ETC RN2F48I30

Solid State Relays
Analog Full Cycle Switching
Type RN.F...
•
•
•
•
•
•
•
•
Product Description
The analog switching relay provides a number of full cycles,
evenly distributed over a fixed
period, depending of the control input. The input of 4-20 mA
or 0-10 VDC respectively,
corresponds to zero and full
output within a period of 1.28 s
@ 50 Hz (1.07 s @ 60 Hz). This
principle makes the transfer
characteristics fully linear. The
AC solid state relay, 1- and 2 poles
Analog switching for resistive loads (heating)
4-20 mA or 0-10 V controls
Rated operational current 30 and 50 AACrms
Rated operational voltage up to 480 VAC
LED-indication for normal operation and alarm status
IP 20 protection
DIN-rail mountable
Ordering Key
principle operates with zero
switching, thus ensuring a
reduced level of radiated and
wire conducted noise. The 2pole type has alarm LED indication by loss of master
phase. The analogue Full
Cycle Switching is not recommended for light control due
to light-flickering.
RN 1 F 40 V 30
Solid State Relay
Number of poles
Switching type
Rated operational voltage
Control signal
Rated operational current
Type Selection, 1-Pole
Rated
operational voltage
Control
input
Control
supply
Rated operational current
30 A
50 A
120 VAC
4-20 mA
0-10 VDC
12-32 VDC, 24 VAC
RN 1F12I30
RN 1F12V30
RN 1F12I50
RN 1F12V50
230 VAC
4-20 mA
0-10 VDC
12-32 VDC, 24 VAC
RN 1F23I30
RN 1F23V30
RN 1F23I50
RN 1F23V50
480 VAC
4-20 mA
0-10 VDC
12-32 VDC, 24 VAC
RN 1F48I30
RN 1F48V30
RN 1F48I50
RN 1F48V50
Type Selection, 2-Pole
Rated
operational voltage
Control
input
Control
supply
Rated operational current
30 A
50 A
120 VAC
4-20 mA
0-10 VDC
12-32 VDC, 24 VAC
RN 2F12I30
RN 2F12V30
RN 2F12I50
RN 2F12V50
230 VAC
4-20 mA
0-10 VDC
12-32 VDC, 24 VAC
RN 2F23I30
RN 2F23V30
RN 2F23I50
RN 2F23V50
480 VAC
4-20 mA
0-10 VDC
12-32 VDC, 24 VAC
RN 2F48I30
RN 2F48V30
RN 2F48I50
RN 2F48V50
Specifications are subject to change without notice (04.02.00)
1
RN 1F
General Specifications
Operational voltage range
Non-rep. peak voltage
Varistor voltage
Zero voltage turn-on
Operational frequency range
Power factor at rated voltage
Average output power
Output power resolution
CE-marking
Approvals
RN.F12...
RN.F23...
RN.F48...
85 to 140 VAC
800 Vp
275 VAC
< 10 V
45 to 65 Hz
≥ 0.9
0 to 100%
1/64 of 100%
Yes
CSA
85 to 265 VAC
800 Vp
275 VAC
< 10 V
45 to 65 Hz
≥ 0.9
0 to 100%
1/64 of 100%
Yes
CSA
190 to 530 VAC
1000 Vp
510 VAC
< 20 V
45 to 65 Hz
≥ 0.9
0 to 100%
1/64 of 100%
Yes
CSA
Input Specifications
RN.F..I..
Current controlled input
Control current range
Allowable input current
Reverse polarity protected
Voltage drop
4 - 20 mA
50 mA
Yes
10 VDC @ 20 mA
RN.F..V..
Voltage controlled input
Supply voltage range
Supply current
Control voltage range
Control input current
21 - 27 VAC, 12 - 32 VDC
30 mA @ 24 VAC/32 VDC
0 - 10 V
0.1 mA @ 10 VDC
Output Specifications
Rated operational current
AC1
@Ta=30°C
“
@Ta=40°C
“
@Ta=50°C
“
@Ta=60°C
Zero crossing detection
Min. operational current (per pole)
Rep. overload current t=1 s
(Tj init.=25°C)
Non-rep. surge current t=10 ms
(Tj init.=25°C)
Off-state leakage current,
@ rated voltage and frequency
(Tj.=125°C, max.)
I2t for fusing t=1 to 10 ms
Critical dV/dt off-state
RN.F..30
RN.F..50
30 A
25 A
23 A
20 A
Yes
500 mA
50 A
50 A
38 A
30 A
Yes
500 mA
55 A (rms)
125 A (rms)
< 250 Ap
< 600 Ap
< 6 mA
310 A2s
500 V/µs
< 6 mA
1800 A2s
500 V/µs
Thermal Specifications
Operational temperature
Storage temperature
Junction temperature
Rth junction to ambient (AC load)
2
RN.F..30
RN.F..50
-20° to +70°C (-4° to +158°F)
-20° to +100°C (-4° to +212°F)
< 125°C (257°F)
2.8 K/W
-20° to +70°C (-4° to +158°F)
-20° to +100°C (-4° to +212°F)
< 125°C (257°F)
1.7 K/W
Specifications are subject to change without notice (04.02.00)
RN 1F
Housing Specifications
Insulation
Mounting
Weight with RHN1
Weight with RHN2
Housing material
LED window material
Base plate
Potting compound
Terminals
Control terminals nominal
Rated imp. withstand voltage
Input to output
Rated imp. withstand voltage
Output to heatsink
Min.
Mounting torque max.
Power terminals nominal
Min.
Mounting torque max.
Heatsink compound used
DIN-rail 35 mm
470 g
780 g
Glass reinforced noryl SE1GFN1
PC Lexan 141R
Aluminium, nickel plated
Polyurethane, Casco Nobel
Screw with captive wire clamp
4 mm2 or 2 x 2.5 mm2
AWG 12 or 2 x AWG 14
0.5 mm2, AWG 20
0.6 Nm
10 mm2 or 2 x 6 mm2
AWG 6 or 2 x AWG 10
1 mm2, AWG 16
2.0 Nm
Dow Corning 340
4000 Vimp
4000 Vimp
Environment Specifications
Humidity max.
95%, no condensation
Dimensions
Dimensions with RHN 1 (30 A)
(H x W x D)
120 x 45 x 110 mm
Dimensions with RHN 2 (50 A)
(H x W x D)
120 x 90 x 110 mm
Dimensions
89
103
70
120
4
71,6
37
71,6
37
45
93
45
20
4
20
70
120
60
60
30
30
103
RHN1
72
33,7
Note: all dimensions in mm
Note: all dimensions in mm
RHN2
Wiring Diagrams
Current Control
4 - 20 mA
+
L1
T1
Single-pole relay
Voltage Control
_
A 1 A2
0 - 10 VDC
+
4 - 20 mA
Current Control
_
L1
A1 A2
T1
A3 A4
Control
Supply
Specifications are subject to change without notice (04.02.00)
+
0 - 10 VDC
Voltage Control
_
+
_
L1
L2 A 1 A2
L1
L2
T1
T2
T1
T 2 A3 A4
Double-pole relay
A1 A 2
Control
Supply
3
RN 1F
Terminal Layout
1-pole RN..
2-pole current controlled input
2-pole RN..
A1
L1
Functional Diagrams
A2
L1
L2
A1
A2
Master
VAC/VDC
VAC
/ VDC(A3, A4 only used for voltage control)
A3
A4
L1
+ A1
control
signal
_ A
2
X
X
C/V
T1
Slave (2-pole version)
X
A3
T1
A4
T1
T2
A3
L2
X
A4
T2
Shown with RHN1
Applications
Single and double pole relay application
Line-Neutral
Double pole relay in 3-phase application
Star and delta application (Economy Switching only)
L1
L2
L3
L1
L2
N
4