only)...
Input impedance, voltage inputs
[c]FP-AI-100................................................
[c]FP-AI-102................................................
[c]FP-AI-110................................................
Input impedance, current inputs ......................
Overvoltage protection (voltage inputs only)
[c]FP-AI-100, [c]FP-AI-102 ..........................
[c]FP-AI-110................................................
Overcurrent protection (current inputs only)....
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • [email protected] • ni.com
8 single-ended
16 single-ended
16 bits, 1 in 65,536
12 bits, 1 in 4,096
50, 60, or 500 Hz, software configurable per channel
170 Hz, first-order analog filter
95 dB (at 50/60 Hz, with filter enabled)
1.5 MΩ
1 MΩ
100 MΩ
100 Ω
250 V
40 V
30 mA
Analog Input Modules for
Compact FieldPoint and FieldPoint
Specifications (contintued)
Input Range
Module
[c]FP-AI-100
Input Range
Voltage
Nominal
0 to 1 V
0 to 5 V
0 to 15 V
0 to 30 V
±1 V
±5 V
±15 V
±30 V
0 to 20 mA
4 to 20 mA
±20 mA
0 to 20 V
0 to 60 V
0 to 120 V
±20 V
±60 V
±120 V
0 to 1 V
0 to 5 V
0 to 10 V
±60 mV
±300 mV
±1 V
±5 V
±10 V
0 to 20 mA
4 to 20 mA
±20 mA
Current
[c]FP-AI-102
Voltage
[c]FP-AI-110
Voltage
Current
With
Overranging
0 to 1.2 V
0 to 6 V
0 to 18 V
0 to 36 V
±1.2 V
±6 V
±18 V
±36 V
0 to 24 mA
3.5 to 24 mA
±24 mA
–
–
–
–
–
–
0 to 1.04 V
0 to 5.2 V
0 to 10.4 V
±65 mV
±325 mV
±1.04 V
±5.2 V
±10.4 V
0 to 21 mA
3.5 to 21 mA
±21 mA
Effective
Effective
Resolution
Resolution
1.5 mV
5 mV
15 mV
25 mV
1.5 mV
5 mV
25 mV
40 mV
15 µA
15 µA
20 µA
15 mV
40 mV
70 mV
25 mV
70 mV
125 mV
25 µV
90 µV
190 µV
3 µV
16 µV
40 µV
190 µV
380 µV
500 nA
500 nA
700 nA
Typical
15 to 35 °C
1.5 mV
6 mV
15 mV
30 mV
2 mV
10 mV
30 mV
60 mV
20 µA
20 µA
40 µA
20 mV
50 mV
100 mV
40 mV
120 mV
220 mV
50 µV
180 µV
300 µV
30 µV
40 µV
75 µV
300 µV
650 µV
1 µA
1 µA
1 µA
Offset Error
Maximum
–40 to 70 °C
15 mV
27 mV
45 mV
70 mV
20 mV
40 mV
90 mV
160 mV
45 µA
45 µA
110 µA
100 mV
150 mV
250 mV
175 mV
350 mV
700 mV
650 µV
1500 µV
2500 µV
500 µV
600 µV
850 µV
2500 µV
4000 µV
10 µA
10 µA
10 µA
Gain Error
Typical
15 to 35 °C
0.09%
0.09%
0.12%
0.22%
0.08%
0.08%
0.11%
0.20%
0.09%
0.09%
0.06%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.03%
0.03%
0.03%
0.03%
0.03%
0.03%
0.03%
0.03%
0.04%
0.04%
0.04%
Maximum
–40 to 70 °C
0.50%
0.50%
0.55%
0.55%
0.50%
0.55%
0.60%
0.55%
0.51%
0.51%
0.55%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.2%
0.2%
0.2%
Isolation Voltage
Safety
Maximum isolation voltage ............................. 250 Vrms, Installation Category II
Channel-to-channel isolation ........................... No isolation between channels
Transient overvoltage....................................... 2,300 Vrms
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to the product label or to ni.com
Physical Characteristics
LED indicators
POWER (green) ..........................................
READY (green) ...........................................
Dimensions (including terminal base)..............
Weight
[c]FP-AI-110, [c]FP-AI-111 ..........................
[c]FP-AI-100, [c]FP-AI-102 ..........................
Power on and self-test passed
Module configured and ready
10.9 by 10.9 by 9.1 cm (4.3 by 4.3 by 3.6 in.)
136 g (4.8 oz)
145 g (5.1 oz)
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 + A2:2001, Table 1
For EMC compliance, operate this device with shielded cabling.
Power Requirement
CE Compliance
Power from network module
[c]FP-AI-110, [c]FP-AI-111 .......................... 350 mW
[c]FP-AI-100, [c]FP-AI-102 .......................... 400 mW
This product meets the essential requirements of applicable European Directives, as amended for
CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC).......................................... 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit ni.com/hardref.nsf/ and search by model number
or product line.
Environment
Operating temperature..................................... -40 to 70 °C
Storage temperature ........................................ -55 to 85 °C
Relative Humidity ............................................. 10 to 90%, noncondensing
Shock and Vibration
These specifications apply only to Compact FieldPoint. NI recommends Compact FieldPoint if your
application is subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64) ........................................ 10 to 500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6) .......................................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ........................................ 50 g, 3 ms half sine, 18 shocks at 6 orientations;
30 g, 11 ms half sine, 18 shocks at 6 orientations
Module
[c]FP-AI-100, [c]FP-AI-102
[c]FP-AI-110
[c]FP-AI-111
Filter Settings
–
50 Hz
60 Hz
500 Hz
50 Hz
60 Hz
500 Hz
Update Rate
(All Channels)
2.8 ms
1.470 s
1.230 s
0.173 s
1.230 s
1.050 s
0.290 s
Input Bandwidth
(–3 dB)
170 Hz
13 Hz
16 Hz
130 Hz
13 Hz
16 Hz
130 Hz
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • [email protected] • ni.com
3
Global Services and Support
NI has the services and support to meet your needs around the globe
and through the application life cycle – from planning and
development through deployment and ongoing maintenance – and
tailored for customer requirements in research, design, validation, and
manufacturing. We have direct operations in more than 37 countries
and distributors in another 12 locations. Our local sales and support
representatives are degreed engineers, ready to partner with you to find
solutions that best fit your needs.
Local Sales and Technical Support
In offices around the globe, our staff is local to the country so that
you have access to field engineers who speak your language and are
available to consult on your unique needs. We also have a worldwide
support organization staffed with Applications Engineers trained to
quickly provide superior technical assistance. Use our online Request
Support interface (ni.com/support) to define your question, then
speak to or e-mail an Applications Engineer, or access more than
14,000 worldwide measurement and automation professionals
within NI Developer Exchange Discussion Forums. ni.com/support
also provides immediate answers to your questions through self-help
troubleshooting, product reference, and application development
resources. For advanced technical support and software maintenance
services, sign up for Premier Support, a program that provides
expanded hours of support availability and
expedited phone/e-mail response time
(typically four business hours).
Professional Services
Our Professional Services team consists of National Instruments
Applications Engineers, NI Consulting Services, and the worldwide
National Instruments Alliance Partner Program (a network of 600
independent consultants and integrators). Our Professional Services
team can offer services ranging from basic start-up assistance and
collaborative development with
your engineers, to turnkey
system
integration
and
maintenance of your system.
In addition to our NI Alliance Partners, we have developed global
relationships with many industry partners that range from computer
software and hardware companies, such as Microsoft, Dell, Siemens,
and Tektronix. By collaborating with these companies, you receive a
complete spectrum of solutions – from components to turnkey
systems. Find the Alliance Partner directory at ni.com/alliance
Product Services
NI hardware products are warranted against defects in workmanship
and material for one year from the date of shipment. To help you
meet project life-cycle requirements, NI offers extended warranties
for an additional charge. NI provides complete repair services for our
products. Express repair and advanced replacement services are also
available. Or, order your software and hardware installed in PXI and
PXI/SCXI™ systems with NI Factory Installation Services.
Ordering Made Easy
Training and
Certification
CUSTOMER
NEEDS
NI recognizes that both initial
instruction and ongoing education
contribute to your success. NI provides a
variety of training alternatives, from selfpaced tutorials and interactive CDs, to worldwide
hands-on courses taught by experienced instructors – all designed so
that you can choose how to learn about our products. Further, NI offers
certifications acknowledging individual expertise in working with NI
products and technologies. Visit ni.com/training for more information.
Visit ni.com/products to browse product specifications, make
comparisons, or access technical representatives via online chat or
telephone. Worldwide customers can use a purchase order or credit
card to buy in local currency and receive direct shipments from local
NI offices. Our North American Customer Service Representatives
are available Monday through Friday between 7 a.m. and 7 p.m.
Central Time. Outside North America, please contact the NI office in
your country.
Order Status and Service Requests
National Instruments brings you real-time status on current orders at
ni.com/status Similarly, find out the status of open technical support
incidents or hardware repair requests at ni.com/support/servicereq
ni.com • (800) 433-3488
National Instruments • Tel: (512) 683-0100 • Fax: (512) 683-9300 • [email protected]
© 2003 National Instruments Corporation. All rights reserved. Product and company names listed are trademarks or trade names of their respective companies.