OMRON S82S

Switch Mode Power Supply
S82S (3/7.5-W Models)
CSM_S82S_DS_E_2_1
Miniature DIN Rail Mounting DC-DC Power
Supplies
• 65 mm depth enables mounting onto control panels with
100 mm depth.
• Inputs: 10.2 to 27.6 VDC (DC input)
• 7.5-W models provide both ±12-V and ±15-V outputs.
• A complete lineup with 10 different models.
• UL and CSA approved.
• RoHS-compliant
! Refer to Safety Precautions for All Power Supplies.
Model Number Structure
■ Model Number Legend
Note: Not all combinations are possible. Please refer to List of Models in Ordering Information, below.
S82S 1
2
3
1. Input Voltage
7: 12 to 24 VDC
2. Power Ratings
3: 3 W
7: 7.5 W
3. Output Voltage
05: 5 V
12: 12 V
15: 15 V
24: 24 V
27: ±12 V
28: ±15 V
Ordering Information
■ List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
Power ratings
3W
7.5 W
Output voltage
Output current
Model
5V
0.6 A
S82S-7305
12 V
0.25 A
S82S-7312
15 V
0.2 A
S82S-7315
24 V
0.13 A
S82S-7324
5V
1.5 A
S82S-7705
12 V
0.6 A
S82S-7712
15 V
0.5 A
S82S-7715
24 V
0.3 A
S82S-7724
±12 V
0.3 A (+12 V)/0.2 A (–12 V)
S82S-7727
±15 V
0.2 A (+15V)/0.2A (–15 V)
S82S-7728
1
S82S
Specifications
■ Ratings/Characteristics
DC input
Item
3W
Efficiency (typical)
Input
Output
(See note
2.)
Voltage
Single output 7.5 W
Dual Output 7.5 W
60% to 73% (Varies with specifications.)
AC
No
DC
10.2 to 27.6 VDC
Current (See note 1.)
0.6 A max.
Noise filter
Yes
Voltage adjustment range
±5% (See note 3.)
Ripple (See note 1.)
2% (p-p) max.
Input variation influence
0.5% max. (10.2 to 27.6 VDC input, 100% load)
Load variation influence
1.5% max.
1.2 A max.
None (See note 4.)
+V: 1.5% max.
–V: 3% max.
Temperature variation influence 0.05%/°C max.
Additional Overload protection (See note 5.) 105% min. of rated load current, voltage drop, automatic reset
function
Other
Ambient operating temperature
Refer to the derating curve in Engineering Data
Storage temperature
−25 to 65°C
Ambient operating humidity
25% to 85% (storage humidity: 20% to 90%)
Dielectric strength
2.0 kVAC, 50/60Hz for 1 min.
(between all inputs and outputs/PE terminal)
Insulation resistance
100 MΩ min. at 500 VDC (between all outputs and inputs/PE terminal)
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
294 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator
Yes (color: green)
Approved standards
Refer to List of Certified Models for details.
Weight
150 g max.
1.5 kVAC, 50/60Hz for 1 min.
(between all inputs and outputs/PE terminal)
Note: 1. A 100% load for rated input voltage.
2. Output characteristics are measured at the power supply output terminals.
3. If the output voltage adjuster (V.ADJ) is turned, the voltage will increase by more than 50% of the voltage adjustment range. When
adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
4. The settings for the output voltage must be within the following range:
+V: ±1% of the rated value
–V: ±5% of the rated value
5. Refer to Overload Protection on page 4 for details.
2
S82S
Connections
■ Block Diagrams
Single Output
Fuse (3 A)
Noise filter
Rectifier
Drive
overload
protection
circuit
Detection
Photocoupler
Dual Outputs
Fuse (3 A)
Noise filter
Rectifier
3-terminal REG
Drive
overload
protection
circuit
Rectifier
Detection
Photocoupler
Construction and Nomenclature
■ Nomenclature
Terminal Arrangement
Single Output Models
6
Dual Output Models
1
1
1
1. DC Output Terminals: Connect the load lines to these
terminals.
2. Input Terminals: Connect the input lines to these
terminals.
S82S-7724
4
Note: The fuse is located on the (+V) side. It is NOT user
replaceable.
4
5
3. Protective earthing terminal: Connect a ground line to
this terminal.
4. Output LED Indicator (DC OUT ON): Lights while a DC
output is ON (for the Dual Output Models, this indicator is
lit when the +V DC output is ON).
5. Output voltage adjuster (V. ADJ): Use to adjust the
output voltage.
2
3
2
3
6. NC Terminals: Vacant terminals.
3
S82S
Engineering Data
Load (%)
■ Derating Curve
120
Note: The derating curve depends on the mounting direction
of the Power Supply
100
(A)
80
(A)
(B)
(B)
60
40
20
Standard Mounting
0
−20
−10
0
10
20
30
40
50
60
Face-up Mounting
70 80
Ambient temperature (°C)
■ Overload Protection
Output voltage (V)
The power supply is provided with an overload protection function
that protects the Power Supply from possible damage by overcurrent.
When the output current rises to 105% or higher of the rated current,
the protection function is triggered, automatically decreasing the
output voltage. When the output current falls within the rated range,
the overload protection function is automatically cleared.
■ Inrush Current, Startup Time,
Hold Time
Input ON
Input OFF
AC
input
voltage
Inrush current on input application
AC
input
current
96.5%
90%
Output
voltage
0
50
100 ms (max.) startup time
20 ms (min.)
hold time
100
Output current (%)
The values shown in the above diagram are for reference only.
Note: Internal parts may occasionally deteriorate or be damaged if a
short-circuit or other overcurrent state continues during
operation. Eliminate the overcurrent state as soon as possible.
Dual Output Models
The total output power for the +V output and −V output is detected for
the protection operation (i.e., total overcurrent protection), but this
condition varies depending on –V output status. –V output has an
independent short-circuit protection feature.
4
S82S
Dimensions
Note: All units are in millimeters unless otherwise indicated.
S82S-73@@ (3W)
S82S-77@@ (7.5W)
37.5
9.8
Mounting Holes
65
4
Mounting bracket
(provided with the model)
75
61
35
L
4.6
(Sliding 7 max.)
Six, M3.5
M4 or 4.5 dia.
27
Note: If more than one Power
Supply is installed in a row,
keep a distance of 20 mm
min. (L = 20 mm min.)
between each adjacent
Power Supply.
7.3 *
* A distance of 7.3 mm is required between the
model and the mounting surface when the
mounting bracket provided with the model is used.
■ Accessories
Note: All units are in millimeters unless otherwise indicated.
Mounting Bracket
Used when not mounting the Power Supply directly on the DIN Rail.
1.8
Two, 4.5±0.1 dia.
1.2
25±0.15
35±0.15
27±0.1
37.5±0.1
7.3
■ DIN Rail (Order Separately)
Mounting Rail (Material: Aluminum)
PFP-100N2
PFP-100N
PFP-50N
16
7.3±0.15
4.5
4.5
35±0.3
15
25
10
25
25
1,000 (500)
(see note)
10
25
15 (5)
(see note)
27±0.15
1
35±0.3 27
15
25
10
25
25
1,000
10
25
15
24
29.2
1
1.5
Note: The values shown in parentheses are for the PFP-50N.
5
S82S
Safety Precautions
!CAUTION
DIN Rail Mounting
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or repair
the Product or touch the interior of the Product.
Minor burns may occasionally occur. Do not touch the
Product while power is being supplied or immediately
after power is turned OFF.
A
Fire may occasionally occur. Tighten terminal screws to
the specified torque of 0.74 N·m (M3.5).
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
B
When mounting to a DIN Rail, lower the S82S onto the Rail until the
Rail stopper clicks into space, hook section A over the edge of the
Rail, and push in the direction of B.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal or
conductors or any clippings or cuttings resulting from
installation work to enter the Product.
Mounting
Rail stopper
To improve and maintain the reliability of the power supply over a
long period of time, adequate consideration must be given to heat
radiation.
The power supply is designed to radiate heat by means of natural airflow. Therefore, mount the power supply so that air flow takes place
around the power supply.
30 mm min.
To remove the S82S from the DIN Rail, insert a screwdriver into
section C and pull the S82S away from the Rail.
Serial or Parallel Operation
No serial or parallel operation is available.
The positive and negative output terminals of a Dual Output Model
cannot be connected in series to operate.
Incorrect
Air
+V
When mounting two or more power supplies side-by-side, allow at
least 10 mm spacing between them, as shown in the following
diagram.
Forced air-cooling is recommended.
INPUT
−V
+V
10 mm min.
INPUT
−V
Incorrect
+V
INPUT
−V
+V
INPUT
Wiring
−V
Do not apply more than 75-N force to the terminal block when
tightening it.
Minimum Output Current
(S82S-7727 and S82S-7728)
The minimum output current of the S82S-7727 and S82S-7728 is
restricted by the output voltage and control method.
Note: All the outputs of the S82S-7727 and S82S-7728 are controlled
by the +V output. If the +V output current falls to 10% or less of
the rated output, the –V output voltage may drop.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
6
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2008.12
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2008 All Right Reserved.