ETC 202404

Moeller NK2528-1024GB
3
easy Control Relay
Description
easy control relay
SIMPLY easy – Clever switching and controlling
easy is a compact, user-friendly control relay for simple control applications. Applications range from building and domestic automation to machine and plant control.
easy has built-in user-friendly operating elements and an LCD display. Just connect
up easy and draw your circuit diagram on the display by pressing the buttons. easy
works with make contacts, break contacts, and relays.
Enter your circuit diagram in easy just like you sketched it on paper. easy has basic
and special functions for relay and contactor controls, and lots more.
You can make changes to your circuit just by pressing the buttons. Time consuming
rewiring is not necessary.
SIMPLY easy – Applications everywhere
• Building and domestic automation, controllers for lighting, doors, window
shutters...
• Controls for ventilators, rotating doors, greenhouses, exterior lighting, window
controllers, shop display lighting control...
• Controls for temperature, ventilation and brightness levels...
• Controls for machines and plant, presses, conveyor belts, oscillating conveyors,
sorters, pumps...
SIMPLY easy – Open for change
The easy circuit diagram can be entered and modified just by pressing the buttons.
S1
K1
S4
S6
S5
T1
T1
K1
K2
T1
SIMPLY easy – Everything built in
(some features depend on the type)
• An LCD display for showing the circuit diagram
• Operation buttons for wiring, value entry or switching
• 4 relay outputs with max. 10 A output current or 0.5 A transistor outputs up to
2 A, suitable for parallel connection
• Circuit diagrams can be created with make contacts, break contacts, relays,
series and parallel circuits
• Voltage supply (24 V DC or 115/230 V AC)
• 8/12 digital inputs, expandable to 24 digital inputs
(115/230 V AC or 24 V DC)
• 2 analog inputs (DC models only, two digital inputs can also be used for analog
signals)
• Non-volatile circuit diagram and parameter memory (EEPROM)
(retentive data) (EEPROM)
• Display of message texts, setpoint and actual values for timers, counters, time
and analog values
• Socket for external memory card or PC interface cable
• Time switch with time and weekday(s)
• DST setting (summer time/winter time change)
• Protect your circuit diagram and settings against unauthorized changes with a
password to protect your know-how
• Optional debounce (input delay) function (reliable switching with fast signals)
• Selectable menu languages, 5 and 10 languages (D, GB, F, I, E, for EASY600 also
P, NL, S, PL,TR)
• 4 cursor buttons can also be used as input contacts in the easy circuit diagra
(built in manual operation mode)
• Local or remote expansion of inputs and outputs.
Remote expansion by means of two wire cable up to 30 m between basic unit
and expansion unit
• Large ambient temperature range from –25 °C to +55 °C
4
Moeller NK2528-1024GB
easy Control Relay
Description
SIMPLY easy – Compact and practical
easy has a 45 mm as a standard dimension (4/6 space units) for installing in
standard domestic distribution panels. easy can be clipped to a top-hat rail or
screwed to a mounting plate for rugged environments. easy’s dimensions are
71.5 X 90 X 53 mm or 107.5 X 90 X 53 mm.
Simply network
Connect easy to a data bus as simply as you can expand it.
Connect the expansion unit for the AS-Interface and easy can already communicate
with the bus master via the AS-Interface.
PROFIBUS-DP is just as simple. easy is always a slave on the bus.
Example:
Remote coupling with EASY200-EASY to a two wire cable
PC software
You can also create easy programs on a PC and download them to easy with the
optional PC interface cable. Create, store, simulate and document the circuit diagram offline.
Three display formats are available: DIN EN, ANSI or the easy display.
SIMPLY easy – More than 20 functions in a single device
• Interconnect make contacts and break contacts
• 3 contacts can be connected in series
• Up to 41 circuits (121 for EASY600) can be connected in parallel
• Switch relay coils
• Create switching functions such changeover switches, self-latching relays, single
pulse relays, start-delta starters
• Create timing functions such as on-delayed, on-delayed with random switching,
off-delayed, off-delayed with random switching, single pulse, flashing, up/down
counter
• Time switch
• Compare analog values
• Output texts, setpoint and actual values
• Store retentively the actual values of timing relays, counters, markers, operating
hours counters.
Simply expand
Connect the expansion unit to the basic unit using the connector to add up to
24 inputs and 16 outputs.
The coupling device enables the expansion unit to be expanded up to 30 m away.
5
Moeller NK2528-1024GB
easy Control Relay
Basic Units, Expansion Units
Type
Article No.
Price
See Price
List
Std. pack
Basic Units
24 V DC,
Retentive
DEL
ESC
• 8 digital inputs (2 inputs also usable as analog inputs)
• 4 relay outputs
• LCD display
• Operating buttons
• Screw terminals
Features as per EASY 412-DC-R plus built-in time switch
Features as per EASY412-DC-RC, without keypad an
LCD display
• 8 digital inputs (2 inputs also usable as analog inputs)
• 4 transistor outputs
• LCD display
• Operating buttons
• Screw terminals
• Time switch
Features as per EASY412-DC-TC, without keypad an
LCD display
• 12 digital inputs (2 inputs also usable as analog inputs)
• 8 transistor outputs
• LCD display
• Operating buttons
• Screw terminals
• Time switch
• 12 digital inputs (2 inputs also usable as analog inputs)
• 8 transistor outputs
• LCD display
• Operating buttons
• Screw terminals
• Time switch
• Expandable with EASY.....E
Features as per EASY621-DC-TC, without keypad an
LCD display
ALT
OK
115/230 V AC
115/230 V AC,
Retentive
• 8 digital inputs, 115/230 V AC
• 4 relay outputs
• LCD display
• Operating buttons
• Screw terminals
Features as per EASY 412-AC-R plus built-in time switch
Features as per EASY412-AC-RC, without keypad an
LCD display
• 12 digital inputs, 115/230 V AC
• 6 relay outputs
• LCD display
• Operating buttons
• Screw terminals
• Time switch
• 12 digital inputs, 115/230 V AC
• 6 relay outputs
• LCD display
• Operating buttons
• Screw terminals
• Time switch
• Expandable with EASY.....E
Features as per EASY619-AC-RC, without keypad an
LCD display
EASY412-DC-R
202403
1 off
EASY412-DC-RC
202404
EASY412-DC-RCX
221596
EASY412-DC-TC
207808
EASY412-DC-TCX
212307
EASY620-DC-TC
212309
EASY621-DC-TC
218719
EASY621-DC-TCX
212311
EASY412-AC-R
202405
1 off
EASY412-AC-RC
202406
EASY412-AC-RCX
212308
EASY618-AC-RC
212310
EASY619-AC-RC
218721
EASY619-AC-RCX
212312
Expansion units
24 V DC
115/230 V AC
Coupling unit
• 12 digital inputs
• 8 transistor outputs
• With connector
• 12 digital inputs, 115/230 V AC
• 6 relay outputs
• With connector
• Coupling unit for connecting to an EASY619/621 basic unit
• Terminals for remote expansion up to 30 m to the expansion
unit
• With connector
EASY620-DC-TE
212313
EASY618-AC-RE
212314
EASY200-EASY
212315
1 off
easy Control Relay
Description
6
Moeller NK2528-1024GB
easy Control Relay
Networking, Accessories, Documentation
easy Control Relay
Description
Type
Article No.
Price
See Price
List
Std. pack
Networking
AS-Interface
PROFIBUS-DP
• Linked directly to EASY619/621
• AS-Interface connection
• Slave
• 4 inputs, 4 outputs, 4 parameter bits
• Addressable, 0 to 31
• Linked directly to EASY619/621
• PROFIBUS-DP slave
EASY205-ASI
221598
1 off
EASY204-DP
212316
1 off
CD, menu in 6 languages
Installation WIN 95, 98, WIN NT
8K memory card for storing the entire easy circuit diagram
for EASY412
16K memory card for storing the entire easy circuit diagram
for EASY6..
2 m, for connecting to 9-pin serial interface on a PC
with interface electronics circuit
Simulator with power supply unit, 115/230 V AC / output 24 V DC,
suitable for EASY412-DC...
EASY-SOFT
202407
EASY-M-8K
202408
EASY-M-16
212317
EASY-PC-CAB
202409
EASY412-DC-SIM
212318
1 off
For screw fixing on mounting plate,
3 fixing feet per EASY412,
3 fixing feet per EASY6..,
2 fixing feet per EASY200-EASY
Primary-switched mode, stabilised
2, suitable for parallel connection to increase power output or for
redundant operation at rated power
ZB4-101-GF1
061360
9 off
EASY400-POW
212319
1 off
AWB2528-1304-D
205375
AWB2528-1304-GB
205481
AWB2528-1304-F
205482
AWB2528-1304-I
205483
AWB2528-1304-E
205484
1 off
AWB2528-1316-D
205376
AWB2528-1316-GB
205485
AWB2528-1316-F
205486
AWB2528-1316-I
205487
AWB2528-1316-E
205488
1 off
Accessories
Software
Memory card
Connection cable
Input/output
simulator
Fixing feet
Switched-mode
power supply unit
• Rated input voltage 50/60 HZ: 115/230 V AC
• Rated output voltage (residual ripple): 24 V DC (g 3%)
• Rated output current: 1.25 A
Documentation
Manual for easy control relay
German
English
French
Italian
Spanish
Training guide for easy control relay
German
English
French
Italian
Spanish
7
Moeller NK2528-1024GB
RMQ Titan
Range Selection
Contacts
M = make contact, B = break contact,
f = Safety function by means of
positive opening to
IEC/EN 60 947-5-1
Colour
Plunger
Type
Article No.
Price
See Price
List
Std. pack
Complete units for surface mounting to IP 66
Emergency-stop actuator, tamper-proof to ISO 13 850/EN 418
Pull to release
Max. configuration: 3x M22-(C)K...
1M
M22-PV-KC11/I
216525
2 off
M22-PVS/KC11/IY
216523
2 off
M22-WRS/KC11/I
216526
2 off
–
M22-D-R-X0/K01
216510
5 off
–
M22-D-G-X1/K10
216512
5 off
–
M22-WRK/K10
216518
5 off
M22-PV/K01
216515
5 off
M22-IVS
216400
1 off
1B
14
13
22
21
Key-release mushroom buttons
With 1 key
MS 1 lock mechanism
–
1M
1Bf
14
13
22
21
14
13
22
21
Key-operated buttons
With two keys,
Two positions, stay-put
MS 1 lock mechanism
–
Push-button
Flush
1M
1Bf
–
1Bf
1M
–
21
22
13
14
Selector switch, thumb-grip black
Stay-put/spring-return function can be changed using M22-XC-. coding adapters
Two positions, stay-put
–
1M
–
13
0
14
Complete units for front mounting, IP 66
Emergency-stop actuator, tamper-proof to ISO 13 850/EN 418
Yellow base
Pull to release
–
–
1Bf
21
22
IVS top-hat rail adapter
Front fixing
Notes
Other products are available in the Moeller catalogue supplement, NK 1160-1033 GB
easy Control Relay
Button plate
8
Moeller NK2528-1024GB
easy Control Relay
Technical Data
easy Control Relay
EASY200-EASY
General
Standards and regulations
Dimensions
W H D [mm]
Weight
Mounting
Ambient temperature
Operating ambient temperature
Horizontal/vertical mounting
Mechanical environmental conditions
Pollution degree
Degree of protection (EN 50 178, IEC 60 529, VBG4)
Oscillations (IEC 60 068-2-6)
Shock (IEC 60 068-2-27)
Dropping (IEC 60 068-2-31)
Free fall, in packaging (IEC 60 068-2-32)
Electromagnetic compatibility (EMC)
Electrostatic discharge
(IEC/EN 61 000-4-2, Level 3)
Electromagnetic fields (IEC/EN 61 000-4-3)
Emitted interference, interference immunity
Burst (Level 3)
Power cables
(IEC/EN 61 000-4-4)
Signal lines
High-energy pulses (surge) easy-AC
(IEC/EN 61 000-4-5)
High-energy pulses (surge) easy-DC
(IEC/EN 61 000-4-5, Level 2)
Dielectric strength
Measurement of the air clearance and creepage distance
Dielectric strength
Tools and cable cross-sections
Single-core
Flexible with ferrule
Slot-head screwdriver, width
Tightening torque
Backup/accuracy of real-time clock (only with easy-C)
Clock battery back-up
at 25 °C
at 40 °C
Accuracy of the real-time clock
Retentive memory
Write cycles of the retentive memory
EASY6..-...
EN 55 011, EN 55 022, IEC/EN 61 000-4, IEC 60 068-2-6, IEC 60 068-2-27
35.5 90 53
71.5 90 53
107.5 90 53
(2 space units)
(4 space units)
(6 space units)
70 g
200 g
300 g
Top-hat rail, DIN 50 022, 35 mm or
screw fixing with ZB 4-101-GF1 fixing feet (accessories)
–25 to +55 °C
Cold to IEC 60 068-2-1
Heat to IEC 60 68-2-2
Prevent condensation with suitable measures
0 to +55 °C
–40 to +70 °C
5 to 95%, non-condensing (IEC 60 068-2-30)
795 to 1080 hPa
SO2 10 cm³/m³, 4 days (IEC 60 068-2-42)
H2S 1 cm³/m³, 4 days (IEC 60 068-2-43)
Condensation
LCD display (clearly visible)
Storage/transport temperature
Relative humidit
Air pressure (operation)
Corrosion resistance
Repetition accuracy of timing relays
Accuracy of timing relays
Resolution
EASY412-...
Range “s”
Range “M:S”
Range “H:M”
2
2
IP 20
IP 20
10 to 57 Hz (constant amplitude 0.15 mm)
57 to 150 Hz (constant acceleration 2 g)
18 shocks
(semi-sinusoidal 15 g/11 ms)
Drop height 50 mm
1m
8 kV air discharge
6 kV contact discharge
Field strength 10 V/m
EN 55 011 Class B, EN 55 022 Class B
2 kV
2 kV
2 kV power cables symmetrical
0.5 kV power cables symmetrical
EN 50 178, UL 508, CSA C22.2, No 142
EN 50 178
min. 0.2 mm², AWG 24
max. 4 mm², AWG 12
min. 0.2 mm², AWG 24
max. 2.5 mm², AWG 13
3.5 0.8 mm
0.5 – 0.7 Nm
–
–
–
Normally 64 h
Normally 24 h
Normally g 5 s/day,
~ g 0.5 h/year
–
–
–
g 1 % of value
10 ms
1s
1 min.
–
f 100 000
2
IP 20
9
Moeller NK2528-1024GB
Power supply
Rated voltage (sinusoidal)
Permissible range
Frequency, rated value, tolerance
Input current consumption
at 115/120 V AC 60 Hz
at 230/240 V AC 50 Hz
Voltage dips (IEC/EN 61 131-2)
Heat dissipation
at 115/120 V AC
at 230/240 V AC
Power supply
Rated voltage
Rated value
Permissible range
Residual ripple
Input current at 24 V DC
Voltage dips (IEC/EN 61 131-2)
Power dissipation at 24 V DC
Digital inputs 115/230 V AC
Number
Status display
Electrical isolation
To power supply
Between each other
To the outputs
Rated voltage L (sinusoidal)
0 signal
1 signal
Rated frequency
Input current on 1 signal
R1 to R12, I1 to I6
(EASY 618/619 also I9 to I12)
Input current on 1 signal
I7, I8
Delay time for 0 to 1 and
1 to 0
Debounce ON (I1 to I6/I12)
Debounce OFF (I1 to I6/I9 to I12)
Delay time I7, I8 for 1 to 0
Debounce ON
Debounce OFF
Delay time I7, I8 for 0 to 1
Debounce ON
Debounce OFF
Max. permissible cable length (per input)
R1 to R12, I1 to I6
(with EASY 618/619 also I9 to I12)
I7, I8
EASY412-AC-...
EASY618/619-AC-RC(X)
EASY618-AC-RC
115/120/230/240 V AC
+10/–15 %
90 to 264 V AC
50/60 Hz, g 5 %
100/110/115/120/230/240 V AC
+10/–15
85 to 264 V AC
50/60 Hz, g 5 %
Normally 40 mA
Normally 20 mA
20ms
Normally 70 m
Normally 35 m
20ms
Normally 5 VA
Normally 5 VA
Normally 10 VA
Normally 10 VA
EASY412-DC-...
EASY620/621-DC-TC(X)
EASY620-DC-TE
24 V DC, –15 %, +20 %
20.4 to 28.8 V DC
F5%
Normally 80 mA
10ms
Normally 2 W
24 V DC, –15 %, +20 %
20.4 to 28.8 V DC
F5%
Normally 140 m
10ms
Normally 5 W
EASY412-AC-...
EASY618/619-AC-RC(X)
EASY618-AC-RE
8
LCD display (if provided)
12
LCD display (if provided)
No
No
Yes
No
No
Yes
0 to 40 V AC
79 to 264 V AC
50/60 Hz
6 x 0.5 mA at 230 V AC 50 Hz
6 x 0.25 mA at 115 V AC 60 Hz
0 to 40 V AC
79 to 264 V AC
50/60 Hz
10 (12) x 0.5 mA at 230 V AC 50 Hz
10 (12) x 0.25 mA at 115 V AC 60 Hz
2 x 6 mA at 230 V AC 50 Hz
2 x 4 mA at 115 V AC 60 Hz
2 x 6 mA at 230 V AC 50 Hz
2 x 4 mA at 115 V AC 60 Hz
80 ms (50 Hz), 66n ms (60 Hz)
20 ms (50 Hz), 16n ms (60 Hz)
80 ms (50 Hz), 66n ms (60 Hz)
20 ms (50 Hz), 16n ms (60 Hz)
160 ms (50 Hz), 150 ms (60 Hz)
100 ms (50 Hz/60 Hz)
80 ms (50 Hz), 66n ms (60 Hz)
20 ms (50 Hz), 16n ms (60 Hz)
80 ms (50 Hz), 66n ms (60 Hz)
20 ms (50 Hz), 16n ms (60 Hz)
80 ms (50 Hz), 66n ms (60 Hz)
20 ms (50 Hz), 16n ms (60 Hz)
Normally 40 m
Normally 40 m
Normally 100 m
Normally 100 m
easy Control Relay
easy Control Relay
Technical Data
10
Moeller NK2528-1024GB
easy Control Relay
easy Control Relay
Technical Data
Digital inputs 24 V AC
Number
Status display
Electrical isolation
To power supply
Between each other
To the outputs
24 V DC power supply
Rated value
0 signal
1 signal
Input current on 1 signal
R1 to R12, I1 to I6
(EASY 620/621 also I9 to I12)
Input current on 1 signal
I7, I8
Delay time for 0 to 1
Debounce ON
Debounce OFF
Delay time for 1 to 0
Debounce ON
Debounce OFF
Cable length (unshielded)
Analog inputs
Number
Electrical isolation
To power supply
To the digital inputs
To the outputs
Input type
Signal range
Resolution analog
Resolution digital
EASY412-DC-...
EASY620/621-DC-TC(X)
EASY620-TC-TE
8, 2 of which (I7,I8) can be used as
analog inputs
LCD display (if provided)
12, 2 of which (I7,I8) can be used as
analog inputs, with basic unit
LCD display (if provided)
No
No
Yes
No
No
Yes
24 V DC
< 5.0 V DC I1 to I8
> 15.0 V DC I1 to I6
3.3 mA at 24 V DC
24 V DC
< 5.0 V DC I1 to I12, R1 to R12
> 15.0 V DC
I1 to I6, I9 to I12, R1 to R12
3.3 mA at 24 V DC
2.2 mA at 24 V DC
2.2 mA at 24 V DC
20 ms
Normally 0.25 ms (I1 to I6)
20 ms
Normally 0.25 ms (I1 to I6, I9 to I12)
20 ms
Normally 0.4 ms, I1 to I6
Normally 0.2 ms I7, I8
100 m
20 ms
Normally 0.4 ms I1 to I6, I9 to I12
Normally 0.2 ms I7, I8
100 m
EASY412-DC...
EASY620/621-DC-TC(X)
2
2
No
No
Yes
DC voltage
0 to 10 V DC
0.1 V
0.1
No
No
Yes
DC voltage
0 to 10 V DC
0.1 V
0.1
U[V]
9.9
5.0
0
Input impedance
Accuracy of
Two easy devices
Within a single device
Conversion time, analog/digital
Input current
Cable length (shielded)
5.0
11.2 kO
g 3 % of actual value
g 2 % of actual value (I7, I8), g 0.12 V
Debounce ON: 20 ms
Debounce OFF: every cycle
< 1 mA
30 m
9.9
11.2 kO
11
Moeller NK2528-1024GB
Relay outputs
Number
Type of outputs
In groups of
Parallel connection of outputs
to increase current rating
Circuit-breaker B 16 or fuse 8 AT
Potential isolation to mains supply, inputs
Mechanical lifespan (operations)
Contacts relays
Conventional free air thermal current
Recommended for load
Short-circuit resistance cos 1
Short-circuit resistance cos 0.5 to 0.7
Rated impulse withstand voltage Uimp contact coil
Rated insulation voltage Ui
Rated operational voltage Ue
Safe isolation to EN 50 178
between coil and contact
Safe isolation to EN 50 178 between two contacts
Making capacity
AC-15 250 V AC, 3 A (600 Ops/h)
DC-13 L/R F150 ms 24 V DC, 1 A (500 Ops/h)
Breaking capacity
AC-15 250 V AC, 3 A (600 Ops/h)
DC-13 L/R F150 ms 24 V DC, 1 A (500 Ops/h)
Filament lamp load
1000 W at 230/240 V AC
500 W at 115/120 V AC
Fluorescent tube
10 x 58 W at 230/240 V AC
With ballast
Uncompensated
1 x 58 W at 230/240 V AC
Conventional, compensated
Operating frequency, relays
Device lifetime
Mechanical switching frequency
Resistive lamp load
Inductive load
EASY412-...-R...
EASY618/619-R...
4
Relay
1
Not permissible
6
Miniature circuit-breaker B16 or 8 A fuse (slow)
Yes
300 Veff AC (safe isolation)
600 Veff AC (Basic isolation)
10 x 106
8 A (10 A UL)
> 500 mA, 12 V AC/DC
16 A characteristic B (B16) at 600 A
16 A characteristic B (B16) at 900 A
6 kV
250 V AC
250 V AC
250 V AC
250 Veff
300 000 switching operations
200 000 switching operations
300 000 switching operations
200 000 switching operations
25 000 switching operations
25 000 switching operations
25 000 switching operations
25 000 switching operations
25 000 switching operations
10 million (107)
10 Hz
2 Hz
0.5 Hz
EASY400-POW
Input voltage
Range
Mains frequency
Range
Output voltage (tolerance)
Output current
Overcurrent limit
Not adversely affected by no-load operation and protected against short-circuit
Terminals
Single-core
Flexible with ferrule
Emitted interference, interference immunity
Potential isolation, primary/secondary
Protection class
Ambient temperature
Storage temperature
115, 230 V AC
85 to 264 V AC
50/60 Hz
47 to 63 Hz
24 V DC (g 3%)
1.25 A
From 1.4 A
Yes
0.2 to 4 mm², AWG 24 to 12
0.2 to 2.5 mm², AWG 24 to 13
EN 50 081-1 Class B; 50 082-2
Yes, SELV
(VDE 0100 T410; IEC 364-4-41)
IP20
–25 to +55°C
–40 to +70 °C
easy Control Relay
easy Control Relay
Technical Data
12
Moeller NK2528-1024GB
easy Control Relay
easy Control Relay
Technical Data
Transistor outputs
Number
Contacts
Rated voltage Ue
Permissible range
Residual ripple
Supply current
0 signal
1 signal
Reverse polarity protection
Potential isolation to inputs, power supply
Rated current Ie for 1 signal
Lamp load
Residual current with 0 signal per channel
Max. output voltage
with 0 signal with external load < 10 MO
with 1 signal, Ie = 0.5 A
Short-circuit protection
Short-circuit tripping current for Ra F 10 mO
Max. total short-circuit current
Peak short-circuit current
Thermal cutout
Maximum operating frequency at constant resistive load
RL < 100 kO : operations per hour
Parallel connection of outputs with resistive load;
inductive load with external suppression circuit,
combination within a group
EASY412-DC-T...
EASY620/621-DC-T...
4
Semiconductors
24 V DC
20.4 to 28.8 V DC
F5 %
8
Semiconductors
24 V DC
20.4 to 28.8 V DC
F5 %
Normally 9 mA, max. 16 mA
Normally 12 mA, max. 22 mA
Yes
Yes
Normally 18 mA, max. 32 mA
Normally 24 mA, max. 44 mA
max. 0.5 A DC
5 watts without RV
< 1.0 mA
2.5 V
U = Ue–1 V
Yes,
(detected via diagnostics input I16, I15; R15; R16)
0.7 A F Ie F 2 A
8A
16 A
16 A
32 A
Yes
Yes
40 000 (depends on circuit diagram and load)
Group 1: Q1 to Q4
Group 1: Q1 to Q4, S1 to S4
Group 2: Q5 to Q8, S5 to S8
Number of outputs
Total maximum current
Status display of the outputs
max. 4
2.0 A
LCD display (if provided)
max. 4
Approvals
currently UL/CSA approved; others in preparation:
EASY412-DC-R
EASY412-DC-RC
EASY412-DC-TC
EASY412-DC-TCX
EASY412-AC-R
EASY412-AC-RC
EASY412-AC-RX
EASY620-DC-TC
EASY618-AC-RC
Notes
For more detailed technical specifications refer to technical data in AWB 2528-1304-GB
LCD display (if provided)
13
Moeller NK2528-1024GB
easy Control Relay
Dimensions
Control Relay
EASY200-EASY
EASY4...
10.75
50
easy Control Relay
7.5
45
110
90
102
M4
4.5
M4
7.5
47.5
35.75
56.5
35.5
71.5
58
EASY618-...
EASY619-...
EASY620-...
EASY621-...
75
16.25
45
110
90
M4
102
16.25
4.5
107.5
47.5
56.5
58