ETC DLD2410

Series DSD, DLD
Time Delay Relay • 10-50 Amp
• DC Control, AC Output
• External Adjustment
• Industry Standard Package
• Zero Voltage Turn-On
• Panel Mount
MODEL NUMBERS
These “on-operate” (pull-in) time-delay
solid state relays are housed in a single
industry standard package. AC output
is controlled by a DC input and has an
externally adjustable time delay.
Choices include models with two timedelay ranges.
Manufactured in Crydom’s ISO 9002
Certified facility for optimum product
performance and reliability.
DSD2410
DSD2425
DSD2450
DLD2410
DLD2425
DLD2450
Operating Voltage Range (47-63 Hz) [Vrms]
48-280
48-280
48-280
48-280
48-280
48-280
Load Current Range ➂ [Arms]
.04-10
.04-25
.04-50
.04-10
.04-25
.04-50
Transient Overvoltage [Vpk]
600
600
600
600
600
600
Max. Surge Current, (16.6ms) [Apk]
120
250
625
120
250
625
Max. On-State Voltage Drop @ Rated Current [Vpk]
1.6
1.6
1.6
1.6
1.6
1.6
OUTPUT SPECIFICATIONS ➀
1.48
1.02
0.63
1.48
1.02
0.63
Maximum I2 t for Fusing, (8.3 msec.) [A2sec]
60
260
1620
60
260
1620
Max. Off-State Leakage Current @ Rated Voltage [mArms]
10
10
10
10
10
10
500
500
500
500
500
500
Thermal Resistance Junction to Case [RθJC]
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]➁
Max. Turn-On Time
➃
Adjustable, See Table
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
Max. Reset Time [µsec] ➄
100
100
100
100
100
100
Power Factor (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
Max. Turn-Off Time
INPUT SPECIFICATIONS ➀
Control Voltage Range
3.5-15Vdc
Max. Turn-On Voltage
3.5 Vdc
Min. Turn-Off Voltage
1.0 Vdc
Min. Input Impedance
1500 Ohms
Typical Input Current
GENERAL NOTES
TYPICAL TURN-ON DELAY ➀
DC CONTROL
3.4mA @ 5 Vdc, 11.4mA @ 15Vdc
RESISTOR
O (Short)
10KΩ
100KΩ
470KΩ
1.0MΩ ➃
TIME (DSD)
TIME (DLD)
0.10 sec
0.19 sec
0.94 sec
4.0 sec
8.3 sec
1.6 sec
3.1 sec
15 sec
64 sec
133 sec
©1998 CRYDOM CORP, Specifications subject to change without notice.
➀ All parameters at 25ºC unless otherwise specified.
➁ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➂ Heat sinking required, for derating curves see page 2.
➃ Timing Resistor may be as high as 10M Ohm with performance dependent on resistor quality.
➄ Before and after time-out.
FastFax Document No. 201
DSD,DLD.032798, PAGE 1 OF 2
For recommended applications and more information contact:
USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280
Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: [email protected]
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191
UK: (44)1202 812300 • fax (44)1202 812340 Crydom International Ltd., 85, Condor Close,
Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU
GERMANY: (49) (0)6874 182580 • fax (49)(0)6874 182585 Crydom GmbH,
Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • e-mail: [email protected]
Series DSD, DLD
Time Delay Relay • 10-50 Amp
GENERAL SPECIFICATIONS
Dielectric Strength, Input section/output/base
4000 Vrms
1010
Insulation Resistance @ 500Vdc
Ambient Operating Temperature Range
-30 to 80ºC
Ambient Storage Temperature Range
-40 to 125ºC
MECHANICAL SPECIFICATIONS
Weight: (typical)
3.0 oz. (43g)
Encapsulation:
Thermally Conductive Epoxy
Terminals:
Screws and Saddle Clamps Furnished, Unmounted
WIRING DIAGRAM
~
1
OUTPUT
1.10
(27.9)
.45
(11.4)
2
2.30
(58.4)
1.70
(43.2)
1.87
(47.5)
TIME DELAY RELAY
4A 4B
8-32 TERMINAL
(2 PLACES )
3A 3B
INPUT
--
Timing
Resistor
.250
(6.35)
1.00
(25.4)
1.80
(45.7)
+
DC CONTROL
.78
(19.8)
.87
(22.2)
FASTON
TERMINAL
.187 X .032
4 PLCS.
All dimensions are in inches (millimeters)
CURRENT DERATING CURVES
25A
3ºC/W
120
2ºC/W
20
15
110
10
NO HEATSINK
5
0
4
6
8
10
20
40
60
80
Max Ambient Temp. [ºC]
1.5ºC/W
40
5
10
15
20
Load Current [Arms]
25
20
40
60
80
Max Ambient Temp. [ºC]
100
2ºC/W
110
20
120
0
Load Current [Arms]
90
1ºC/W .5ºC/W
100
3ºC/W
Power Dissipation
NO HEATSINK
2
60
Base Plate Temp [ºC]
115
25
Power Dissipation
8
4
95
1ºC/W
5ºC/W 110
Base Plate Temp [ºC]
Power Dissipation
7ºC/W
9ºC/W
50A
30
Base Plate Temp [ºC]
10A
12
120
NO HEATSINK
0
10
20
30
40
Load Current [Arms]
50
20
40
60
80
Max Ambient Temp. [ºC]
©1998 CRYDOM CORP, Specifications subject to change without notice.
APPROVALS
UL E116949
FastFax Document No. 201
DSD,DLD.032798, PAGE 2 OF 2
For recommended applications and more information contact:
USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280
Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: [email protected]
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191
UK: (44)1202 812300 • fax (44)1202 812340 Crydom International Ltd., 85, Condor Close,
Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU
GERMANY: (49) (0)6874 182580 • fax (49)(0)6874 182585 Crydom GmbH,
Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • e-mail: [email protected]