SYSTEMSENSOR RR2

RR2
Polarity Reversal
Relay Module
Model
RR2
RR2
General Description
The RR2 Polarity Reversal Relay
Module is intended for use with
2-wire and 4-wire detectors with
built-in sounder, such as the following
System Sensor models: 2100AT,
2112/24AT, 2112/24ATR and
2112/24AITR. Per NFPA requirements, the RR2 is designed to allow
all detectors on a loop to sound when
one goes into alarm. The RR2 can differentiate between steady and pulsed
panel outputs.
Product Overview
Specifications
Can be used with a single alarm
output panel that provides both
coded (pulsed) output for fire and
continuous output for burglary.
Operating Voltage Range:
8.5 to 35 VDC
Maximum Operating Current
25mA
Relay Contacts:
2A at 35 VDC
Fulfills NFPA 72 requirement for
sounder models
Operating Temperature Range:
32° to 131° F (0° to 55° C)
Operating Humidity Range:
5% to 95% non-condensing
Dimensions:
2 1/2" x 2 1/2" x 1"
Wire connections:
18 AWG stranded, tinned, 16" long
Designed for use with System
Sensor 2100 Series sounder
models
Colored wires facilitate easy
installation
Compatible with 2-wire and
4-wire smoke detectors
Can be used with 12 VDC and
24 VDC systems
Plug-in quick disconnects for
easy wiring
Frequently Asked Questions
Q. What advantage does the RR2 have over the RR1?
A. The RR2 has the ability to differentiate between
continuous and pulsed panel outputs and can be
used on single output panels.
Q. Are there any special wiring instructions to follow with
the RR2?
A. Polarity should be observed and the RR2 must be
connected to an auxiliary power supply.
Q. What panel types are compatible with the RR2?
A. The RR2 can be used with 2-wire, 4-wire, 12 VDC or
24 VDC single or combination output panels.
Q. What kind of panel outputs are required for use with
the RR2?
A. The RR2 can be used with fire control panels with a
bell/alarm output or an alarm relay output.
Q. Does the RR2 operate with Ademco panels? Are
separate Ademco modules also required?
A. The RR2 operates with Ademco panels and does not
require a separate Ademco module.
Q. Does the RR2 accommodate more than one 2-wire
sounder detector (2100AT) on a loop?
A. Yes, more than one model 2100AT can be placed on a
zone when the panel switches to a reverse polarity, noncurrent-limited auxiliary power supply*. Refer to
wiring diagrams below for specific 2-wire detector
wiring.
Q. Does the RR2 operate with continuous and coded
(pulsed) alarm signals?
A. The RR2 offers a field-selectable switch for setting the
RR2 for continuous or coded outputs.
* Current supply must be adequate per appropriate calculations.
2-Wire System Triggered from IAC/Bell Circuit:
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
PURPLE
T+
EOL
BROWN
OUT+
UL LISTED
ALARM
CONTROL
PANEL
+
YELLOW
IN+
–
ORANGE
IN–
INITIATING
CIRCUIT
+
RED
PWR+
–
BLACK
PWR–
AUX POWER
+
+
–
A+
A-
WHITE
OUT–
+
+
–
A+
A-
Power
Power
Not
Used
Not
Used
+
+
–
–
NOTE:
If optional Style A (Class A)
wiring is used, a second RR2
module must be added to
enable concurrent loop
polarity reversal.
RA400Z
RA400Z
2-Wire System Triggered from Alarm Relay Contact:
PURPLE
T+
ALARM
RELAY
(NO Contact)
EOL
BROWN
OUT+
UL LISTED
ALARM
CONTROL
PANEL
+
YELLOW
IN+
–
ORANGE
IN–
INITIATING
CIRCUIT
+
+
–
A+
A-
WHITE
OUT–
RED
PWR+
–
Power
Not
Used
Not
Used
+
+
+
+
–
A+
A-
Power
+
–
AUX POWER
–
RA400Z
BLACK
PWR–
RA400Z
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/736-7672
Fx: 630/377-6495
Documents-on-Demand:
800/736-7672 x3
Web: www.systemsensor.com
System Sensor in Canada
Ph: 905/812-0767
Fx: 905/812-0771
System Sensor in China
Ph: + 86.29.524.6253
Fx: + 86.29.524.6259
System Sensor in the Far East
Ph: + 852.21919003
Fx: + 852.27366580
System Sensor in Europe
Ph: + 44.1403.276500
Fx: + 44.1403.276501
System Sensor in Singapore
Ph: + 65.273.2230
Fx: + 65.273.2610
System Sensor in Australia
Ph: + 613.54.281.142
Fx: + 613.54.281.172
©2001 System Sensor. The company reserves the right to change product specifications without notice.
System Sensor in India
Ph: + 91.11.558.2119
Fx: + 91.11.527.6815