MEANWELL PS-120P-54C

120W Single Output Power Supply or Battery Charger
PS-120
series
Features :
AC input range selected by switch
Built-in passive PFC function compliance to EN61000-3-2
With AC ON-OFF switch
3 poles AC inlet with fuse holder
Protections: Short circuit / Overload / Over voltage / Over temperature
Charger type can be selected (Optional)
Charger for lead-acid batteries
2 color LED loading indicator
Open frame models available (Without safety approval)
Low cost, High reliability
2 years warranty
TUV
Rheinland
Product Safety
S:Power Supply
A:Voltage detector
B:Current detector
P A
120 P
geprUfre
Sicherheit
13 C
:O.D.M. number
P:Open P.C.B.
C:With case
13:13.8V
27:27.6V
54:55.2V
P:With PFC
N:None PFC
SPECIFICATION
MODEL
OUTPUT
PS-120-13P/C
PS-120-27P/C
PS-120-54P/C
DC VOLTAGE
13.8V
27.6V
54V
RATED CURRENT
7.2A
4.3A
2.2A
CURRENT RANGE
0 ~ 7.2A
0 ~ 4.3A
0 ~ 2.2A
RATED POWER
99.36W
118.68W
118.8W
RIPPLE & NOISE (max.) Note.2 150mVp-p
200mVp-p
250mVp-p
VOLTAGE ADJ. RANGE
24 ~ 30V
1.0% 8.0%
48 ~ 60V
1.0% 7.5%
VOLTAGE TOLERANCE Note.3
LINE REGULATION
INPUT
12 ~ 15V
3.0% 8.5%
1.0%
1.0%
1.0% 5.0%
LOAD REGULATION
1.0% 6.0%
SETUP, RISE TIME
1000ms, 50ms at full load
HOLD UP TIME (Typ.)
16ms at full load
VOLTAGE RANGE
88 ~ 132VAC / 176 ~ 264VAC selected by switch
FREQUENCY RANGE
47~63Hz
POWER FACTOR (Typ.)
>0.65 (with PFC series)
EFFICIENCY (Typ.)
77%/70%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
3A/115VAC
1.5A/230VAC
COLD START 25A/115VAC
LEAKAGE CURRENT
<1.5mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
81%/76%
1.0%
1.0% 5.0%
82%/78%
50A/230VAC
15 ~ 17V
30 ~ 35V
60 ~ 66V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
RTH2 70
10 detect on RTH2 thermistor
Protection type : Hiccup mode, recovers automatically after fault condition is removed
-10 ~ +60
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.05%/ (0 ~ 45
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFETY &
EMC
(Note 4)
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
MTBF
DIMENSION
PACKING
NOTE
UL60950-1, TUV EN60950-1, EN60335, EN60335-1, EN60335-2-29 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
249.5K hrs min.
MIL-HDBK-217F (25
)
PCB Type:144*90*33mm
External case type:180*96*49mm (L*W*H)
1.1Kg; 16pcs / 17.9Kg / 1.47CUFT(without PFC)
1.24Kg; 16pcs / 20.1Kg / 1.47CUFT(with PFC)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. With PFC I/P range: 95~132VAC/190~264VAC.
6. For open P.C.B. WITH 17.8CFM min. Forced air.
PS-120
120W Single Output Power Supply or Battery Charger
Mechanical Specification
Case No. PS-120A
series
Unit:mm
1
2
3
115
FUSE
CASE:
Output cable length=183cm 5cm
Pin No.
1
2,3
Assignment
DC OUTPUT +V
DC OUTPUT -V
Pin No.
1
2
3
Assignment
AC/L
No Pin
AC/N
49
PCB:
AC Input Connector (CN1) : JST B3P-VH or equivalent
Mating Housing
Terminal
JST VHR
or equivalent
JST SVH-21T-P1.1
or equivalent
180
144
43.
134
5
8
12VDC FAN Output Connector (CN4) : JST B2B-XH or equivalent
Assignment
+V
-V
Mating Housing
JST XHP
or equivalent
ADJ.
Terminal
CN4
JST SXH-001T-P0.6
or equivalent
F4 A/250V
Pin No.
1
2
CN3
+V
JST SVH-21T-P1.1
or equivalent
-V
Terminal
JST VHR
or equivalent
1 2 3 4
Mating Housing
80
Assignment
-V
+V
90
Pin No.
1,2
3,4
5
DC Output Connector (CN3) : JST B4P-VH or equivalent
LED
12
+CN5
1 2 3
SHORT FOR 115V
OPEN FOR 230V
CN1
Switch
115V
230V
Mating Housing
Terminal
JST VHR
or equivalent
JST SVH-21T-P1.1
or equivalent
2 max.
Assignment
Short
Open
33
115/230V selected by switch Connector (CN5) : JST B2P-VH or equivalent
Derating Curve
Static Characteristics (27V)
100
LOAD (%)
60
OUTPUT VOLTAGE (V)
Open frame series
17.8CFM air cooling
(L=15cm face HS)
80
Other series
40
20
-10
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
(HORIZONTAL)
30
350
29
300
28
250
27
200
26
150
25
100
24
50
80
160
85
170
90
180
95
190
100
200
105
210
110
220
115
230
120
240
125
250
OUTPUT RIPPLE (mVp-p)
Ta=25
130
260
INPUT VOLTAGE (VAC) 60Hz
File Name:PA,PB-120-SPEC 2008-05-06