EMERSON-NETWORKPOWER UFE2000-9-D

Embedded Power for
Business-Critical Continuity
Rev.06.14.11_47
UFE / UFR Series
1 of 6
UFE / UFR Series
Up to 6000 Watts
Total Power:
Input Voltage:
# of Outputs:
Output:
Up to 6000 W
85 - 264 Vac
Single + Aux
24 V & 48 V
Special Features
• Rack mounted chassis (1U, 19”)
• 3 hot pluggable rectifiers per 1U
chassis, up to 4 kW redundant or
6 kW available power
(180 - 264 Vac input)
• Up to 2.6 kW redundant or
3.9 kW available per shelf at
90 - 132 Vac input
• Stackable to 6U high to provide
up to 36 kW available power
• Class B conducted EMI EN55022
(See Note 1)
• Automatic fan speed control with
fault reporting
• Auxiliary standby output, 11 V at
approximately 2.8 W
• High density up to 22 W/in3
• High efficiency up to 91%
• Floating as well as isolated main
output voltage allows positive or
negative polarity operation
• EU directive 2002/95/EC
compliant for RoHS
• 2 year warranty
• PMBus compliant
Safety
•VDE EN/IEC60950-1
•UL/cUL60950-1
Electrical Specifications
Output
Output Power:
Main output
Auxiliary output
See Table 1
11 V ±15%, 2.875 W
Lin­­­­e regulation:
Low line to high line
±0.15% max.
Load regulation (active share mode):
Full load to min. load
±0.15% max.
Turn-on delay:
(See Note 4)
5.0 s max.
Ambient temp. coefficient:
At full load, min. Vin
± 0.005%/°C
Voltage adjustability:
Adjustable PMBus command
(See Note 6)
Output setpoint accuracy:
48 Vout
24 Vout
42-57 Vdc
21-28.5 Vdc
Default output voltage:
setting 25 ºC
48 Vout (active default)
24 Vout (active default)
48 V ± 0.5% @ 41 A
27 V ± 0.5% @ 48 A
Voltage droop:
(operation set PMBus command)
24 Vout
40.3 mV/A ± 3.0% from
10 A up to power limit
80.6 mV/A ± 3.0% from
10 A up to power limit
± 0.5%
48 Vout
Total error band:
-40 °C to +70 °C, FL range
±1.0% max.
Overshoot/undershoot:
Main output @ turn-on/off
0%/0%
Ripple and noise (20 MHz):
Main output, -5 ºC and above
Auxiliary output
500 mV pk-pk, 150 mV rms
400 mV pk-pk, 150 mV rms
Dynamic regulation (except droop mode):
Peak dev., 25% load step Recovery 2.5% max.
time
1 ms max.
(I1-I2) / ILIMIT x 100
15% max.
Current sharing (See Note 3):
All specifications are typical at nominal input, full load at 25 °C ambient unless otherwise stated.
Embedded Power for
Business-Critical Continuity
Input
Input voltage range:
(See note 2)
Input frequency range:
Input current:
Ground leakage current:
Input fuse (internal)
Power factor:
Undervoltage lockout:
(power up)
Undervoltage lockout:
(power down)
Rev.06.14.11_47
UFE / UFR Series
2 of 6
88 - 264 Vac
176 - 264 Vac
47 - 63 Hz
15 A max.
2 mA max.
30 A Notes
0.98 1 Final EMI performance is system/shelf
dependent.
176 Vac max.
2 Auto ranging sets power limit based on input
88 Vac. max
voltage at turn on.
162 Vac min. 3 The difference in output current among any
two rectifiers operating in parallel does not
LED warning @ 176 V max.
exceed a value equal to 15% of the rated
current limit. This specification applies for
76 Vac min.
operation with any output current from no
LED warning @ 88 V max.
load to 110­% of maximum.
AC to safety ground
Both lines fused
50 to 100% load
High line range
Wide line range
High line range
Wide line range
General Specifications
Electrical insulation:
Switching frequency:
Approvals and standards:
Weight:
Hold-up time:
Input/output
Input/chassis
Fixed
3000 Vac / 4242 Vdc
1500 Vac / 2121 Vdc
450 kHz
VDE EN/IEC60950-1
UL/CUL60950-1
5.5 lbs
20 ms min.
20 ms min.
279,069 hours
71 dB max.
58 dB typ.
48 Vout at rated output power
24 Vout at rated output power
Telcordia SR-332 Issue 1
Over all conditions
25 ºC ambient at rated output power
MTBF (@25 ºC):
Acoustical noise:
4 Maximum 15 minute warm up time at light
loads below -15 °C. See Application Note 212
for cold start timing data.
5 For operation above 1,524 m (5,000 ft),
maximum operation temperature is derated
by 2 °C per 305 m (1,000 ft).
6 Output voltage can be modified on the fly
between
21-28.5 V (24 V model) or 42-57 V (48 V
model) PMBus command.
7 PM BUs communication. Pin names in
parenthesis refer to the PMBus version names.
UFE2000-96S48PJ and UFE130096S24PJ use
PMBus.
EMC
Conducted emissions:
Immunity:
Harmonic current:
ESD air/contact:
Surge:
Fast transients:
Flicker:
Magnetic field:
Radiated immunity:
Conducted immunity:
EN55022, FCC part 15
Class B (when installed in system)
EN61000-3-2
EN61000-4-2
EN61000-4-5
EN61000-4-4
EN61000-3-3
EN61000-4-8
EN61000-4-3
EN61000-4-6
Compliant
Level 3
Level 3
Compliant
Compliant
Level 3
Level 3
Ordering Information
Rated Output
Power
Output Voltage
Vout
Power Limit
Output
+15% / -0% Vout
Current (Min)
(min)
Min
Max
1300 W
21 v
28.5 V
0A
1300 W
1300 W
2000 W
1300 W
2000 W
1300 W
2000 W
42 V
42 V
42 V
42 V
42 V
42 V
57 V
57 V
57 V
57 V
57 V
57 V
0A
0A
0A
0A
0A
0A
1300 W
2000 W
1300 W
2000 W
1300 W
2000 W
Line Range at Turn Operating
Current Limit
Model Numbers (7)
On (Auto Ranging) Line Range (Vout) < Vout (min)
24 Vout Models
90-264 Vac
48 Vout Models
90-264 Vac
180-264 Vac
90-264 Vac
180-264 Vac
90-264 Vac
180-264 Vac
65 A
65 A
33 A
52 A
33 A
52 A
33 A
52 A
33 A
52 A
33 A
52 A
33 A
52 A
Order Number
UFE1300-96S24C1J
UFE1300-5
UFE2000-96S48PJ
UFE2000-9
UFE2000-96S48PDJ
UFE2000-9-D
UFE2000-96S48PHDJ UFE2000-9-HD
Rack Ordering Information
Rack Model Number
UFR6000-00J
UFR6000-01J
UFR6000PJ
Hot Plug Interface
Yes
Yes
Blank Panel
Number of Power Modules per Pack
3
2 + 1 (Split Rack)
3
Embedded Power for
Business-Critical Continuity
Rev.06.14.11_47
UFE / UFR Series
3 of 6
Environmental Specifications
Thermal performance:
(See Notes 4 and derating curves)
Operating
Non-operating
Cold Start
-33 °C to +70 °C
-40 °C to +100 °C
-40 °C
Relative humidity:
non-condensing
Operating
Non-operating
Up to 80%
Up to 95%
Altitude:
(See Note 5)
Operating
Non-operating
10,000 feet max.
35,000 feet max.
Vibration:
Operating
Non-operating
1.0 G peak
1.5 G peak
Shock:
Operating
Non-operating
10 G peak / 11 ms
40 G peak / 11 ms
Protection
Power limit:
Vo > Vout min
± Rated power +15%/-0%
Current limit:
Constant current limiting - brickwall
Vo ² Vout min
Short-circuit:
Hiccup mode at
Vo < 40 Vdc
Vo < 20 Vdc
Output shutdown
Latching after 1 retry
Overvoltage:
Thermal:
Self protecting
OR-ing fault
(See Note 7)
Tested via I C or PMBus
± limit, ± 8%
200 ms on / 1/8 s off
60 V max.
32 V max.
Non-latching
LED alarm (by read) in case of OR-ing
fault
2
Communication Monitoring Readout Accuracy
Current:
Valid from 15% to max. load
Voltage:
Measured before output OR-ing
Temperature:
Measured Internal output OR-ing
± 15%
± 5%
± 5 °C
Hours counter:
± 36 s/hours approx.
Part Number System with Options
Product
Family
UFE
UFE
Rated Output
Power
2000 Input
Range
Standard
Compliance
9 6 Type of
Output
Output
Voltage
S
48
48 UFE = Universal 1300 = 1300 Watts 9 = Universal 6 = UL/CSA/VDE S = Single
Input
2000 = 2000 Watts
Class A/B
Front-End
with PFC
48 = 48 V
24 = 24 V
Communications
Type
C
P C1 = I C serial
communication
P = PMBus serial
communication
2
Option Code
D
None = Active Ishare
D = Droop Ishare
HD = PS Enable
HI/Droop
Special
RoHS
Modification Compliance (9)
J
XX
J
J = Pb free
(RoHS 6/6
compliant)
Embedded Power for
Business-Critical Continuity
Rev.06.14.11_47
UFE / UFR Series
4 of 6
Mechanical Drawing
5.51 ± 0.02
(140.0 ±0.5)
9.58 ± 0.02
(243.3 ±0.5)
WITH PEM SCREW
FASTENED
10.74 ± 0.02
(272.8 ±0.5)
FRONT FACE TO
CONNECTOR
11.95 ± 0.03
(303.5 ±0.8)
5.56 ± 0.03
(141.2 ±0.8)
1.60 ± 0.02
(40.6 ±0.5)
0.17 ± 0.01 (4.3 ±0.3)
Dimensions in Inches (mm)
Power Supply Connector
Mating Connector
Molex: 87663-4006
Molex: 87664-2004
Pin
Tyco: 2-1450330-8
Tyco: 1450370-5
P1
L1
FCI Berg: 51939-180
FCI Berg: 51915-070
P2
L2
P3
PEG
Power Supply Connector
SIGNAL
POWER
P1
P2
P3
1 2 3 4 5 6 P4
POWER
P5
P6
P7
D
C
B
A
Power Connections Layout
(Looking into Connector Side of UFE Power Supply)
Power Supply Connector Pinout
D
C
B
A
1
Sense-
Sense+
GND
Shortpin
2
Present-L
GND
PS-ID0
GND
3
PS-ID3
PS-ID2
GND
12V-AUX
4
GND
SCL
PS-ID1
GND
5
SDA
GND
GND
I C-En-H
(Comm-En-H)
6
SMBALERT#
Ishare
DC-OK-L
PS-EN (Control)
P4
DC_N
P5
DC_N
P6
DC_P
P7
DC_P
2
Embedded Power for
Business-Critical Continuity
Rev.06.14.11_47
UFE / UFR Series
5 of 6
Rack Specifications
11.777 ± .015
10.326 ± .015
.256 ± .015
R.125 ± .015
0.389 ± .015
.125 ± .010
1.740 ± .015
1.250 ± .010
.220 ± .010
15.570 ± .015
16.515 ± .015
18.435 ± .010
18.880 ± .015
14.972 ± .010
14.559 ± .015
15.259 ± .015
15.000 ± .015
17.312 ± .015
1.740 ± .015
Rack Signal Connector Pinout
Pin No.
Function
Pin No.
Signal Connector (1 per shelf)
Function
Shelf Connector
Mating Connector
1
48V Sense+
14
48V Ishare
Molex: 52986-2679
Molex: 52316-2619
2
Ground
15
Unit 1 Present
Tyco: 2-178238-4
Tyco: 2-5175677-4
3
48V Sense-
16
Ground
4
Ground
17
Unit 2 Present
5
PS-EN (Control)
18
Ground
6
DC1-OK0-L
19
Unit 3 Present
7
DC2-OK-L
20
Ground
DC3-OK-L
21
SCL
8
AC Input Connector (3 per shelf)
Shelf Connector
Mating Connector
IEC320 C20 Socket
IEC320 C20 Plug
(Straight Entry)
Shelf DIP Switch Table
9
I C-En-H-1 (Comm-En-H)
22
Ground
Shelf Number
DIP Switch
DIP Switch
10
I2C-En-H-2 (Comm-En-H)
23
SDA
1
Up
Up
11
I C-En-H-3 (Comm-En-H)
24
Ground
2
Up
Down
2
2
12
Ground
25
SMBALERT#
3
Down
Up
13
12V-Aux
26
N/C
4
Down
Down
Embedded Power for
Business-Critical Continuity
­Americas
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone:+1 760 930 4600
Facsimile: +1 760 930 0698
OUTPUT POWER (W)
1400
1300
All Output Voltages
Below
120 Vac
1200
120 Vac to
149 Vac
1100
1000
40
45
50
55
60
65
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone:+44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
Asia (HK)
70
AMBIENT TEMPERATURE (ºC)
Figure 1 - Thermal Derating Curve for UFE2000-96S48J Model
Low Line Input Voltage
2100
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone:+852 2176 3333
Facsimile: +852 2176 3888
For global contact, visit:
2000
OUTPUT POWER (W)
Rev.06.14.11_47
UFE / UFR Series
6 of 6
www.Emerson.com/EmbeddedPower
1900
Above 180 Vac
1800
52-57 V
48 V
42 V
1700
1600
techsupport.embeddedpower
@emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
1500
1400
40
45
50
55
60
65
70
AMBIENT TEMPERATURE (ºC)
Figure 2 - Thermal Derating Curve for UFE2000-96S48J Model
High Line Input Voltage
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
1400
POWER RATING (W)
Embedded Computing
Embedded Power
1300
Monitoring
Outside Plant
1200
Power Switching & Controls
1100
Precision Cooling
Racks & Integrated Cabinets
1000
Services
40
45
50
55
60
65
70
AMBIENT TEMPERATURE (ºC)
Figure 3 - Thermal Derating Curve for UFE1300-96S24J Model
All Conditions
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co. ©2011 Emerson Electric Co.