19-4717; Rev 0; 7/09 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers The MAX16065/MAX16066 flash-configurable system managers monitor and sequence multiple system voltages. The MAX16065/MAX16066 can also accurately monitor (±2.5%) one current channel using a dedicated high-side current-sense amplifier. The MAX16065 manages up to twelve system voltages simultaneously, and the MAX16066 manages up to eight supply voltages. These devices integrate a selectable differential or single-ended analog-to-digital converter (ADC) and configurable outputs for sequencing power supplies. Device configuration information, including overvoltage and undervoltage limits, timing settings, and the sequencing order is stored in nonvolatile flash memory. During a fault condition, fault flags and channel voltages can be automatically stored in the nonvolatile flash memory for later read-back. The internal 1% accurate 10-bit ADC measures each input and compares the result to one overvoltage, one undervoltage, and one early warning limit that can be configured as either undervoltage or overvoltage. A fault signal asserts when a monitored voltage falls outside the set limits. Up to three independent fault output signals are configurable to assert under various fault conditions. Because the MAX16065/MAX16066 support a powersupply voltage of up to 14V, they can be powered directly from the 12V intermediate bus in many systems. The integrated sequencer provides precise control over the power-up and power-down order of up to twelve (MAX16065) or up to eight (MAX16066) power supplies. Eight outputs (EN_OUT1–EN_OUT8) are configurable with charge-pump outputs to directly drive external n-channel MOSFETs. Features S Operate from 2.8V to 14V S ±2.5% Current-Monitoring Accuracy S 1% Accurate 10-Bit ADC Monitors 12/8 Voltage Inputs S Single-Ended or Differential ADC for System Voltage/Current Monitoring S Integrated High-Side Current-Sense Amplifier S 12/8 Monitored Inputs with Overvoltage/ Undervoltage/Early Warning Limit S Nonvolatile Fault Event Logger S Power-Up and Power-Down Sequencing Capability S Independent Secondary Sequence Block S 12/8 Outputs for Sequencing/Power-Good Indicators S Two Programmable Fault Outputs and One Reset Output S Eight General-Purpose Inputs/Outputs Configurable as: Dedicated Fault Outputs Watchdog Timer Function Manual Reset Margin Enable S SMBus (with Timeout) or JTAG Interface S Flash Configurable Time Delays and Thresholds S -40NC to +85NC Operating Temperature Range Applications The MAX16065/MAX16066 include eight/six programmable general-purpose inputs/outputs (GPIO_s). GPIO_s are flash configurable as dedicated fault outputs, as a watchdog input or output, or as a manual reset. Networking Equipment The MAX16065/MAX16066 feature nonvolatile fault memory for recording information during system shutdown events. The fault logger records a failure in the internal flash and sets a lock bit protecting the stored fault data from accidental erasure. An SMBus™ or a JTAG serial interface configures the MAX16065/MAX16066. The MAX16065 is available in a 48-pin, 7mm x 7mm, TQFN package, and the MAX16066 is available in a 40-pin, 6mm x 6mm, TQFN package. Both devices are fully specified from -40NC to +85NC. Servers SMBus is a trademark of Intel Corp. Telecom Equipment (Base Stations, Access) Storage/Raid Systems Ordering Information TEMP RANGE PIN-PACKAGE MAX16065ETM+ PART -40NC to +85NC 48 TQFN-EP* MAX16066ETL+ -40NC to +85NC 40 TQFN-EP* +Denotes a lead(Pb)-free/RoHS-compliant package. *EP = Exposed pad. Pin Configuration and Typical Operating Circuits appear at end of data sheet. ________________________________________________________________ Maxim Integrated Products 1 For pricing, delivery, and ordering information, please contact Maxim Direct at 1-888-629-4642, or visit Maxim’s website at www.maxim-ic.com. MAX16065/MAX16066 General Description MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers ABSOLUTE MAXIMUM RATINGS VCC, CSP, CSM to GND.........................................-0.3V to +15V CSP to CSM...........................................................-0.7V to +0.7V MON_, GPIO_, SCL, SDA, A0, RESET, EN_OUT9–EN_OUT12 to GND (programmed as open-drain outputs).........-0.3V to +6V EN, TCK, TMS, TDI to GND.....................................-0.3V to +4V DBP, ABP to GND....-0.3V to the lower of +3V and (VCC + 0.3V) EN_OUT1–EN_OUT8 to GND (programmed as open-drain outputs) .............................................................-0.3V to +15V TDO, EN_OUT_, GPIO_, RESET (programmed as push-pull outputs)............................................... -0.3V to (VDBP + 0.3V) Input/Output Current ..........................................................20mA Continuous Power Dissipation (TA = +70NC) 40-Pin TQFN (derate 26.3mW/NC above +70NC)........2105mW 48-Pin TQFN (derate 27.8mW/NC above +70NC)........2222mW Operating Temperature Range........................... -40NC to +85NC Junction Temperature .....................................................+150NC Storage Temperature Range............................. -65NC to +150NC Lead Temperature (soldering, 10s).................................+300NC Stresses beyond those listed under “Absolute Maximum Ratings” may cause permanent damage to the device. These are stress ratings only, and functional operation of the device at these or any other conditions beyond those indicated in the operational sections of the specifications is not implied. Exposure to absolute maximum rating conditions for extended periods may affect device reliability. ELECTRICAL CHARACTERISTICS (VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.) (Note 1) PARAMETER Operating Voltage Range Undervoltage Lockout (Rising) Undervoltage Lockout Hysteresis Minimum Flash Operating Voltage Supply Current SYMBOL VCC VUVLO CONDITIONS MIN Reset output asserted low 1.2 (Note 2) 2.8 ICC MAX 14 Minimum voltage on VCC to ensure the device is flash configurable 2.7 VUVLO_HYS Vflash TYP UNITS V V 100 mV Minimum voltage on VCC to ensure flash erase and write operations 2.7 V No load on output pins 4.5 7 During flash writing cycle 10 14 mA ABP Regulator Voltage VABP CABP = 1μF, no load, VCC = 5V 2.85 3 3.15 DBP Regulator Voltage VDBP CABP = 1μF, no load, VCC = 5V 2.8 3 3.1 V Boot Time tBOOT VCC > VUVLO 200 350 μs 8-byte word 122 Flash Writing Time Internal Timing Accuracy EN Input Voltage EN Input Current Input Voltage Range (Note 3) VTH_EN_R EN voltage rising VTH_EN_F EN voltage falling IEN -8 ms +8 1.41 1.365 1.39 V 1.415 % V -0.5 +0.5 μA 0 5.5 V 2 _______________________________________________________________________________________ 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers (VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.) (Note 1) PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS Bits LSB ADC DC ACCURACY Resolution Gain Error ADCGAIN Offset Error ADCOFF 10 0.35 0.70 1 Integral Nonlinearity ADCINL 1 LSB Differential Nonlinearity ADCDNL 1 LSB 50 μs ADC Total Monitoring Cycle Time tCYCLE ADC IN_ Ranges TA = +25°C TA = -40°C to +85°C No MON_ fault detected 40 1 LSB = 5.43mV 5.56 1 LSB = 2.72mV 2.78 1 LSB = 1.36mV 1.39 % V CURRENT SENSE CSP Input-Voltage Range VCSP 3 ICSP Input Bias Current ICSM CSP Total Unadjusted Error Overcurrent Differential Threshold VSENSE Fault Threshold Hysteresis CSPERR OVCTH VCSP = VCSM VSENSE Ranges VCSP VCSM 46 51 56 Gain = 12 94 101 108 Gain = 6 190 202 210 0.5 CMRRSNS PSRRSNS μA %FSR mV 0 3 4 5 r73h[6:5] = ‘10’ 12 16 20 r73h[6:5] = ‘11’ 50 64 60 Gain = 6 232 Gain = 12 116 Gain = 24 58 ms mV 29 -2.5 Q0.2 +2.5 -4 Q0.2 +4 VSENSE = 25mV, gain = 24 Q0.5 VSENSE = 10mV, gain = 48 Q1 VCSP > 4V V % OVCTH r73h[6:5] = ‘01’ VSENSE = 20mV to 100mV, VCSP = 5V, gain = 6 Power-Supply Rejection Ratio 30.5 Gain = 24 VSENSE = 50mV, gain = 12 Common-Mode Rejection Ratio 25 2 VSENSE = 150mV (gain = 6 only) Gain Accuracy 5 21.5 Gain = 48 ADC Current Measurement Accuracy 3 Gain = 48 OVCHYS OVCDEL 25 (Note 4) r73h[6:5] = ‘00’ Secondary Overcurrent Threshold Timeout 14 14 -1.5 +1.5 % % 80 dB 80 dB _______________________________________________________________________________________ 3 MAX16065/MAX16066 ELECTRICAL CHARACTERISTICS (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers ELECTRICAL CHARACTERISTICS (continued) (VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.) (Note 1) PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS OUTPUTS (EN_OUT_, RESET, GPIO_) ISINK = 2mA 0.4 ISINK = 10mA, GPIO_ only 0.7 VCC = 1.2V, ISINK = 100μA (RESET only) 0.3 Maximum Output Sink Current Total current into EN_OUT_, RESET, GPIO_, VCC = 3.3V 30 Output-Voltage High (Push-Pull) ISOURCE = 100μA Output-Voltage Low VOL EN_OUT1–EN_OUT8 = 13.2V OUT_ Overdrive (Charge Pump) (EN_OUT1–EN_OUT8 Only) ICH_UP mA V 1 Output Leakage (Open Drain) OUT_ Pullup Current (Charge Pump) 2.4 V 5 IGATE_ = 1μA 10 11 During power up, VGATE = 1V 2.5 4 13 μA V μA SMBus INTERFACE Logic-Input Low Voltage VIL Input voltage falling Logic-Input High Voltage VIH Input voltage rising 2.0 IN = GND or VCC -1 Input Leakage Current Output Sink Current Input Capacitance SMBus Timeout VOL V +1 μA 0.4 V 35 ms 0.8 V V ISINK = 3mA CIN tTIMEOUT 0.8 5 SCL time low for reset 25 pF INPUTS (A0, GPIO_) Input Logic-Low VIL Input Logic-High VIH 2.0 V WDI Pulse Width tWDI 100 ns MR Pulse Width tMR 1 μs MR to RESET Delay 0.5 μs MR Glitch Rejection SMBus TIMING 100 ns Serial Clock Frequency fSCL Bus Free Time Between STOP and START Condition tBUF 1.3 μs START Condition Setup Time tSU:STA 0.6 μs START Condition Hold Time tHD:STA 0.6 μs STOP Condition Setup Time tSU:STO 0.6 μs Clock Low Period tLOW 1.3 μs Clock High Period tHIGH 0.6 μs tSU:DAT 100 ns Data Setup Time 400 4 _______________________________________________________________________________________ kHz 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers (VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.) (Note 1) PARAMETER SYMBOL Output Fall Time tOF Data Hold Time tHD:DAT Pulse Width of Spike Suppressed CONDITIONS MIN TYP CBUS = 10pF to 400pF From 50% SCL falling to SDA change 0.3 tSP MAX UNITS 250 ns 0.9 μs 30 ns JTAG INTERFACE TDI, TMS, TCK Logic-Low Input Voltage VIL Input voltage falling TDI, TMS, TCK Logic-High Input Voltage VIH Input voltage rising TDO Logic-Output Low Voltage VOL ISINK = 3mA TDO Logic-Output High Voltage VOH ISOURCE = 200μA 2.4 TDI, TMS Pullup Resistors RPU Pullup to DBP 40 I/O Capacitance CI/O TCK Clock Period 0.8 2 V 0.4 V 60 kω V 50 5 t1 TCK High/Low Time V pF 1000 500 ns t2, t3 50 TCK to TMS, TDI Setup Time t4 15 ns TCK to TMS, TDI Hold Time t5 10 TCK to TDO Delay t6 500 ns TCK to TDO High-Z Delay t7 500 ns ns ns Note 1: Specifications are guaranteed for the stated global conditions, unless otherwise noted. 100% production tested at TA = +25NC and TA = +85NC. Specifications at TA = -40NC are guaranteed by design. Note 2: For VCC of 3.6V or lower, connect VCC, DBP, and ABP together. For higher supply applications, connect only VCC to the supply rail. Note 3: Applies to RESET, fault, autoretry, sequence delays, and watchdog timeout. Note 4: Total unadjusted error is a combination of gain, offset, and quantization error. _______________________________________________________________________________________ 5 MAX16065/MAX16066 ELECTRICAL CHARACTERISTICS MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers SDA tSU:DAT tHD:DAT tLOW tBUF tSU:STA tHD:STA tSU:STO SCL tHIGH tHD:STA tR tF START CONDITION STOP CONDITION REPEATED START CONDITION Figure 1. SMBus Timing Diagram t1 t2 t3 TCK t4 t5 TDI, TMS t6 t7 TDO Figure 2. JTAG Timing Diagram 6 _______________________________________________________________________________________ START CONDITION 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers VCC SUPPLY CURRENT vs. VCC SUPPLY VOLTAGE TA = -40NC ABP AND DBP REGULATORS ACTIVE 2 FOR LOW-VOLTAGE APPLICATIONS VCC < 3.6V CONNECT ABP AND DBP TO VCC 1 0 2 4 6 8 10 0.6 0.4 0.2 MAX16065 toc03 1.002 1.000 0.998 0.996 0.994 0.992 -40 14 -20 0 20 40 60 80 -40 -20 0 20 40 60 VCC (V) TEMPERATURE (NC) TEMPERATURE (NC) TRANSIENT DURATION vs. THRESHOLD OVERDRIVE (EN) NORMALIZED TIMING ACCURACY vs. TEMPERATURE MON_ DEGLITCH vs. TRANSIENT DURATION 120 100 80 60 40 0.984 0.982 0.980 0.978 0.976 120 100 0 10 1 100 80 60 40 20 0.974 20 80 MAX16065 toc06 0.986 TRANSIENT DURATION (µs) MAX16065 toc04 140 0 0.972 -40 -20 0 20 40 60 2 80 4 8 16 EN OVERDRIVE (mV) TEMPERATURE (NC) DEGLITCH VALUE MR TO RESET PROPAGATION DELAY vs. TEMPERATURE OUTPUT VOLTAGE vs. SINK CURRENT (OUT = LOW) OUTPUT-VOLTAGE HIGH vs. SOURCE CURRENT (CHARGE-PUMP OUTPUT) EN_OUT_ 0.35 1.4 12 10 0.30 1.0 MIN 0.8 8 0.25 VOUT (V) VOUT (V) 1.2 GPIO_ RESET 0.20 0.15 0.6 0.4 0.10 0.2 0.05 -40 -20 0 20 40 TEMPERATURE (NC) 60 80 6 4 2 0 0 MAX16065 toc09 MAX 0.40 MAX16065 toc08 1.8 1.6 0.45 MAX16065 toc07 2.0 DELAY (µs) 5.6V RANGE, HALF SCALE, PUV THRESHOLD 1.004 0 12 160 TRANSIENT DURATION (µs) 0.8 MAX16065 toc05 0 1.0 1.006 NORMALIZED EN THRESHOLD TA = +25NC 3 NORMALIZED SLOT DELAY ICC (mA) 4 1.2 MAX16065 toc02 5 TA = +85NC NORMALIZED MON_ THRESHOLD ABP AND DBP CONNECTED TO VCC MAX16065 toc01 6 NORMALIZED EN THRESHOLD vs. TEMPERATURE NORMALIZED MON_ THRESHOLD vs. TEMPERATURE 0 5 10 IOUT (mA) 15 20 0 0 1 2 3 4 IOUT (µA) _______________________________________________________________________________________ 7 MAX16065/MAX16066 Typical Operating Characteristics (Typical values are at VCC = 3.3V, TA = +25°C, unless otherwise noted.) Typical Operating Characteristics (continued) (Typical values are at VCC = 3.3V, TA = +25°C, unless otherwise noted.) 0.8 0.6 0.8 0.6 0.4 3.0 0.2 0.2 GPIO_ EN_OUT_ 2.7 2.6 2.5 RESET 2.4 500 0 1000 -0.2 -0.4 -0.4 -0.6 -0.6 -0.8 -0.8 -1.0 -1.0 0 1500 128 256 384 512 640 768 896 1024 IOUT (µA) 0 CURRENT-SENSE TRANSIENT DURATION vs. CSP-CSM OVERDRIVE MAX16065 toc14 1.0 MAX16065 toc13 1.03 200mV CODE (LSB) CURRENT-SENSE ACCURACY vs. CSP-CSM VOLTAGE 1.05 0.8 0.6 0.4 ERROR (mV) 25mV 1.01 0.99 100mV 0.2 0 -0.2 -0.4 0.97 0.95 1.8 1.6 0 20 40 60 80 1.4 1.2 1.0 0.8 0.6 -0.6 0.4 -0.8 0.2 -1.0 -20 128 256 384 512 640 768 896 1024 CODE (LSB) NORMALIZED CURRENT-SENSE ACCURACY vs. TEMPERATURE -40 0 -0.2 MAX16065 toc15 2.8 0 TRANSIENT DURATION (Fs) 2.9 DNL (LSB) 0.4 INL (LSB) 3.1 0 0 5 10 15 20 25 30 0 20 40 60 CSP-CSM VOLTAGE (mV) CSP-CSM OVERDRIVE (mV) FET TURN-ON WITH CHARGE PUMP SEQUENCING MODE RESET OUTPUT CURRENT vs. SUPPLY VOLTAGE MAX16065 toc17 MAX16065 toc16 18 ABP AND DBP CONNECTED TO VCC 16 OUTPUT CURRENT (mA) EN_OUT ILOAD 100 80 TEMPERATURE (NC) MAX16065 toc18 3.2 DIFFERENTIAL NONLINEARITY vs. CODE 1.0 MAX16065 toc11 3.3 VOUT (V) INTEGRAL NONLINEARITY vs. CODE 1.0 MAX16065 toc10 3.4 MAX16065 toc12 OUTPUT-VOLTAGE HIGH vs. SOURCE CURRENT (PUSH-PULL OUTPUT) NORMALIZED CURRENT-SENSE OUTPUT MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers 14 12 ABP AND DBP REGULATORS ACTIVE 10 8 6 4 VLOAD 2 VRESET = 0.3V 0 20ms/div 20ms/div 0 2 4 6 8 10 SUPPLY VOLTAGE (V) 8 _______________________________________________________________________________________ 12 14 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers PIN NAME FUNCTION MAX16065 MAX16066 1–6, 43–46 1–5, 36–40 MON1– MON10 Monitor Voltage Inputs. Set monitor voltage range through configuration registers. Measured value written to ADC register can be read back through the SMBus or JTAG interface. 47, 48 — MON11, MON12 Monitor Voltage Inputs. Set monitor voltage range through configuration registers. Measured value written to ADC register can be read back through the SMBus or JTAG interface. 7 6 CSP Current-Sense Amplifier Positive Input. Connect CSP to the source side of the external sense resistor. 8 7 CSM Current-Sense Amplifier Negative Input. Connect CSM to the load side of the external sense resistor. 9 8 RESET 10 9 TMS Configurable Reset Output JTAG Test Mode Select 11 10 TDI JTAG Test Data Input 12 11 TCK JTAG Test Clock 13 12 TDO JTAG Test Data Output 14 13 SDA SMBus Serial-Data Open-Drain Input/Output 15 14 A0 16 15 SCL SMBus Serial-Clock Input 17, 42 16, 35 GND Ground 20–25 17–22 GPIO1– GPIO6 General-Purpose Input/Outputs. GPIO_s can be configured to act as a TTL input, a push-pull, open-drain, or high-impedance output or a pulldown circuit during a fault event. 18, 19 — GPIO7, GPIO8 General-Purpose Input/Outputs. GPIO_s can be configured to act as a TTL input, a push-pull, open-drain, or high-impedance output or a pulldown circuit during a fault event or reverse sequencing. 26–29 — EN_OUT12– EN_OUT9 Outputs. Set EN_OUT_ with active-high/active-low logic and with push-pull or open-drain configuration. EN_OUT_ can be asserted by a combination of IN_ voltages configurable through the flash. Outputs. Set EN_OUT_ with active-high/active-low logic and with push-pull or open-drain configuration. EN_OUT_ can be asserted by a combination of IN_ voltages configurable through the flash. EN_OUT1–EN_OUT8 can be configured with a charge-pump output (+10V above GND) that can drive an external n-channel MOSFET. Four-State SMBus Address. Address sampled upon POR. 30–37 23–30 EN_OUT1– EN_OUT8 38 31 EN 39 32 DBP Digital Bypass. All push-pull outputs are referenced to DBP. Bypass DBP with a 1FF capacitor to GND. 40 33 VCC Device Power Supply. Connect VCC to a voltage from 2.8V to 14V. Bypass VCC with a 10FF capacitor to GND. 41 34 ABP Analog Bypass. Bypass ABP with a 1FF ceramic capacitor to GND. — — EP Analog Enable Input. All outputs deassert when VEN is below the enable threshold. Exposed Pad. Internally connected to GND. Connect to ground, but do not use as the main ground connection. _______________________________________________________________________________________ 9 MAX16065/MAX16066 Pin Description MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Functional Diagram ABP VCC DBP OVERC RESET MAX16065 RESET ANYFAULT FAULT1 DECODE LOGIC FAULT2 MR C O N T R O L MARGIN WATCHDOG TIMER EN WDI WDO GPIO1–GPIO8 PRIMARY SEQUENCE BLOCK 1.4V AV REF MON1– MON12 VOLTAGE SCALING AND MUX 10-BIT ADC (SAR) ADC REGISTERS DIGITAL COMPARATORS RAM REGISTERS SMBus INTERFACE AO SCL SDA FLASH MEMORY GND JTAG INTERFACE TDO TDI GPIO2 GPIO3 GPIO4 GPIO5 GPIO6 GPIO7 EN_OUT1– EN_OUT12 SECONDARY SEQUENCE BLOCK VCSTH GPIO1 GPIO8 CSP CSM G P I O TCK TMS 10 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers The MAX16065 manages up to twelve system power supplies and the MAX16066 can manage up to eight system power supplies. After boot-up, if EN is high and the software enable bit is set to ‘1,’ a power-up sequence begins based on the configuration stored in flash and the EN_OUT_s are controlled accordingly. When the power-up sequence is successfully completed, the monitoring phase begins. An internal multiplexer cycles through each MON_ input. At each multiplexer stop, the 10-bit ADC converts the monitored analog voltage to a digital result and stores the result in a register. Each time a conversion cycle (50Fs, max) completes, internal logic circuitry compares the conversion results to the overvoltage and undervoltage thresholds stored in memory. When a result violates a programmed threshold, the conversion can be configured to generate a fault. GPIO_ can be programmed to assert on combinations of faults. Additionally, faults can be configured to shut off the system and trigger the nonvolatile fault logger, which writes all fault information automatically to the flash and writeprotects the data to prevent accidental erasure. The MAX16065/MAX16066 contain both SMBus and JTAG serial interfaces for accessing registers and flash. Use only one interface at any given time. For more information on how to access the internal memory through these interfaces, see the SMBus-Compatible Interface and JTAG Serial Interface sections. The memory map is divided into three pages with access controlled by special SMBus and JTAG commands. The factory-default values at POR (power-on reset) for all RAM registers are ‘0’s. POR occurs when VCC reaches the undervoltage-lockout threshold (UVLO) of 2.8V (max). At POR, the device begins a boot-up sequence. During the boot-up sequence, all monitored inputs are masked from initiating faults and flash contents are copied to the respective register locations. During boot-up, the MAX16065/MAX16066 are not accessible through the serial interface. The boot-up sequence takes up to 150Fs, after which the device is ready for normal operation. RESET is asserted low up to the boot-up phase and remains asserted for its programmed timeout period once sequencing is completed and all monitored channels are within their respective thresholds. Up to the boot-up phase, the GPIO_s and EN_OUT_s are high impedance. Power Apply 2.8V to 14V to VCC to power the MAX16065/ MAX16066. Bypass VCC to ground with a 10FF capacitor. Two internal voltage regulators, ABP and DBP, supply power to the analog and digital circuitry within the device. For operation at 3.6V or lower, disable the regulators by connecting ABP and DBP to VCC. ABP is a 3.0V (typ) voltage regulator that powers the internal analog circuitry. Bypass ABP to GND with a 1FF ceramic capacitor installed as close to the device as possible. DBP is an internal 3.0V (typ) voltage regulator. DBP powers flash and digital circuitry. All push-pull outputs refer to DBP. DBP supplies the input voltage to the internal charge pump when the programmable outputs are configured as charge-pump outputs. Bypass the DBP output to GND with a 1FF ceramic capacitor installed as close as possible to the device. Do not power external circuitry from ABP or DBP. Sequencing To sequence a system of power supplies safely, the output voltage of a power supply must be good before the next power supply may turn on. Connect EN_OUT_ outputs to the enable input of an external power supply and connect MON_ inputs to the output of the power supply for voltage monitoring. More than one MON_ can be used if the power supply has multiple outputs. Sequence Order The MAX16065/MAX16066 provide a system of ordered slots to sequence multiple power supplies. To determine the sequence order, assign each EN_OUT_ to a slot ranging from Slot 1 to Slot 12. EN_OUT_(s) assigned to Slot 1 are turned on first, followed by outputs assigned to Slot 2, and so on through Slot 12. Multiple EN_OUT_s assigned to the same slot turn on at the same time. Each slot includes a built-in configurable sequence delay (registers r77h to r7Dh) ranging from 20Fs to 1.6s. During a reverse sequence, slots are turned off in reverse order starting from Slot 12. The MAX16065/MAX16066 can be configured to power-down in simultaneous mode or in reverse sequence mode as set in r75h[0]. See Tables 5 and 6 for the EN_OUT_ slot assignment bits, and Tables 3 and 4 for the sequence delays. During power-up or power-down sequencing, the current sequencer state can be found in r21h[4:0]. ______________________________________________________________________________________ 11 MAX16065/MAX16066 Detailed Description MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 1. Current Sequencer Slot REGISTER ADDRESS 21h BIT RANGE DESCRIPTION [4:0] Current Sequencer State: 00000 = Slot 0 00001 = Slot 1 00010 = Slot 2 00011 = Slot 3 00100 = Slot 4 00101 = Slot 5 00110 = Slot 6 00111 = Slot 7 01000 = Slot 8 01001 = Slot 9 01010 = Slot 10 01011 = Slot 11 01100 = Slot 12 01101 = Secondary sequence monitoring mode 01110 = Primary sequence fault 01111 = Primary sequence monitoring mode 10000 = Secondary sequence fault 10001 to 11111 = Reserved [7:5] Reserved Multiple Sequencing Groups The MAX16065/MAX16066 sequencing slots can be split into two groups: the primary sequence and the secondary sequence. The last slot of the primary sequence is selected using register bits r7Dh[7:4]. The secondary sequence begins at the slot after the one specified in register bits 7Dh[7:4]. The primary sequence is controlled by the EN input and the software enable bit in r73h[0]. Outputs assigned to slots in the primary sequence turn on, and monitoring begins for inputs assigned to these slots. RESET deasserts after the primary sequence and timeout period completes. To initiate secondary sequencing and monitoring, set the software enable 73h[1] bit to 1. Additionally, if GPIO_ is configured as EN2 then both the software enable 2 and EN2 must be high. Outputs assigned to slots in the secondary sequence turn on, and monitoring begins for inputs assigned to these slots. If a GPIO_ is configured as the RESET2 output, it deasserts after the secondary sequence and timeout period completes. If a critical fault occurs in the primary sequence group, both sequence groups automatically shut down. If a critical fault occurs in the secondary sequence group, then just the outputs assigned to slots in the secondary sequence turn off. The failing slot in secondary sequence is stored in r1Dh. Multiple sequencing groups can be used to conserve power by powering down secondary systems when not in use. Enable and Enable2 To initiate sequencing/tracking and enable monitoring, the voltage at EN must be above 1.4V and the software enable bit in r73h[0] must be set to ‘1.’ To power down and disable monitoring, either pull EN below 1.35V or set the Software Enable bit to ‘0.’ See Table 2 for the software enable bit configurations. Connect EN to ABP if not used. If a fault condition occurs during the power-up cycle, the EN_OUT_ outputs are powered down immediately, regardless of the state of EN. In the monitoring state, if EN falls below the threshold, the sequencing state machine begins the power-down sequence. If EN rises above the threshold during the power-down sequence, the sequence state machine continues the power-down sequence until all the channels are powered off and then the device immediately begins the power-up sequence. When in the monitoring state, a register bit, ENRESET, is set to a ‘1’ when EN falls below the undervoltage threshold. This register bit latches and must be cleared through software. This bit indicates if RESET asserted low due to EN going under the threshold. The POR state of ENRESET is ‘0’. The bit is only set on a falling edge 12 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers To initiate secondary sequencing and monitoring set the software enable r73h[1] bit to 1. Additionally, if GPIO_ is configured as EN2 then both the software enable 2 bit and EN2 must be high. To power-down and disable monitoring, either drive EN2 low or set the Software Enable2 bit to ‘0.’ See Table 2 for the software enable bit configurations. When a fault condition occurs during the power-up cycle, the EN_OUT_ outputs are powered down immediately, independent of the state of EN2. Drive EN2 low to begin the secondary power-down sequence. When EN2 is driv- en high during the power-down sequence, the sequence state machine continues the power-down sequence until the secondary channels are powered off and then the device immediately begins the power-up sequence. Monitoring Inputs While Sequencing An enabled MON_ input can be assigned to a slot ranging from Slot 1 to Slot 12. EN_OUT_s are always asserted at the beginning of a slot. The supply voltages connected to the MON_ inputs must exceed the undervoltage threshold before the programmed timeout period expires otherwise a fault condition will occur. The undervoltage threshold checking cannot be disabled during power-up and power-down. See Tables 5 and 6 for the MON_ slot assignment bits. The programmed Table 2. Software Enable Configurations REGISTER ADDRESS 73h FLASH ADDRESS BIT RANGE 273h DESCRIPTION [0] Software enable 1 (primary sequence) [1] Software enable 2 (secondary sequence) [2] 1 = Margin mode enabled [3] Early warning threshold select 0 = Early warning is undervoltage 1 = Early warning is overvoltage [4] Independent watchdog mode enable 1 = Watchdog timer is independent of sequencer 0 = Watchdog timer boots after sequence completes Table 3. Slot Delay Register REGISTER ADDRESS FLASH ADDRESS 77h 277h 78h 79h 7Ah 7Bh 7Ch 7Dh 278h 279h 27Ah 27Bh 27Ch 27Dh BIT RANGE DESCRIPTION [3:0] Sequence Slot 0 Delay [7:4] Sequence Slot 1 Delay [3:0] Sequence Slot 2 Delay [7:4] Sequence Slot 3 Delay [3:0] Sequence Slot 4 Delay [7:4] Sequence Slot 5 Delay [3:0] Sequence Slot 6 Delay [7:4] Sequence Slot 7 Delay [3:0] Sequence Slot 8 Delay [7:4] Sequence Slot 9 Delay [3:0] Sequence Slot 10 Delay [7:4] Sequence Slot 11 Delay [3:0] Sequence Slot 12 Delay [7:4] Grouped Sequence Split Location, Final Slot of Primary Sequence ______________________________________________________________________________________ 13 MAX16065/MAX16066 of the EN comparator output or the software enable bit. If operating in latch-on fault mode, toggle EN or toggle the Software Enable bit to clear the latch condition and restart the device once the fault condition has been removed. MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 4. Power-Up/Power-Down Slot Delays CODE VALUE 0000 0001 0010 0011 0100 0101 0110 0111 1000 1001 25Fs 500Fs 1ms 2ms 3ms 4ms 6ms 8ms 10ms 12ms 1010 1011 25ms 100ms 1100 1101 200ms 400ms 1110 1111 800ms 1.6s sequence delay is then counted before moving to the next slot. Slot 0 does not monitor any MON_ input and does not control any EN_OUT_. Slot 0 waits for the Software Enable bit r73h[0] to be a logic-high and for the voltage on EN to rise above 1.4V before initiating the power-up sequence and counting its own sequence delay. Any MON_ input that suffers a fault that occurs during power-up sequencing causes all the EN_OUT_s to turn off and the sequencer to shut down regardless of the state of the critical fault enables (see the Faults section for more information). If a MON_ input is less critical to system operation, it can be configured as “monitoring only” (see Table 6) for either the primary or secondary sequence. Monitoring for MON_ inputs assigned as “monitoring only” begins after sequencing is complete for that group, and can trigger a critical fault only if specifically configured to do so using the critical fault enables. Power-Up On power-up, when EN is high and the Software Enable bit is 1, the MAX16065/MAX16066 begin sequencing with Slot 0. After the sequencing delay for Slot 0 expires, the sequencer advances to Slot 1, and all EN_OUT_s assigned to the slot assert. All MON_ inputs assigned to Slot 1 are monitored and when the voltage rises above the UV fault threshold, the sequence delay counter is started. When the tFAULT counter expires before all MON_ inputs assigned to the slot are above the fault UV threshold, a fault asserts. EN_OUT_ outputs are disabled and the MAX16065/MAX16066 return to the power-off state. When the sequence delay expires, the MAX16065/ MAX16066 proceed to the next slot. After the voltages on all MON_ inputs assigned to the last slot exceed the UV fault threshold and the slot delay expires, the MAX16065/MAX16066 start the reset timeout counter. After the reset timeout, RESET deasserts. r75h[4:1] sets the tFAULT delay. See Table 7 for details. Power-Down Power-down starts when EN is pulled low or the Software Enable bit is set to ‘0.’ Power down EN_OUT_s simultaneously or in reverse-sequence mode by setting the Reverse Sequence bit (r75h[0]) appropriately. Reverse-Sequence Mode When the MAX16065/MAX16066 are fully powered up (including secondary sequence group, if enabled) and EN or the Software Enable bit is set to ‘0’, the EN_OUT_s assigned to Slot 12 deassert, the MAX16065/MAX16066 wait for the Slot 12 sequence delay and then proceed to the previous slot (Slot 11), and so on until the EN_OUT_s assigned to Slot 1 turn off. When simultaneous powerdown is selected (r75h[0] set to ‘0’), all EN_OUT_s turn off at the same time. 14 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers SLOT 1 SLOT 2 (PRIMARY SEQUENCE) tFAULT SLOT1-SLOT2 DELAY EN_OUT1 FINAL SLOT SLOT1-SLOT2 DELAY OV BOTH ARE ASSIGNED TO SLOT 1 MON4 UV EN_OUT2 UV/OV MONITORING BEGINS WHEN MON4 REACHES UV THRESHOLD MON4 MUST REACH UV THRESHOLD BY THIS TIME BOTH ARE ASSIGNED TO SLOT 2 RESET TIMEOUT MON3 MON5 RESET EN Figure 3. Delay and Reset Timing Table 5. MON_ and EN_OUT_ Assignment Registers REGISTER ADDRESS FLASH ADDRESS 7Eh 27Eh 7Fh 27Fh 80h 280h 81h 281h 82h 282h 83h 283h BIT RANGE DESCRIPTION [3:0] MON1 [7:4] MON2 [3:0] MON3 [7:4] MON4 [3:0] MON5 [7:4] MON6 [3:0] MON7 [7:4] MON8 [3:0] MON9 [7:4] MON10 [3:0] MON11 [7:4] MON12 ______________________________________________________________________________________ 15 MAX16065/MAX16066 SLOT 0 MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 5. MON_ and EN_OUT_ Assignment Registers (continued) REGISTER ADDRESS FLASH ADDRESS 84h 284h 85h 86h 87h 88h 89h 285h 286h 287h 288h 289h BIT RANGE DESCRIPTION [3:0] EN_OUT1 [7:4] EN_OUT2 [3:0] EN_OUT3 [7:4] EN_OUT4 [3:0] EN_OUT5 [7:4] EN_OUT6 [3:0] EN_OUT7 [7:4] EN_OUT8 [3:0] EN_OUT9 [7:4] EN_OUT10 [3:0] EN_OUT11 [7:4] EN_OUT12 Table 6. MON_ and EN_OUT_ Slot Assignment Codes SLOT ASSIGNMENT CODE MON_ DESCRIPTION OUT_ DESCRIPTION 0000 0001 Not assigned Slot 1 Not assigned Slot 1 0010 0011 Slot 2 Slot 3 Slot 2 Slot 3 0100 0101 Slot 4 Slot 5 Slot 4 Slot 5 0110 0111 Slot 6 Slot 7 1000 1001 1010 1011 1100 1101 1110 1111 Slot 8 Slot 9 Slot 10 Slot 11 Slot 12 Monitoring only, primary sequence Monitoring only, secondary sequence Not assigned Slot 6 Slot 7 Slot 8 Slot 9 Slot 10 Slot 11 Slot 12 General-purpose input (EN_OUT9–EN_OUT12 only) General-purpose output (EN_OUT9–EN_OUT12 only) Not assigned 16 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers CODE DELAY 0000 0001 0010 0011 0100 0101 0110 0111 1000 120Fs 150Fs 1001 6ms 1010 1011 1100 1101 1110 1111 10ms 15ms 25ms 40ms 60ms 100ms When the secondary sequence group is already powered down and EN or the Software Enable bit is set to ‘0’, the reverse power-down sequence is similar to above, but starts from the last slot assigned to the primary sequence r7Dh[7:4]. After the last assigned slot is powered down the previous slot will power down and so on until Slot 0 is powered down. To power down the secondary sequence group, drive EN2 low or set r75h[1] to ‘0’. The secondary reverse power-down sequence will start at Slot 12 and end at the primary sequence monitoring mode state at which point only the slots assigned to the primary sequence are active. Voltage/Current Monitoring The MAX16065/MAX16066 feature an internal 10-bit ADC that monitors the MON_ voltage inputs. An internal multiplexer cycles through each of the enabled inputs, taking less than 40Fs for a complete monitoring cycle. Each acquisition takes approximately 3.2Fs. At each multiplexer stop, the 10-bit ADC converts the analog input to a digital result and stores the result in a register. ADC conversion results are stored in registers r00h to r1Ah (see Table 10). Use the SMBus or JTAG serial interface to read ADC conversion results. The MAX16065 provides twelve inputs, MON1–MON12, for voltage monitoring. The MAX16066 provides eight inputs, MON1–MON8, for voltage monitoring. Each input 250Fs 380Fs 600Fs 1ms 1.5ms 2.5ms 4ms voltage range is programmable in registers r43h to r45h (see Table 9). When MON_ configuration registers are set to ’11,’ MON_ voltages are not monitored, and the multiplexer does not stop at these inputs, decreasing the total cycle time. These inputs cannot be configured to trigger fault conditions. The three programmable thresholds for each monitored voltage include an overvoltage, an undervoltage, and a secondary warning threshold that can be set in r73h[3] to be either an undervoltage or overvoltage threshold. See the Faults section for more information on setting overvoltage and undervoltage thresholds. All voltage thresholds are 8 bits wide. The 8 MSBs of the 10-bit ADC conversion result are compared to these overvoltage and undervoltage thresholds. For any undervoltage or overvoltage condition to be monitored and any faults detected, the MON_ input must be assigned to a sequence order or set to monitoring mode as described in the Sequencing section. Inputs that are not enabled are not converted by the ADC; they contain the last value acquired before that channel was disabled. The ADC conversion result registers are reset to 00h at boot-up. These registers are not reset when a reboot command is executed. Configure the MAX16065/MAX16066 for differential mode in r46h (Table 9). The possible differential pairs ______________________________________________________________________________________ 17 MAX16065/MAX16066 Table 7. tFAULT Delay Settings MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers are MON1/MON2, MON3/MON4, MON5/MON6, MON7/ MON8, MON9/MON10, MON11/MON12 with the first input always being at a higher voltage than the second. Use differential voltage sensing to eliminate voltage offsets or measure supply current. See Figure 4. In differential mode, the odd-numbered MON_ input measures the absolute voltage with respect to GND while the result of the even input is the difference between the odd and even inputs. See Figure 4 for the typical differential measurement circuit. In addition, there are two programmable current-sense trip thresholds: primary overcurrent and secondary overcurrent. For fast fault detection, the primary overcurrent threshold is implemented with an analog comparator connected to the internal OVERC signal. The OVERC signal can be output on one of the GPIO_s. See the General-Purpose Inputs/Outputs section for configuring the GPIO_ to output the OVERC signal. The primary threshold is set by: Internal Current-Sense Amplifier where ITH is the current threshold to be set, VCSTH is the threshold set by r47h[3:2], and RSENSE is the value of the sense resistor. See Table 8 for a description of r47h. OVERC depends only on the primary overcurrent threshold. The secondary overcurrent threshold is implemented through ADC conversions and digital comparison set by r6Ch. The secondary overcurrent threshold includes programmable time delay options located in r73h[6:5]. Primary and secondary current-sense faults are enabled/ disabled through r47h[0]. The current-sense inputs, CSP/CSM, and a currentsense amplifier facilitate power monitoring (see Figure 5). The voltage on CSP relative to GND is also monitored by the ADC when the current-sense amplifier is enabled with r47h[0]. The conversion results are located in registers r19h and r1Ah (see Table 10). There are two selectable voltage ranges for CSP set by r47h[1], see Table 8. Although the voltage can be monitored over SMBus or JTAG, this voltage has no threshold comparators and cannot trigger any faults. Regarding the current-sense amplifier, there are four selectable ranges and the ADC output for a current-sense conversion is: XADC = (VSENSE x AV)/1.4V x (28 - 1) where XADC is the 8-bit decimal ADC result in register r18h, VSENSE is VCSP - VCSM, and AV is the currentsense voltage gain set by r47h[3:2]. RS POWER SUPPLY ITH = VCSTH/RSENSE General-Purpose Inputs/Outputs GPIO1–GPIO8 are programmable general-purpose inputs/outputs. GPIO1–GPIO8 are configurable as a manual reset input, a watchdog timer input and output, logic inputs/outputs, fault-dependent outputs. When programmed as outputs, GPIO_s are open drain or pushpull. See Tables 12 and 13 for more detailed information on configuring GPIO1–GPIO8. ILOAD VMON CS+ MONEVEN MONODD RSENSE - CS- TO ADC MUX *AV + MAX16065 MAX16066 MAX16065 LOAD MONODD MONEVEN OVERC + + - POWER SUPPLY *VCSTH LOAD *ADJUSTABLE BY r47h[1:0] Figure 4. Differential Measurement Connections Figure 5. Current-Sense Amplifier 18 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS 47h FLASH ADDRESS BIT RANGE [0] 1 = Current sense is enabled 0 = Current sense is disabled [1] 1 = CSP full-scale range is 14V 0 = CSP full-scale range is 7V 247h 73h 273h DESCRIPTION [3:2] Overcurrent Primary Threshold and Current-Sense Gain Setting: 00 = 200mV threshold, AV = 6V/V 01 = 100mV threshold, AV = 12V/V 10 = 50mV threshold, AV = 24V/V 11 = 25mV threshold, AV = 48V/V [6:5] Overcurrent Secondary Threshold Deglitch: 00 = No delay 01 = 4ms 10 = 15ms 11 = 60ms Table 9. ADC Configuration Registers REGISTER ADDRESS 43h FLASH ADDRESS BIT RANGE DESCRIPTION [1:0] ADC1 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [3:2] ADC2 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [5:4] ADC3 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [7:6] ADC4 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted 243h ______________________________________________________________________________________ 19 MAX16065/MAX16066 Table 8. Overcurrent Primary Threshold and Current-Sense Control MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 9. ADC Configuration Registers (continued) REGISTER ADDRESS 44h 45h FLASH ADDRESS BIT RANGE DESCRIPTION [1:0] ADC5 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [3:2] ADC6 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [5:4] ADC7 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [7:6] ADC8 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [1:0] ADC9 Full-Scale Range 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [3:2] ADC10 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [5:4] ADC11 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted [7:6] ADC12 Full-Scale Range: 00 = 5.6V 01 = 2.8V 10 = 1.4V 11 = Channel not converted 244h 245h 20 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS 46h FLASH ADDRESS BIT RANGE DESCRIPTION [0] Differential Conversion ADC1–ADC2: 0 = Disabled 1 = Enabled [1] Differential Conversion ADC3–ADC4: 0 = Disabled 1 = Enabled [2] Differential Conversion ADC5–ADC6: 0 = Disabled 1 = Enabled [3] Differential Conversion ADC7–ADC8: 0 = Disabled 1 = Enabled [4] Differential Conversion ADC9–ADC10: 0 = Disabled 1 = Enabled [5] Differential Conversion ADC11–ADC12: 0 = Disabled 1 = Enabled 246h Table 10. ADC Conversion Results (Read Only) REGISTER ADDRESS 00h 01h 02h 03h 04h 05h 06h 07h 08h 09h 0Ah 0Bh 0Ch 0Dh 0Eh 0Fh 10h 11h 12h 13h 14h 15h 16h 17h 18h 19h 1Ah BIT RANGE [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:6] [7:0] [7:0] [7:6] DESCRIPTION ADC1 result (MSB) bits 9–2 ADC1 result (LSB) bits 1–0 ADC2 result (MSB) bits 9–2 ADC2 result (LSB) bits 1–0 ADC3 result (MSB) bits 9–2 ADC3 result (LSB) bits 1–0 ADC4 result (MSB) bits 9–2 ADC4 result (LSB) bits 1–0 ADC5 result (MSB) bits 9–2 ADC5 result (LSB) bits 1–0 ADC6 result (MSB) bits 9–2 ADC6 result (LSB) bits 1–0 ADC7 result (MSB) bits 9–2 ADC7 result (LSB) bits 1–0 ADC8 result (MSB) bits 9–2 ADC8 result (LSB) bits 1–0 ADC9 result (MSB) bits 9–2 ADC9 result (LSB) bits 1–0 ADC10 result (MSB) bits 9–2 ADC10 result (LSB) bits 1–0 ADC11 result (MSB) bits 9–2 ADC11 result (LSB) bits 1–0 ADC12 result (MSB) bits 9–2 ADC12 result (LSB) bits 1–0 Current-sense ADC result CSP ADC output (MSB) bits 9–2 CSP ADC output (LSB) bits 1–0 ______________________________________________________________________________________ 21 MAX16065/MAX16066 Table 9. ADC Configuration Registers (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers When GPIO1–GPIO8 are configured as general-purpose inputs/outputs, read values from the GPIO_ ports through r1Eh and write values to GPIO_s through r3Eh. Note that r3Eh has a corresponding flash register, which programs the default state of a general-purpose output. See Table 11 for more information on reading and writing to the GPIO_. Fault1 and Fault2 GPIO1–GPIO8 are configurable as dedicated fault outputs, Fault1 or Fault2. Fault outputs can assert on one or more overvoltage, undervoltage, or early warning conditions for selected inputs, as well as the secondary overcurrent comparator. Fault1 and Fault2 dependencies are set using registers r36h to r3Ah. See Table 14. When a fault output depends on more than one MON_, the fault output asserts when one or more MON_ exceeds a programmed threshold voltage. These fault outputs act independently of the critical fault system, described in the Critical Faults section. Table 11. GPIO_ State Registers REGISTER ADDRESS 1Eh 3Eh FLASH ADDRESS — 23Eh BIT RANGE DESCRIPTION [0] GPIO1 input state [1] GPIO2 input state [2] GPIO3 input state [3] GPIO4 input state [4] GPIO5 input state [5] GPIO6 input state [6] GPIO7 input state [7] GPIO8 input state [0] GPIO1 output state [1] GPIO2 output state [2] GPIO3 output state [3] GPIO4 output state [4] GPIO5 output state [5] GPIO6 output state [6] GPIO7 output state [7] GPIO8 output state Table 12. GPIO_ Configuration Registers REGISTER ADDRESS 3Fh 40h FLASH ADDRESS 23Fh 240h BIT RANGE DESCRIPTION [2:0] GPIO1 configuration [5:3] GPIO2 configuration [7:6] GPIO3 configuration (LSB) [0] GPIO3 configuration (MSB) [3:1] GPIO4 configuration [6:4] GPIO5 configuration [7] GPIO6 configuration (LSB) 22 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS FLASH ADDRESS 41h 241h BIT RANGE GPIO6 configuration (MSB) [4:2] GPIO7 configuration [7:5] GPIO8 configuration [1] [2] [3] 42h DESCRIPTION [1:0] [0] 242h [4] [5] [6] [7] MAX16065/MAX16066 Table 12. GPIO_ Configuration Registers (continued) Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain Output Configuration 0 = Push-pull 1 = Open drain for GPIO1: for GPIO2: for GPIO3: for GPIO4: for GPIO5: for GPIO6: for GPIO7: for GPIO8: Table 13. GPIO_ Function Configuration Bits GPIO1 GPIO2 000 Logic input Logic input GPIO3 Logic input 001 Logic output Logic output 010 Fault2 output 011 GPIO4 GPIO5 GPIO6 GPIO7 GPIO8 Logic input Logic input Logic input Logic input Logic input Logic output Logic output Logic output Logic output Logic output Logic output Fault2 output Fault2 output Fault2 output Fault2 output Fault2 output Fault2 output Fault2 output Fault1 output Fault1 output FAULTPU output Fault1 output Fault1 output Fault1 output Fault1 output FAULTP output 100 ANY_FAULT output RESET2 output ANY_FAULT output ANY_FAULT output ANY_FAULT output RESET2 output ANY_FAULT output RESET2 output 101 OVERC output OVERC output OVERC output OVERC output OVERC output OVERC output OVERC output OVERC output 110 MR input WDO output MR input WDO output MR input WDO output MR input WDO output 111 WDI input — — EXTFAULT input/output EN2 input MARGIN input EN2 input EXTFAULT input/output ______________________________________________________________________________________ 23 MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers ANY_FAULT GPIO1, GPIO3, GPIO4, GPIO5, and GPIO7 are configurable to assert low during any fault condition. This includes power-up, power-down fault conditions as well as conditions where Fault1 or Fault2 assert. Second Enable (EN2) GPIO5 and GPIO7 are configurable as the enable input for the secondary sequence. See the Multiple Sequencing Groups section for more details. Table 14. Fault1 and Fault2 Dependencies REGISTER ADDRESS 36h 37h 38h FLASH ADDRESS 236h BIT RANGE 0 1 = Fault1 depends on MON1 1 1 = Fault1 depends on MON2 2 1 = Fault1 depends on MON3 3 1 = Fault1 depends on MON4 4 1 = Fault1 depends on MON5 5 1 = Fault1 depends on MON6 6 1 = Fault1 depends on MON7 7 1 = Fault1 depends on MON8 0 1 = Fault1 depends on MON9 1 1 = Fault1 depends on MON10 2 1 = Fault1 depends on MON11 3 1 = Fault1 depends on MON12 4 1 = Fault1 depends on the overvoltage thresholds of the inputs selected by r36h and r37h[3:0] 5 1 = Fault1 depends on the undervoltage thresholds of the inputs selected by r36h and r37h[3:0] 6 1 = Fault1 depends on the early warning thresholds of the inputs selected by r36h and r37h[3:0] 7 0 = Fault1 is an active-low digital output 1 = Fault1 is an active-high digital output 237h 238h DESCRIPTION [0] 1 = Fault2 depends on MON1 [1] 1 = Fault2 depends on MON2 [2] 1 = Fault2 depends on MON3 [3] 1 = Fault2 depends on MON4 [4] 1 = Fault2 depends on MON5 [5] 1 = Fault2 depends on MON6 [6] 1 = Fault2 depends on MON7 [7] 1 = Fault2 depends on MON8 24 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS 39h 3Ah FLASH ADDRESS BIT RANGE [0] 1 = Fault2 depends on MON9 [1] 1 = Fault2 depends on MON10 [2] 1 = Fault2 depends on MON11 [3] 1 = Fault2 depends on MON12 [4] 1 = Fault2 depends on the overvoltage thresholds of the inputs selected by r38h and r39h[3:0] [5] 1 = Fault2 depends on the undervoltage thresholds of the inputs selected by r38h and r39h[3:0] [6] 1 = Fault2 depends on the early warning thresholds of the inputs selected by r38h and r39h[3:0] [7] 0 = Fault2 is an active-low digital output 1 = Fault2 is an active-high digital output [0] 1 = Fault1 depends on secondary overcurrent comparator [1] 1 = Fault2 depends on secondary overcurrent comparator 239h 23Ah DESCRIPTION [7:2] Reserved Overcurrent Comparator (OVERC) GPIO1 to GPIO8 are configurable to assert low when the voltage across CSP and CSM exceed the primary overcurrent threshold. See the Internal Current-Sense Amplifier section for more details. no MON_ inputs are assigned to Slot 12, the power-up sequence is complete after the slot sequence delay expires. RESET2 shares configuration bits with RESET with the exception of polarity (active-high or active-low) and output type (push-pull or open drain), see Table 23. Fault-On Power-Up (FAULTPU) GPIO3 and GPIO8 are configurable to indicate a fault during power-up or power-down on the secondary sequence. This output asserts low when a MON_ input exceeds the overvoltage or undervoltage threshold. The sequencer will still enter the fault state and turn off all the EN_OUT_ outputs assigned to the secondary sequence. During normal monitoring, RESET2 can be configured to assert when any combination of MON_ inputs violates configurable combinations of thresholds: undervoltage, overvoltage, or early warning. Select the combination of thresholds using r3Bh[1:0], and select the combination of MON_ inputs using 3Ch[7:1] and 3Dh[4:0]. Note that MON_ inputs in the secondary sequence configured as critical faults will always cause RESET2 to assert regardless of these configuration bits. Manual Reset (MR) GPIO1, GPIO3, GPIO5, and GPIO7 are configurable to act as an active-low manual reset input, MR. Drive MR low to assert RESET. RESET remains asserted for the selected reset timeout period after MR transitions from low to high. See the RESET2 Output section for more information on selecting a reset timeout period. RESET2 Output GPIO2, GPIO6, and GPIO8 are configurable to act as a reset indicator related to the secondary sequence. RESET2 asserts during power-up/power-down and deasserts following the reset timeout period once the powerup of the secondary sequence is complete. The secondary power-up sequence is completed when any MON_ inputs assigned to Slot 12 exceed the undervoltage thresholds and Slot 12 sequence delay expires. When RESET2 can be configured as push-pull or open drain using the appropriate GPIO_ configuration bit in r42h (see Table 12), and is always active-low. Select the reset timeout for RESET and RESET2 by loading a value from Table 5 into r3Bh[7:4]. RESET and RESET2 can be forced to assert by writing a ‘1’ into r3Ch[0]. RESET2 remains asserted for the reset timeout period after a ‘0’ is written into r3Ch[0]. Watchdog Input (WDI) and Output (WDO) GPIO2, GPIO4, GPIO6, and GPIO8 are configurable as the watchdog timer output, WDO. GPIO1 is configurable as WDI. See Table 24 for configuration details. WDO is an active-low output. See the Watchdog Timer section for more information about the operation of the watchdog timer. ______________________________________________________________________________________ 25 MAX16065/MAX16066 Table 14. Fault1 and Fault2 Dependencies (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers External Fault (EXTFAULT) GPIO4 and GPIO8 are configurable as the external fault input/output. When configured as push-pull, EXTFAULT signals that a critical fault has occurred on one or more monitored voltages or current. When configured as open-drain, EXTFAULT can be asserted low by an external circuit to trigger a critical fault. This signal can be used to cascade multiple MAX16065/MAX16066s. Two configuration bits determine the behavior of the MAX16065/MAX16066 when EXTFAULT is pulled low by some other device. Register bit r72h[5], if set to a ‘1’, causes the sequencer state machine to enter the fault state, deasserting all the outputs, when EXTFAULT is pulled low. When this happens, the flag bit r1Ch[5] gets set to indicate the cause of the fault. If register bit r6Dh[2] is set in addition to r72h[5], EXTFAULT going low triggers a nonvolatile fault log operation. Faults tiplexer. Only the upper 8 bits of a conversion result are compared with the programmed fault thresholds. The general-purpose inputs/outputs (GPIO1 to GPIO8) can be configured as ANY_FAULT outputs or dedicated Fault1 and Fault2 outputs to indicate fault conditions. These fault outputs are not masked by the critical fault enable bits shown in Table 18. See the General-Purpose Inputs/Outputs section for more information on configuring GPIO_s as fault outputs. Deglitch Fault conditions are detected at the end of each conversion. When the voltage on an input falls outside a monitored threshold for one acquisition, the input multiplexer remains on that channel and performs several successive conversions. To trigger a fault, the input must stay outside the threshold for a certain number of acquisitions as determined by the deglitch setting in r73h[6:5] and r74h[6:5] (see Table 16). The MAX16065/MAX16066 monitor the input (MON_) channels and compare the results with an overvoltage threshold, an undervoltage threshold, and a selectable overvoltage or undervoltage early warning threshold. Based on these conditions, the MAX16065/MAX16066 assert various fault outputs and save specific information about the channel conditions and voltages into the nonvolatile flash. Once a critical fault event occurs, the failing channel condition, ADC conversions at the time of the fault, or both can be saved by configuring the event logger. The event logger records a single failure in the internal flash and sets a lock bit that protects the stored fault data from accidental erasure on a subsequent power-up. Fault Flags Fault flags indicate the fault status of a particular input. The fault flag of any monitored input in the device can be read at any time from registers r1Bh and r1Ch, as shown in Table 17. Clear a fault flag by writing a ‘1’ to the appropriate bit in the flag register. Unlike the fault signals sent to the fault outputs, these bits are masked by the critical fault enable bits (see Table 18). The fault flag is only set when the matching enable bit in the critical fault enable register is also set. An overvoltage event occurs when the voltage at a monitored input exceeds the overvoltage threshold for that input. An undervoltage event occurs when the voltage at a monitored input falls below the undervoltage threshold. Fault thresholds are set in registers r48h to r6Ch as shown in Table 15. Disabled inputs are not monitored for fault conditions and are skipped over by the input mul- If a fault occurs during the secondary sequence group, the slot number where the failure occurred is stored in r1Dh. If a GPIO_ is configured as an open-drain EXTFAULT input/output, and EXTFAULT is pulled low by an external circuit, bit r1Ch[5] is set. The SMBus Alert bit is set if the MAX16065/MAX16066 have asserted the SMBus Alert output. Clear by writing a ‘1’. See the SMBALERT section for more details. 26 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS FLASH ADDRESS BIT RANGE 48h 248h [7:0] MON1 secondary threshold 49h 249h [7:0] MON1 overvoltage threshold 4Ah 24Ah [7:0] MON1 undervoltage threshold 4Bh 24Bh [7:0] MON2 secondary threshold 4Ch 24Ch [7:0] MON2 overvoltage threshold 4Dh 24Dh [7:0] MON2 undervoltage threshold 4Eh 24Eh [7:0] MON3 secondary threshold 4Fh 24Fh [7:0] MON3 overvoltage threshold 50h 250h [7:0] MON3 undervoltage threshold 51h 251h [7:0] MON4 secondary threshold 52h 252h [7:0] MON4 overvoltage threshold 53h 253h [7:0] MON4 undervoltage threshold 54h 254h [7:0] MON5 secondary threshold 55h 255h [7:0] MON5 overvoltage threshold 56h 256h [7:0] MON5 undervoltage threshold 57h 257h [7:0] MON6 secondary threshold 58h 258h [7:0] MON6 overvoltage threshold DESCRIPTION 59h 259h [7:0] MON6 undervoltage threshold 5Ah 25Ah [7:0] MON7 secondary threshold 5Bh 25Bh [7:0] MON7 overvoltage threshold 5Ch 25Ch [7:0] MON7 undervoltage threshold 5Dh 25Dh [7:0] MON8 secondary threshold 5Eh 25Eh [7:0] MON8 overvoltage threshold 5Fh 25Fh [7:0] MON8 undervoltage threshold 60h 260h [7:0] MON9 secondary threshold 61h 261h [7:0] MON9 overvoltage threshold 62h 262h [7:0] MON9 undervoltage threshold 63h 263h [7:0] MON10 secondary threshold 64h 264h [7:0] MON10 overvoltage threshold 65h 265h [7:0] MON10 undervoltage threshold 66h 266h [7:0] MON11 secondary threshold 67h 267h [7:0] MON11 overvoltage threshold 68h 268h [7:0] MON11 undervoltage threshold 69h 269h [7:0] MON12 secondary threshold 6Ah 26Ah [7:0] MON12 overvoltage threshold 6Bh 26Bh [7:0] MON12 undervoltage threshold 6Ch 26Ch [7:0] Secondary overcurrent threshold ______________________________________________________________________________________ 27 MAX16065/MAX16066 Table 15. Fault Threshold Registers MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 16. Deglitch Configuration REGISTER ADDRESS FLASH ADDRESS 73h 273h 74h 274h BIT RANGE DESCRIPTION [6:5] Overcurrent Comparator Deglitch Time: 00 = No deglitch 01 = 4ms 10 = 15ms 11 = 60ms [6:5] Voltage Comparator Deglitch Configuration: 00 = 2 cycles 01 = 4 cycles 10 = 8 cycles 11 = 16 cycles Critical Faults During normal operation, a fault condition can be configured to shut down all the EN_OUT_s and store fault information in the flash memory by setting the appropriate critical fault enable bits. During power-up and power-down, all sequenced MON_ inputs are considered critical. Faults during power-up and power-down always cause the EN_OUT_s to turn off and can store fault information in the flash memory, depending on the contents of r6Dh[1:0]. Set the appropriate critical fault enable bits in registers r6Eh to r72h (see Table 18) for a fault condition to trigger a critical fault. Logged fault information is stored in flash registers r200h to r20Fh (see Table 19). After fault information is logged, the flash is locked and must be unlocked to enable a new fault log to be stored. Write a ‘0’ to r8Ch[1] to unlock the FAULT flash. Fault information can be configured to store ADC conversion results and/or fault flags in registers. Select the critical fault configuration in r6Dh[1:0]. Set r6Dh[1:0] to ‘11’ to turn off the fault logger. All stored ADC results are 8 bits wide. Power-Up/Power-Down Faults All EN_OUT_s deassert when an overvoltage or undervoltage fault is detected during power-up/power-down and the MAX16065/MAX16066 return to the poweroff condition. Fault information can be stored to flash depending on r6D[1:0], see Table 18. GPIO3 and GPIO8 can be configured as power-up fault outputs (ANY_FAULT). Autoretry/Latch Mode The MAX16065/MAX16066 can be configured for one of two fault management methods: autoretry or latchon fault. Set r74h[4:3] to ‘00’ to select the latch-on-fault mode. In this configuration, EN_OUT_s deassert after a critical fault event. The device does not reinitiate the power-up sequence until EN is toggled or the Software Enable bit is toggled. See the Enable section for more information on setting the software enable bit. Table 17. Fault Flags REGISTER ADDRESS 1Bh BIT RANGE DESCRIPTION [0] MON1 [1] MON2 [2] MON3 [3] MON4 [4] MON5 [5] MON6 [6] MON7 [7] MON8 28 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS BIT RANGE 1Ch 1Dh DESCRIPTION [0] MON9 [1] MON10 [2] MON11 [3] MON12 [4] Overcurrent [5] External fault (EXTFAULT) [6] SMB alert [4:0] Slot where failure occurred during secondary sequence [7:5] Reserved Table 18. Critical Fault Configuration REGISTER ADDRESS FLASH ADDRESS BIT RANGE [1:0] 6Dh 26Dh [2] [7:3] 6Eh 6Fh 26Eh 26Fh DESCRIPTION Fault Information to Log: 00 = Save failed line flags and ADC values in flash 01 = Save only failed line flags in flash 10 = Save only ADC values in flash 11 = Do not save anything 1 = Fault log triggered when EXTFAULT is pulled low externally Not used [0] 1 = Fault log triggered when MON1 is below its undervoltage threshold [1] 1 = Fault log triggered when MON2 is below its undervoltage threshold [2] 1 = Fault log triggered when MON3 is below its undervoltage threshold [3] 1 = Fault log triggered when MON4 is below its undervoltage threshold [4] 1 = Fault log triggered when MON5 is below its undervoltage threshold [5] 1 = Fault log triggered when MON6 is below its undervoltage threshold [6] 1 = Fault log triggered when MON7 is below its undervoltage threshold [7] 1 = Fault log triggered when MON8 is below its undervoltage threshold [0] 1 = Fault log triggered when MON9 is below its undervoltage threshold [1] 1 = Fault log triggered when MON10 is below its undervoltage threshold [2] 1 = Fault log triggered when MON11 is below its undervoltage threshold [3] 1 = Fault log triggered when MON12 is below its undervoltage threshold [4] 1 = Fault log triggered when MON1 is above its overvoltage threshold [5] 1 = Fault log triggered when MON2 is above its overvoltage threshold [6] 1 = Fault log triggered when MON3 is above its overvoltage threshold [7] 1 = Fault log triggered when MON4 is above its overvoltage threshold ______________________________________________________________________________________ 29 MAX16065/MAX16066 Table 17. Fault Flags (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 18. Critical Fault Configuration (continued) REGISTER ADDRESS 70h FLASH ADDRESS 270h 71h 271h 72h 272h BIT RANGE DESCRIPTION [0] 1 = Fault log triggered when MON5 is above its overvoltage threshold [1] 1 = Fault log triggered when MON6 is above its overvoltage threshold [2] 1 = Fault log triggered when MON7 is above its overvoltage threshold [3] 1 = Fault log triggered when MON8 is above its overvoltage threshold [4] 1 = Fault log triggered when MON9 is above its overvoltage threshold [5] 1 = Fault log triggered when MON10 is above its overvoltage threshold [6] 1 = Fault log triggered when MON11 is above its overvoltage threshold [7] 1 = Fault log triggered when MON12 is above its overvoltage threshold [0] 1 = Fault log triggered when MON1 is above/below the early threshold warning [1] 1 = Fault log triggered when MON2 is above/below the early threshold warning [2] 1 = Fault log triggered when MON3 is above/below the early threshold warning [3] 1 = Fault log triggered when MON4 is above/below the early threshold warning [4] 1 = Fault log triggered when MON5 is above/below the early threshold warning [5] 1 = Fault log triggered when MON6 is above/below the early threshold warning [6] 1 = Fault log triggered when MON7 is above/below the early threshold warning [7] 1 = Fault log triggered when MON8 is above/below the early threshold warning [0] 1 = Fault log triggered when MON9 is above/below the early threshold warning [1] 1 = Fault log triggered when MON10 is above/below the early threshold warning [2] 1 = Fault log triggered when MON11 is above/below the early threshold warning [3] 1 = Fault log triggered when MON12 is above/below the early threshold warning [4] 1 = Fault log triggered when overcurrent early threshold is exceeded [5] 1 = EXTFAULT pulled low externally causes sequencer to enter fault state, turning off all EN_OUT_s 0 = EXTFAULT pulled low externally does not cause sequencer to enter fault state [7:6] Reserved Table 19. Nonvolatile Fault Log Registers FLASH ADDRESS 200h 201h BIT RANGE DESCRIPTION [4:0] Sequencer state where the fault has happened (see Table 1 for state codes) [7:5] Not used [0] Fault log triggered on MON1 [1] Fault log triggered on MON2 [2] Fault log triggered on MON3 [3] Fault log triggered on MON4 [4] Fault log triggered on MON5 [5] Fault log triggered on MON6 [6] Fault log triggered on MON7 [7] Fault log triggered on MON8 30 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers FLASH ADDRESS BIT RANGE 202h DESCRIPTION [0] Fault log triggered on MON9 [1] Fault log triggered on MON10 [2] Fault log triggered on MON11 [3] Fault log triggered on MON12 [4] Fault log triggered on overcurrent [5] Fault log triggered on EXTFAULT [7:6] Not used 203h [7:0] MON1 ADC output bits 9–2 204h [7:0] MON2 ADC output bits 9–2 205h [7:0] MON3 ADC output bits 9–2 206h [7:0] MON4 ADC output bits 9–2 207h [7:0] MON5 ADC output bits 9–2 208h [7:0] MON6 ADC output bits 9–2 209h [7:0] MON7 ADC output bits 9–2 20Ah [7:0] MON8 ADC output bits 9–2 20Bh [7:0] MON9 ADC output bits 9–2 20Ch [7:0] MON10 ADC output bits 9–2 20Dh [7:0] MON11 ADC output bits 9–2 20Eh [7:0] MON12 ADC output bits 9–2 20Fh [7:0] Current-sense ADC output bits 9–2 Table 20. Autoretry Configuration REGISTER ADDRESS 74h FLASH ADDRESS BIT RANGE DESCRIPTION [2:0] Retry Delay: 000 = 20ms 001 = 40ms 010 = 80ms 011 = 150ms 100 = 280ms 101 = 540ms 110 = 1s 111 = 2s [4:3] Autoretry/Latch Mode: 00 = Latch 01 = Retry 1 time 10 = Retry 3 times 11 = Always retry 274h ______________________________________________________________________________________ 31 MAX16065/MAX16066 Table 19. Nonvolatile Fault Log Registers (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Set r74h[4:3] to a value other than ‘00’ to select autoretry mode (see Table 20). In this configuration, the device shuts down after a critical fault event then restarts following a configurable delay. Use r74h[2:0] to select an autoretry delay from 20ms to 1.6s. See Table 20 for more information on setting the autoretry delay. When fault information is stored in flash (see the Critical Faults section) and autoretry mode is selected, set an autoretry delay greater than the time required for the storing operation. When fault information is stored in flash and latch-on-fault mode is chosen, toggle EN or reset the software enable bit only after the completion of the storing operation. When saving information about the failed lines only, ensure a delay of at least 150ms before the restart procedure. Otherwise, ensure a minimum 280ms timeout, to ensure that ADC conversions are completed and values are stored correctly in flash. Programmable Ouputs (EN_OUT1–EN_OUT12) The MAX16065 includes twelve programmable outputs, and the MAX16066 includes eight programmable outputs. These outputs are capable of connecting to either the enable (EN) inputs of a DC-DC or LDO power supply, or to drive the gate of an n-channel MOSFET in charge-pump mode. Selectable output configurations include: active-low or active-high, open drain or pushpull. EN_OUT1–EN_OUT8 can act as charge-pump outputs, EN_OUT9–EN_OUT12 can be configured as general-purpose inputs or general-purpose outputs. Use registers r30h to r33h to configure outputs. See Table 21 for detailed information on configuring EN_OUT1– EN_OUT12. In charge-pump configuration, EN_OUT1–EN_OUT8 act as high-voltage charge-pump outputs to drive up to eight external n-channel MOSFETs. During sequencing, an EN_ OUT_ output set to the charge-pump configuration outputs 11V relative to GND. See the Sequencing section for more detailed information on power-supply sequencing. In open-drain output configuration, connect an external pullup resistor from the output to an external voltage up to 5.5V (EN_OUT9–EN_OUT12) or 14V (EN_OUT1– EN_OUT8). Choose the pullup resistor depending on the number of devices connected to the open-drain output and the allowable current consumption. The open-drain output configuration allows wire-ORed connection. In push-pull configuration, the MAX16065/MAX16066’s programmable outputs are referenced to VDBP. Table 21. EN_OUT1–EN_OUT12 Configuration REGISTER ADDRESS 30h FLASH ADDRESS BIT RANGE DESCRIPTION [1:0] EN_OUT1 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [3:2] EN_OUT2 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [5:4] EN_OUT3 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [7:6] EN_OUT4 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull 230h 32 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS 31h FLASH ADDRESS BIT RANGE [1:0] EN_OUT5 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [3:2] EN_OUT6 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [5:4] EN_OUT7 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [7:6] EN_OUT8 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [1:0] EN_OUT9 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [3:2] EN_OUT10 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [5:4] EN_OUT11 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull [7:6] EN_OUT12 Configuration: 00 = Active-low, open drain 01 = Active-high, open drain 10 = Active-low, push-pull 11 = Active-high, push-pull 231h 32h (MAX16065 Only) DESCRIPTION 232h ______________________________________________________________________________________ 33 MAX16065/MAX16066 Table 21. EN_OUT1–EN_OUT12 Configuration (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 21. EN_OUT1–EN_OUT12 Configuration (continued) REGISTER ADDRESS 33h FLASH ADDRESS BIT RANGE DESCRIPTION [0] EN_OUT1 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [1] EN_OUT2 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [2] EN_OUT3 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [3] EN_OUT4 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [4] EN_OUT5 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [5] EN_OUT6 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [6] EN_OUT7 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) [7] EN_OUT8 Charge-Pump Output Configuration: 0 = Charge-pump output disabled 1 = Charge-pump output enabled (active-high) 233h EN_OUT_s as GPIO_ (MAX16065 Only) EN_OUT9 to EN_OUT12 can be configured as GPIO_ by setting the sequencing slot assignments in r88h and r89h to ‘1101’ and ‘1110’, see Tables 5 and 6. If an EN_OUT_ is configured as a general-purpose input, the state of the pin can be read from r1Fh (see Table 22). If an EN_OUT_ is configured as a general-purpose output, it is controlled by r34h. EN_OUT_ State During Power-Up When VCC is ramped from 0 to the operating supply voltage, the EN_OUT_ output is high impedance until VCC reaches UVLO and then EN_OUT_ goes into the configured deasserted state after the boot-up relay. See Figures 6 and 7. Configure RESET as an active-low push-pull or open-drain output pulled up to VCC through a 10kI resistor for Figures 6 and 7. Reset Output The reset output, RESET, indicates the status of the primary sequence. It asserts during power-up/power-down and deasserts following the reset timeout period once the power-up sequence is complete. The power-up sequence is complete when any MON_ inputs assigned to the final slot exceed the undervoltage thresholds and final sequence delay expires. When no MON_ inputs are assigned to the final slot, the power-up sequence is complete after the slot sequence delay expires. During normal monitoring, RESET can be configured to assert when any combination of MON_ inputs violates configurable combinations of thresholds: undervoltage, overvoltage, or early warning. Select the combination of thresholds using r3Bh[1:0], and select the combination of MON_ inputs using r3Ch[7:1] and r3Dh[4:0]. Note that MON_ inputs configured as critical faults will always cause RESET to assert regardless of these configuration bits. RESET can be configured as push-pull or open drain using r3Bh[3], and active-high or active-low using r3Bh[2]. Select the reset timeout by loading a value from Table 23 into r3Bh[7:4]. RESET can be forced to assert by writing a ‘1’ into r3Ch[0]. RESET remains asserted for the reset timeout period after a ‘0’ is written into r3Ch[0]. See Table 23. The current state of RESET can be checked by reading r20h[0]. 34 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS FLASH ADDRESS 1Fh BIT RANGE — 34h 234h DESCRIPTION [0] EN_OUT9 input state [1] EN_OUT10 input state [2] EN_OUT11 input state [3] EN_OUT12 input state [0] 1 = Assert EN_OUT9 [1] 1 = Assert EN_OUT10 [2] 1 = Assert EN_OUT11 [3] 1 = Assert EN_OUT12 MAX16065 fig06 MAX16065 fig07 VCC 2V/div UVLO VCC 2V/div 0V 0V RESET 2V/div 0V RESET 2V/div 0V EN_OUT_ 2V/div 0V 20ms/div ASSERTED LOW HIGH-Z EN_OUT_ 2V/div 0V 10ms/div Figure 6. RESET and EN_OUT_ During Power-Up, EN_OUT_ in Open-Drain Active-Low Configuration Figure 7. RESET and EN_OUT_ During Power-Up, EN_OUT_ in Push-Pull Active-High Configuration Watchdog Timer Dependent Watchdog Timer Operation Use the watchdog timer to monitor FP activity in two modes. Flexible timeout architecture provides an adjustable watchdog startup delay of up to 300s, allowing complicated systems to complete lengthy boot-up routines. An adjustable watchdog timeout allows the supervisor to provide quick alerts when processor activity fails. After each reset event (VCC drops below UVLO then returns above UVLO, software reboot, manual reset (MR), EN input going low then high, or watchdog reset) and once sequencing is complete, the watchdog startup delay provides an extended time for the system to power up and fully initialize all FP and system components before assuming responsibility for routine watchdog updates. Set r76h[6:4] to a value other than ‘000’ to enable the watchdog startup delay. Set r76h[6:4] to ‘000’ to disable the watchdog startup delay. The watchdog timer operates together with or independently of the MAX16065/MAX16066. When operating in dependent mode, the watchdog is not activated until the sequencing is complete and RESET is deasserted. When operating in independent mode, the watchdog timer is independent of the sequencing operation and activates immediately after VCC exceeds the UVLO threshold and the boot phase is complete. Set r73h[4] to ‘0’ to configure the watchdog in dependent mode. Set r73h[4] to ‘1’ to configure the watchdog in independent mode. See Table 24 for more information on configuring the watchdog timer in dependent or independent mode. ______________________________________________________________________________________ 35 MAX16065/MAX16066 Table 22. EN_OUT_ GPIO_ State Registers MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 23. Reset Output Configuration REGISTER ADDRESS FLASH ADDRESS BIT RANGE [1:0] 3Bh 0 = Active-low 1 = Active-high [3] 0 = Push-pull 1 = Open drain 23Bh 3Dh 23Ch 23Dh Reset Output Depends On: 00 = Undervoltage threshold violations 01 = Early warning threshold violations 10 = Overvoltage threshold violations 11 = Undervoltage or overvoltage threshold violations [2] [7:4] 3Ch DESCRIPTION Reset Timeout Period: 0000 = 25Fs 0001 = 1.5ms 0010 = 2.5ms 0011 = 4ms 0100 = 6ms 0101 = 10ms 0110 = 15ms 0111 = 25ms 1000 = 40ms 1001 = 60ms 1010 = 100ms 1011 = 150ms 1100 = 250ms 1101 = 400ms 1110 = 600ms 1111 = 1s [0] Reset Soft Trigger: 0 = Normal RESET behavior 1 = Force RESET to assert [1] 1 = RESET depends on MON1 [2] 1 = RESET depends on MON2 [3] 1 = RESET depends on MON3 [4] 1 = RESET depends on MON4 [5] 1 = RESET depends on MON5 [6] 1 = RESET depends on MON6 [7] 1 = RESET depends on MON7 [0] 1 = RESET depends on MON8 [1] 1 = RESET depends on MON9 [2] 1 = RESET depends on MON10 [3] 1 = RESET depends on MON11 [4] 1 = RESET depends on MON12 [7:5] Reserved 36 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers The watchdog can be configured to control the RESET output as well as the WDO output. RESET asserts for the reset timeout, tRP, when the watchdog timer expires and the Watchdog Reset Output Enable bit (r76h[7]) is set to ‘1.’ When RESET is asserted, the watchdog timer is cleared and WDO is deasserted, therefore, WDO pulses low for a short time (approximately 1Fs) when the watchdog timer expires. RESET is not affected by the watchdog timer when the Watchdog Reset Output Enable bit (r76h[7]) is set to ‘0.’ If a RESET is asserted by the watchdog timeout, the WDRESET bit is set to ‘1.’ A connected processor can check this bit to see the reset was due to a watchdog timeout. See Table 24 for more information on configuring watchdog functionality. While EN is low, the watchdog timer is in reset. The watchdog timer does not begin counting until the poweron mode is reached and RESET is deasserted. The watchdog timer is reset and WDO deasserts any time RESET is asserted (Figure 10). The watchdog timer will be held in reset while RESET is asserted. VTH LAST MON_ < tWDI tWDI_STARTUP WDI < tWDI tRP RESET Figure 8. Normal Watchdog Startup Sequence VCC WDI < tWDI < tWDI > tWDI < tWDI < tWDI < tWDI < tWDI 0V tWDI VCC WDO 0V Figure 9. Watchdog Timer Operation ______________________________________________________________________________________ 37 MAX16065/MAX16066 The normal watchdog timeout period, tWDI, begins after the first transition on WDI before the conclusion of the long startup watchdog period, tWDI_STARTUP (Figures 7 and 8). During the normal operating mode, WDO asserts if the FP does not toggle WDI with a valid transition (high-to-low or low-to-high) within the standard timeout period, tWDI. WDO remains asserted until WDI is toggled or RESET is asserted (Figure 9). MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers VCC < tWDI WDI tWDI tRP < tWDI_STARTUP 0V VCC RESET 0V VCC WDO 0V 1µs Figure 10. Watchdog Startup Sequence with Watchdog Reset Enable Bit Set to ‘1’ Table 24. Watchdog Configuration REGISTER ADDRESS FLASH ADDRESS BIT RANGE 73h 273h [4] 1 = Independent mode 0 = Dependent mode [7] 1 = Watchdog affects RESET output 0 = Watchdog does not affect RESET output 76h DESCRIPTION [6:4] Watchdog Startup Delay: 000 = No initial timeout 001 = 30s 010 = 40s 011 = 80s 100 = 120s 101 = 160s 110 = 220s 111 = 300s [3:0] Watchdog Timeout: 0000 = Watchdog disabled 0001 = 1ms 0010 = 2ms 0011 = 4ms 0100 = 8ms 0101 = 14ms 0110 = 27ms 0111 = 50ms 1000 = 100ms 1001 = 200ms 1010 = 400ms 1011 = 750ms 1100 = 1.4s 1101 = 2.7s 1110 = 5s 1111 = 10s 276h 38 ������������������������������������������������������������������������������������� < tWDI 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS 8Ch FLASH ADDRESS BIT RANGE DESCRIPTION 0 Configuration Register Lock: 1 = Locked 0 = Unlocked 1 Flash Fault Register Lock: 1 = Locked 0 = Unlocked 2 Flash Configuration Lock: 1 = Locked 0 = Unlocked 3 User Flash Lock: 1 = Locked 0 = Unlocked 28Ch Independent Watchdog Timer Operation When r73h[3] is ‘1’ the watchdog timer operates in independent mode. In independent mode, the watchdog timer operates as if it were a separate device. The watchdog timer is activated immediately upon VCC exceeding UVLO and once the boot-up sequence is finished. When RESET is asserted by the sequencer state machine, the watchdog timer and WDO are not affected. There will be a startup delay if r76h[6:4] is set to a value different than ‘000.’ If r76h[6:4] is set to ‘000,’ there will not be a startup delay. See Table 24 for delay times. In independent mode, if the Watchdog Reset Output Enable bit r76h[7] is set to ‘1,’ when the watchdog timer expires, WDO asserts then RESET asserts. WDO will then deassert. WDO will be low for approximately 1Fs. If the Watchdog Reset Output Enable bit (r76h[7]) is set to ‘0,’ when the WDT expires, WDO asserts but RESET is not affected. User-Defined Register Register r8Ah provides storage space for a user-defined configuration or firmware version number. Note that this register controls the contents of the JTAG USERCODE register bits 7:0. The user-defined register is stored at r28Ah in the flash memory. Memory Lock Bits Register r8Ch contains the lock bits for the configuration registers, configuration flash, user flash and fault register lock. See Table 25 for details. SMBus-Compatible Interface The MAX16065/MAX16066 feature an SMBuscompatible, 2-wire serial interface consisting of a serial data line (SDA) and a serial clock line (SCL). SDA and SCL facilitate bidirectional communication between the MAX16065/MAX16066 and the master device at clock rates up to 400kHz. Figure 1 shows the 2-wire interface timing diagram. The MAX16065/MAX16066 are transmit/ receive slave-only devices, relying upon a master device to generate a clock signal. The master device (typically a microcontroller) initiates a data transfer on the bus and generates SCL to permit that transfer. A master device communicates to the MAX16065/ MAX16066 by transmitting the proper address followed by a command and/or data words. The slave address input, A0, is capable of detecting four different states, allowing multiple identical devices to share the same serial bus. The slave address is described further in the Slave Address section. Each transmit sequence is framed by a START (S) or REPEATED START (SR) condition and a STOP (P) condition. Each word transmitted ______________________________________________________________________________________ 39 MAX16065/MAX16066 Table 25. Memory Lock Bits MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers SDA SDA SCL SCL DATA LINE STABLE, CHANGE OF DATA ALLOWED DATA VALID S P START CONDITION STOP CONDITION Figure 11. Bit Transfer Figure 12. START and STOP Conditions over the bus is 8 bits long and is always followed by an acknowledge pulse. SCL is a logic input, while SDA is an open-drain input/output. SCL and SDA both require external pullup resistors to generate the logic-high voltage. Use 4.7kI for most applications. Acknowledge The acknowledge bit (ACK) is the 9th bit attached to any 8-bit data word. The receiving device always generates an ACK. The MAX16065/MAX16066 generate an ACK when receiving an address or data by pulling SDA low during the 9th clock period (Figure 14). When transmitting data, such as when the master device reads data back from the MAX16065/MAX16066, the device waits for the master device to generate an ACK. Monitoring ACK allows for detection of unsuccessful data transfers. An unsuccessful data transfer occurs if the receiving device is busy or if a system fault has occurred. In the event of an unsuccessful data transfer, the bus master can reattempt communication at a later time. The MAX16065/MAX16066 generate a NACK after the command byte received during a software reboot, while writing to the flash, or when receiving an illegal memory address. Bit Transfer Each clock pulse transfers one data bit. The data on SDA must remain stable while SCL is high (Figure 11); otherwise the MAX16065/MAX16066 register a START or STOP condition (Figure 12) from the master. SDA and SCL idle high when the bus is not busy. START and STOP Conditions Both SCL and SDA idle high when the bus is not busy. A master device signals the beginning of a transmission with a START condition by transitioning SDA from high to low while SCL is high. The master device issues a STOP condition by transitioning SDA from low to high while SCL is high. A STOP condition frees the bus for another transmission. The bus remains active if a REPEATED START condition is generated, such as in the block read protocol (see Figure 1). Early STOP Conditions The MAX16065/MAX16066 recognize a STOP condition at any point during transmission except if a STOP condition occurs in the same high pulse as a START condition. This condition is not a legal SMBus format; at least one clock pulse must separate any START and STOP condition. REPEATED START Conditions A REPEATED START can be sent instead of a STOP condition to maintain control of the bus during a read operation. The START and REPEATED START conditions are functionally identical. Slave Address Use the slave address input, A0, to allow multiple identical devices to share the same serial bus. Connect A0 to GND, DBP (or an external supply voltage greater than 2V), SCL, or SDA to set the device address on the bus. See Table 27 for a listing of all possible 7-bit addresses. The slave address can also be set to a custom value by loading the address into register r8Bh[6:0]. See Table 26. If r8Bh[6:0] is loaded with 00h, the address is set by input A0. Do not set the address to 09h or 7Fh to avoid address conflicts. The slave address setting takes effect immediately after writing to the register. Packet Error Checking (PEC) The MAX16065/MAX16066 feature a PEC mode that is useful for improving the reliability of the communication bus by detecting bit errors. By enabling PEC, an extra 40 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers REGISTER ADDRESS FLASH ADDRESS 8Bh 28Bh BIT RANGE DESCRIPTION [6:0] SMBus Slave Address Register. Set to 00h to use A0 pin address setting. [7] 1 = Enable PEC (packet error check). Table 27. Setting the SMBus Slave Address SLAVE ADDRESSES A0 SLAVE ADDRESS 0 1010 000R 1 1010 001R SCL 1010 010R SDA 1010 011R R = Read/Write select bit. Table 28. Command codes COMMAND CODE ACTION A5h Block write A6h Block read A7h Reboot flash in register file A8h Trigger emergency save to flash A9h Flash page access ON AAh Flash page access OFF ABh User flash access ON (must be in flash page already) ACh User flash access OFF (return to flash page) CRC-8 error check byte is added in the data string during each read and/or write sequence. Enable PEC by writing a ‘1’ to r8Bh[7]. as a hardware-initiated power-on reset. During boot-up, flash configuration data in the range of 230h to 28Ch is copied to r30h to r8Ch registers in the default page. The CRC-8 byte is calculated using the polynomial C = X8 + X2 + X + 1 Send command code A8h to trigger a fault store to flash. Configure the Critical Fault Log Control register (6Dh) to store ADC conversion results and/or fault flags. The PEC calculation includes all bytes in the transmission, including address, command, and data. The PEC calculation does not include ACK, NACK, START, STOP, or REPEATED START. Command Codes The MAX16065/MAX16066 use eight command codes for block read, block write, and other commands. See Table 28 for a list of command codes. To initiate a software reboot, send A7h using the send byte format. A software-initiated reboot is functionally the same While in the flash page, send command code A9h to access the flash page (addresses from 200h to 28Fh). Once command code A9h has been sent, all addresses are recognized as flash addresses only. Send command code AAh to return to the default page (addresses from 000h to 0FFh). Send command code ABh to access the user flash-page (addresses from 300h to 3A4h and 3ADh to 3FFh), and send command code ACh to return to the flash page. ______________________________________________________________________________________ 41 MAX16065/MAX16066 Table 26. SMBus Settings Register MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers 5) The addressed slave asserts an ACK (or NACK) on SDA. Restrictions When Writing to Flash Flash must be written to 8 bytes at a time. The initial address must be aligned to 8-byte boundaries—the 3 LSBs of the initial address must be ‘000’. Write the 8 bytes using a single block-write command or using 8 successive Write Byte commands. 6) The master sends a STOP condition. Receive Byte The receive byte protocol allows the master device to read the register content of the MAX16065/MAX16066 (see Figure 14). The flash or register address must be preset with a send byte or write word protocol first. Once the read is complete, the internal pointer increases by one. Repeating the receive byte protocol reads the contents of the next address. The receive byte procedure follows: Send Byte The send byte protocol allows the master device to send one byte of data to the slave device (see Figure 14). The send byte presets a register pointer address for a subsequent read or write. The slave sends a NACK instead of an ACK if the master tries to send a memory address or command code that is not allowed. If the master sends A5h or A6h, the data is ACK, because this could be the start of the write block or read block. If the master sends a STOP condition before the slave asserts an ACK, the internal address pointer does not change. If the master sends A7h, this signifies a software reboot. The send byte procedure is the following: 1) The master sends a START condition. 2) The master sends the 7-bit slave address and a read bit (high). 3) The addressed slave asserts an ACK on SDA. 4) The slave sends 8 data bits. 5 The master asserts a NACK on SDA. 1) The master sends a START condition. 6) The master generates a STOP condition. 2) The master sends the 7-bit slave address and a write bit (low). Write Byte The write byte protocol (see Figure 14) allows the master device to write a single byte in the default page, extended page, or flash page, depending on which 3) The addressed slave asserts an ACK on SDA. 4) The master sends an 8-bit memory address or command code. CLOCK PULSE FOR ACKNOWLEDGE 1 SCL 2 8 9 SDA BY TRANSMITTER S NACK SDA BY RECEIVER ACK Figure 13. Acknowledge 42 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers 1) The master sends a START condition. 6) The master sends a REPEATED START condition. 7) The master sends the 7-bit slave address and a read bit (high). 2) The master sends the 7-bit slave address and a write bit (low). 8) The addressed slave asserts an ACK on SDA. 3) The addressed slave asserts an ACK on SDA. 10) The master asserts a NACK on SDA. 4) The master sends an 8-bit memory address. 11) The master sends a STOP condition. 5) The addressed slave asserts an ACK on SDA. 6) The master sends an 8-bit data byte. If the memory address is not valid, it is NACKed by the slave at step 5 and the address pointer is not modified. 7) The addressed slave asserts an ACK on SDA. When PEC is enabled, the Read Byte protocol becomes: 8) The master sends a STOP condition. 1) The master sends a START condition. To write a single byte, only the 8-bit memory address and a single 8-bit data byte are sent. The data byte is written to the addressed location if the memory address is valid. The slave asserts a NACK at step 5 if the memory address is not valid. 2) The master sends the 7-bit slave ID plus a write bit (low). When PEC is enabled, the Write Byte protocol becomes: 1) The master sends a START condition. 2) The master sends the 7-bit slave ID plus a write bit (low). 3) The addressed slave asserts an ACK on the data line. 4) The master sends an 8-bit command code. 5) The active slave asserts an ACK on the data line. 6) The master sends an 8-bit data byte. 7) The slave asserts an ACK on the data line. 9) The slave sends an 8-bit data byte. 3) The addressed slave asserts an ACK on the data line. 4) The master sends 8 data bits. 5) The active slave asserts an ACK on the data line. 6) The master sends a REPEATED START condition. 7) The master sends the 7-bit slave ID plus a read bit (high). 8) The addressed slave asserts an ACK on the data line. 9) The slave sends 8 data bits. 10) The master asserts an ACK on the data line. 11) The slave sends an 8-bit PEC byte. 12) The master asserts a NACK on the data line. 8) The master sends an 8-bit PEC byte. 13) The master generates a STOP condition. 9) The slave asserts an ACK on the data line (if PEC is good, otherwise NACK). Block Write The block write protocol (see Figure 14) allows the master device to write a block of data (1 byte to 16 bytes) to memory. Preload the destination address by a previous send byte command; otherwise the block write command begins to write at the current address pointer. After the last byte is written, the address pointer remains preset to the next valid address. If the number of bytes to be written causes the address pointer to exceed 8Fh for configuration registers or configuration flash or FFh for user flash, the address pointer stays at 8Fh or FFh, respectively, overwriting this memory address with the remaining bytes of data. The slave generates a NACK at step 5 if the command code is invalid or if the device is busy, and the address pointer is not altered. 10) The master generates a STOP condition. Read Byte The read byte protocol (see Figure 14) allows the master device to read a single byte located in the default page, extended page, or flash page depending on which page is currently selected. The read byte procedure is the following: 1) The master sends a START condition. 2) The master sends the 7-bit slave address and a write bit (low). 3) The addressed slave asserts an ACK on SDA. 4) The master sends an 8-bit memory address. 5) The addressed slave asserts an ACK on SDA. ______________________________________________________________________________________ 43 MAX16065/MAX16066 page is currently selected. The write byte procedure is the following: MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers The block write procedure is the following: 1) The master sends a START condition. 2) The master sends the 7-bit slave address and a write bit (low). 3) The addressed slave asserts an ACK on SDA. 4) The master sends the 8-bit command code for a block write (94h). the configuration register or configuration flash or FFh in user flash, the address pointer stays at 8Fh or FFh, respectively. The block read procedure is the following: 1) The master sends a START condition. 2) The master sends the 7-bit slave address and a write bit (low). 3) The addressed slave asserts an ACK on SDA. 5) The addressed slave asserts an ACK on SDA. 4) The master sends 8 bits of the block read command (95h). 6) The master sends the 8-bit byte count (1 byte to 16 bytes), n. 5) The slave asserts an ACK on SDA, unless busy. 7) The addressed slave asserts an ACK on SDA. 8) The master sends 8 bits of data. 7) The master sends the 7-bit slave address and a read bit (high). 9) The addressed slave asserts an ACK on SDA. 8) The slave asserts an ACK on SDA. 10) Repeat steps 8 and 9 n - 1 times. 9) The slave sends the 8-bit byte count (16). 11) The master sends a STOP condition. 10)The master asserts an ACK on SDA. When PEC is enabled, the Block Write protocol becomes: 11)The slave sends 8 bits of data. 1) The master sends a START condition. 12)The master asserts an ACK on SDA. 2) The master sends the 7-bit slave ID plus a write bit (low). 13)Repeat steps 11 and 12 up to fifteen times. 3) The addressed slave asserts an ACK on the data line. 15)The master sends a STOP condition. 4) The master sends 8 bits of the block write command code. When PEC is enabled, the Block Read protocol becomes: 5) The slave asserts an ACK on the data line. 1) The master sends a START condition. 6) The master sends an 8-bit byte count (min 1, max 16) N. 2) The master sends the 7-bit slave ID plus a write bit (low). 7) The slave asserts an ACK on the data line. 3) The addressed slave asserts an ACK on the data line. 8) The master sends 8 bits of data. 4) The master sends 8 bits of the block read command code. 9) The slave asserts an ACK on the data line. 10) Repeat 8 and 9 n - 1 times. 11) The master sends an 8-bit PEC byte. 12) The slave asserts an ACK on the data line (if PEC is good, otherwise NACK). 13) The master generates a STOP condition. Block Read The block read protocol (see Figure 14) allows the master device to read a block of up to 16 bytes from memory. Read fewer than 16 bytes of data by issuing an early STOP condition from the master, or by generating a NACK with the master. The destination address should be preloaded by a previous send byte command; otherwise the block read command begins to read at the current address pointer. If the number of bytes to be read causes the address pointer to exceed 8Fh for 6) The master generates a REPEATED START condition. 14)The master asserts a NACK on SDA. 5) The slave asserts an ACK on the data line unless busy. 6) The master sends a REPEATED START condition. 7) The master sends the 7-bit slave ID plus a read bit (high). 8) The slave asserts an ACK on the data line. 9) The slave sends an 8-bit byte count (16). 10) The master asserts an ACK on the data line. 11) The slave sends 8 bits of data. 12) The master asserts an ACK on the data line. 13) Repeat 11 and 12 up to 15 times. 14) The slave sends an 8-bit PEC byte. 15) The master asserts a NACK on the data line. 16) The master generates a STOP condition. 44 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers JTAG Serial Interface The MAX16065/MAX16066 feature a JTAG port that complies with a subset of the IEEE 1149.1 specification. Either the SMBus or the JTAG interface can be used to access internal memory; however, only one interface is allowed to run at a time. The MAX16065/MAX16066 do not support IEEE 1149.1 boundary-scan functionality. The MAX16065/MAX16066 contain extra JTAG instructions and registers not included in the JTAG specification that provide access to internal memory. The extra instructions include LOAD ADDRESS, WRITE, READ, REBOOT, SAVE. Test Access Port (TAP) Controller State Machine The TAP controller is a finite state machine that responds to the logic level at TMS on the rising edge of TCK. See Figure 16 for a diagram of the finite state machine. The possible states are described in the following: Test-Logic-Reset: At power-up, the TAP controller is in the test-logic-reset state. The instruction register contains the IDCODE instruction. All system logic of the device operates normally. This state can be reached from any state by driving TMS high for five clock cycles. Run-Test/Idle: The run-test/idle state is used between scan operations or during specific tests. The instruction register and test data registers remain idle. Select-DR-Scan: All test data registers retain their previous state. With TMS low, a rising edge of TCK moves the controller into the capture-DR state and initiates a scan sequence. TMS high during a rising edge on TCK moves the controller to the select-IR-scan state. Capture-DR: Data can be parallel-loaded into the test data registers selected by the current instruction. If the instruction does not call for a parallel load or the selected test data register does not allow parallel loads, the test data register remains at its current value. On the rising edge of TCK, the controller goes to the shift-DR state if TMS is low or it goes to the exit1-DR state if TMS is high. Shift-DR: The test data register selected by the current instruction connects between TDI and TDO and shifts data one stage toward its serial output on each rising edge of TCK while TMS is low. On the rising edge of TCK, the controller goes to the exit1-DR state if TMS is high. Exit1-DR: While in this state, a rising edge on TCK puts the controller in the update-DR state. A rising edge on TCK with TMS low puts the controller in the pause-DR state. Table 29. SMBus Alert Configuration REGISTER ADDRESS 35h FLASH ADDRESS 235h BIT RANGE [1:0] DESCRIPTION SMBus Alert Configuration: 00 = Disabled 01 = Fault1 is SMBus ALERT 10 = Fault2 is SMBus ALERT 11 = Any_Fault is SMBus ALERT ______________________________________________________________________________________ 45 MAX16065/MAX16066 SMBALERT The MAX16065/MAX16066 support the SMBus alert protocol. To enable the SMBus alert output, set r35h[1:0] according to Table 29, which configures a Fault1, Fault2, or Any_Fault output to act as the SMBus alert. This output is open-drain and uses the wired-OR configuration with other devices on the SMBus. During a fault, the MAX16065/MAX16066 assert ALERT low, signaling the master that an interrupt has occurred. The master responds by sending the ARA (Alert Response Address) protocol on the SMBus. This protocol is a read byte with 09h as the slave address. The slave acknowledges the ARA (09h) address and sends its own SMBus address to the master. The slave then deasserts ALERT. The master can then query the slave and determine the cause of the fault. By checking r1C[6], the master can confirm that the MAX16065/MAX16066 triggered the SMBus alert. The master must send the ARA before clearing r1Ch[6]. Clear r1Ch[6] by writing a ‘1.’ MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Send Byte Format S ADDRESS Receive Byte Format R/W ACK 7 bits 0 COMMAND ACK 8 bits 0 0 Slave Address: Address of the slave on the serial interface bus. S P ADDRESS Data Byte: Presets the internal address pointer or represents a command. ADDRESS 7 bits SLAVE ADDRESS 0 DATA NACK 8 bits 1 P Data Byte: Data is read from the location pointed to by the internal address pointer. SMBALERT# R/W ACK 0 ACK 8 bits 0 0 COMMAND ACK 8 bits 0 0 Slave Address: Address of the slave on the serial interface bus. DATA ACK 8 bits 0 P S SR SLAVE ADDRESS R/W ACK 7 bits ADDRESS R/W ACK 0001100 D.C. 0 Alert Response Address: Only the device that interrupted the master responds to this address. Data Byte: Data is written to the locations set by the internal address pointer. Command Byte: Sets the internal address pointer. R/W ACK 7 bits COMMAND 0 Slave Address: Address of the slave on the serial interface bus. Read Byte Format S 1 Slave Address: Address of the slave on the serial interface bus. Write Byte Format S R/W ACK 7 bits 1 0 DATA BYTE NACK 8 bits DATA NACK 8 bits 1 P Slave Address: Slave places its own address on the serial bus. P 1 Data Byte: Data is written to the locations set by the internal address pointer. Command Byte: Sets the internal address pointer. Block Write Format S ADDRESS R/W ACK 7 bits 0 COMMAND ACK BYTE COUNT = N 8 bits 0 8 bits 0 Slave Address: Address of the slave on the serial interface bus. ACK DATA BYTE 1 ACK DATA BYTE … ACK DATA BYTE N ACK 8 bits 0 Command Byte: FAh 8 bits 0 0 8 bits Slave to master P 0 Master to slave Data Byte: Data is written to the locations set by the internal address pointer. Block Read Format S ADDRESS R/W ACK 7 bits 0 COMMAND ACK 8 bits 0 0 Slave Address: Address of the slave on the serial interface bus. SR ADDRESS R/W ACK 7 bits 1 0 Slave Address: Address of the slave on the serial interface bus. Command Byte: FBh BYTE COUNT = N ACK DATA BYTE N ACK DATA BYTE … ACK DATA BYTE N NACK 8 bits 0 8 bits 0 8 bits 0 8 bits P 1 Data Byte: Data is read from the locations set by the internal address pointer. Write Byte Format with PEC S ADDRESS R/W ACK 7 BITS 0 COMMAND ACK DATA ACK PEC ACK 8 BITS 0 8 BITS 0 8 BITS 0 0 P Read Byte Format with PEC S ADDRESS R/W ACK 7 BITS 0 COMMAND 0 8 BITS ACK SR 0 ADDRESS R/W ACK 1 7 BITS 0 DATA ACK PEC ACK 8 BITS 0 8 BITS 0 P Block Write with PEC S ADDRESS R/W ACK 7 BITS 0 COMMAND 8 BITS 0 ACK BYTE COUNT N ACK DATA BYTE 1 ACK 0 8 BITS 0 8 BITS 0 DATA BYTE ACK 8 BITS 0 DATA N ACK PEC ACK 8 BITS 0 8 BITS 0 DATA BYTE ACK DATA N ACK PEC NACK 8 BITS 0 8 BITS 0 8 BITS 1 P Block Read with PEC S ADDRESS 7 BITS R/W ACK 0 COMMAND 0 8 BITS ACK SR 0 ADDRESS 7 BITS R/W ACK BYTE COUNT N ACK DATA BYTE 1 ACK 1 0 8 BITS S = START Condition ACK = Acknowledge, SDA pulled low during rising edge of SCL. P = STOP Condition NACK = Not acknowledge, SDA left high during rising edge of SCL. Sr = REPEATED START Condition D.C. = Don’t Care All data is clocked in/out of the device on rising edges of SCL. 0 8 BITS 0 = SDA transitions from high to low during period of SCL. = SDA transitions from low to high during period of SCL. Figure 14. SMBus Protocols 46 ������������������������������������������������������������������������������������� P 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers 01100 01011 01010 01001 01000 00111 MEMORY WRITE REGISTER [LENGTH = 8 BITS] 00110 MEMORY READ REGISTER [LENGTH = 8 BITS] 00101 MEMORY ADDRESS REGISTER [LENGTH = 8 BITS] 00100 USER CODE REGISTER [LENGTH = 32 BITS] 00011 IDENTIFICATION REGISTER [LENGTH = 32 BITS] BYPASS REGISTER [LENGTH = 1 BIT] MUX 1 00000 11111 COMMAND DECODER 01001 SETFLSHADD 01010 RSTFLSHADD 01011 SETUSRFLSH 01100 RSTUSRFLSH 01000 SAVE 00111 REBOOT VDB INSTRUCTION REGISTER [LENGTH = 5 BITS] RPU TDI MUX 2 TMS TDO TEST ACCESS PORT (TAP) CONTROLLER TCK Figure 15. JTAG Block Diagram Pause-DR: Shifting of the test data registers halts while in this state. All test data registers retain their previous state. The controller remains in this state while TMS is low. A rising edge on TCK with TMS high puts the controller in the exit2-DR state. changes in the shift register. On the rising edge of TCK, the controller goes to the run-test/idle state if TMS is low or goes to the select-DR-scan state if TMS is high. Exit2-DR: A rising edge on TCK with TMS high while in this state puts the controller in the update-DR state. A rising edge on TCK with TMS low enters the shift-DR state. Select-IR-Scan: All test data registers retain the previous states. The instruction register remains unchanged during this state. With TMS low, a rising edge on TCK moves the controller into the capture-IR state. TMS high during a rising edge on TCK puts the controller back into the test-logic-reset state. Update-DR: A falling edge on TCK while in the updateDR state latches the data from the shift register path of the test data registers into a set of output latches. This prevents changes at the parallel output because of Capture-IR: Use the capture-IR state to load the shift register in the instruction register with a fixed value. This value is loaded on the rising edge of TCK. If TMS is high on the rising edge of TCK, the controller enters the ______________________________________________________________________________________ 47 MAX16065/MAX16066 REGISTERS AND FLASH MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers exit1-IR state. If TMS is low on the rising edge of TCK, the controller enters the shift-IR state. Shift-IR: In this state, the shift register in the instruction register connects between TDI and TDO and shifts data one stage for every rising edge of TCK toward the TDO serial output while TMS is low. The parallel outputs of the instruction register as well as all test data registers remain at the previous states. A rising edge on TCK with TMS high moves the controller to the exit1-IR state. A rising edge on TCK with TMS low keeps the controller in the shift-IR state while moving data one stage through the instruction shift register. Exit1-IR: A rising edge on TCK with TMS low puts the controller in the pause-IR state. If TMS is high on the rising edge of TCK, the controller enters the update-IR state. Pause-IR: Shifting of the instruction shift register halts temporarily. With TMS high, a rising edge on TCK puts the controller in the exit2-IR state. The controller remains in the pause-IR state if TMS is low during a rising edge on TCK. Exit2-IR: A rising edge on TCK with TMS high puts the controller in the update-IR state. The controller loops back to shift-IR if TMS is low during a rising edge of TCK in this state. Update-IR: The instruction code that has been shifted into the instruction shift register latches to the parallel outputs of the instruction register on the falling edge of TCK as the controller enters this state. Once latched, this instruction becomes the current instruction. A rising edge on TCK with TMS low puts the controller in the runtest/idle state. With TMS high, the controller enters the select-DR-scan state. Instruction Register The instruction register contains a shift register as well as a latched 5-bit wide parallel output. When the TAP controller enters the shift-IR state, the instruction shift register connects between TDI and TDO. While in the shift-IR state, a rising edge on TCK with TMS low shifts the data one stage toward the serial output at TDO. A rising edge on TCK in the exit1-IR state or the exit2-IR state with TMS high moves the controller to the update-IR state. The falling edge of that same TCK latches the data in the instruction shift register to the instruction register parallel output. Table 30 shows the instructions supported by the MAX16065/MAX16066 and the respective operational binary codes. BYPASS: When the BYPASS instruction is latched into the instruction register, TDI connects to TDO through the 1-bit bypass test data register. This allows data to pass from TDI to TDO without affecting the device’s operation. IDCODE: When the IDCODE instruction is latched into the parallel instruction register, the identification data register is selected. The device identification code is loaded into the identification data register on the rising edge of TCK following entry into the capture-DR state. Shift-DR can be used to shift the identification code out serially through TDO. During test-logic-reset, the IDCODE instruction is forced into the instruction register. The identification code always has a ‘1’ in the LSB position. The next 11 bits identify the manufacturer’s JEDEC number and number of continuation bytes followed by 16 bits for the device and 4 bits for the version. See Table 31. USERCODE: When the USERCODE instruction latches into the parallel instruction register, the user-code data register is selected. The device user-code loads into the user-code data register on the rising edge of TCK following entry into the capture-DR state. Shift-DR can be used to shift the user-code out serially through TDO. See Table 32. This instruction can be used to help identify multiple MAX16065/MAX16066 devices connected in a JTAG chain. LOAD ADDRESS: This is an extension to the standard IEEE 1149.1 instruction set to support access to the memory in the MAX16065/MAX16066. When the LOAD ADDRESS instruction latches into the instruction register, TDI connects to TDO through the 8-bit memory address test data register during the shift-DR state. READ DATA: This is an extension to the standard IEEE 1149.1 instruction set to support access to the memory in the MAX16065/MAX16066. When the READ instruction latches into the instruction register, TDI connects to TDO through the 8-bit memory read test data register during the shift-DR state. WRITE DATA: This is an extension to the standard IEEE 1149.1 instruction set to support access to the memory in the MAX16065/MAX16066. When the WRITE instruction latches into the instruction register, TDI connects to TDO through the 8-bit memory write test data register during the shift-DR state. REBOOT: This is an extension to the standard IEEE 1149.1 instruction set to initiate a software-controlled reset to the MAX16065/MAX16066. When the REBOOT instruction latches into the instruction register, the MAX16065/MAX16066 resets and immediately begins the boot-up sequence. 48 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers TEST-LOGIC-RESET 0 RUN-TEST/IDLE MAX16065/MAX16066 1 0 1 SELECT-DR-SCAN 1 SELECT-IR-SCAN 0 1 0 1 CAPTURE-DR CAPTURE-IR 0 0 SHIFT-DR 1 1 1 1 EXIT1-IR 0 0 PAUSE-DR PAUSE-IR 0 1 0 1 0 EXIT2-DR EXIT2-IR 1 1 UPDATE-DR 1 0 SHIFT-IR 0 EXIT1-DR 0 1 UPDATE-IR 1 0 0 Figure 16. Tap Controller State Diagram Table 30. JTAG Instruction Set INSTRUCTION CODE NOTES BYPASS 0x1F Mandatory instruction code IDCODE 0x00 Load manufacturer ID code/part number USERCODE 0x03 Load user code LOAD ADDRESS 0x04 Load address register content READ DATA 0x05 Read data pointed by current address WRITE DATA 0x06 Write data pointed by current address REBOOT 0x07 Reboot FLASH data content into register file SAVE 0x08 Trigger emergency save to flash SETFLSHADD 0x09 Flash page access ON RSTFLSHADD 0x0A Flash page access OFF SETUSRFLSH 0x0B User flash access ON (must be in flash page already) RSTUSRFLSH 0x0C User flash access OFF (return to flash page) Table 31. 32-Bit Identification Code MSB LSB Version (4 bits) Part number (16 bits) Manufacturer (11 bits) Fixed value (1 bit) 0001 1000000000000001 00011001011 1 ______________________________________________________________________________________ 49 MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Table 32. 32-Bit User-Code Data MSB LSB Don’t Care 00000000000000000 SMBus slave id See Table 27 SAVE: This is an extension to the standard IEEE 1149.1 instruction set that triggers a fault log. The current ADC conversion results along with fault information are saved to flash depending on the configuration of the Critical Fault Log Control register (r6Dh). SETFLSHADD: This is an extension to the standard IEEE 1149.1 instruction set that allows access to the flash page. Flash registers include ADC conversion results, DACOUT enables, and GPIO_ input/output data. Use this page to access registers 200h to 2FFh RSTFLSHADD: This is an extension to the standard IEEE 1149.1 instruction set. Use RSTFLSHADD to return to the default page and disable access to the flash page. SETUSRFLSH: This is an extension to the standard IEEE 1149.1 instruction set that allows access to the user flash page. When on the configuration flash page, send the SETUSRFLSH command, all addresses are recognized as flash addresses only. Use this page to access registers 300h to 3FFh. RSTUSRFLSH: This is an extension to the standard IEEE 1149.1 instruction set. Use RSTUSRFLSH to return to the configuration flash page and disable access to the user flash. Restrictions When Writing to Flash Flash must be written to 8 bytes at a time. The initial address must be aligned to 8-byte boundaries—the 3 LSBs of the initial address must be ‘000’. Write the 8 bytes using eight successive Write Data commands. Applications Information Unprogrammed Device Behavior When the flash has not been programmed using the JTAG or SMBus interface, the default configuration of the EN_OUT_ outputs is open-drain active-low. This means that the EN_OUT_ outputs are high impedance. When it is necessary to hold an EN_OUT_ high or low to prevent premature startup of a power supply before the flash is programmed, connect a resistor from EN_OUT_ to ground or the supply voltage. Avoid connecting a resistor to ground when the output is to be configured as open-drain with a separate pullup resistor. User ID (r8A[7:0]) Device Behavior at Power-Up When VCC is ramped from 0, the RESET output is high impedance until VCC reaches 1.4V, at which point RESET goes low. All other outputs are high impedance until VCC reaches 2.7V, when the flash contents are copied into register memory. This takes 150Fs (max), after which the outputs assume their programmed states. Programming the MAX16065/MAX16066 in Circuit The MAX16065/MAX16066 can be programmed in the application circuit by taking into account the following points during circuit design: U The MAX16065/MAX16066 needs to be powered from an intermediate voltage bus or auxiliary voltage supply so programming can occur even when the board’s power supplies are off. This could also be achieved by using ORing diodes so that power can be provided through the programming connector. U The SMBus or JTAG bus lines should not connect through a bus multiplexer powered from a voltage rail controlled by the MAX16065/MAX16066. If the device needs to be controlled by an on-board FP, consider connecting the FP to one bus (such as SMBus) and use the other bus for in-circuit programming. U An unprogrammed MAX16065/MAX16066’s EN_OUT_s go high impedance. Ensure that this does not cause undesired circuit behavior. If necessary, connect pulldown resistors to prevent power supplies from turning on. Maintaining Power During a Fault Condition Power to the MAX16065/MAX16066 must be maintained for a specific period of time to ensure a successful flash fault log operation during a fault that removes power to the circuit. Table 33 shows the amount of time required depends on the settings in the fault control register (r6Dh[1:0]). Maintain power for shutdown during fault conditions in applications where the always-on power supply cannot be relied upon by placing a diode and a large capacitor between the voltage source, VIN, and VCC (Figure 17). The capacitor value depends on VIN and the time delay 50 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers R6Dh[1:0] VALUE MAXIMUM WRITE TIME (ms) DESCRIPTION 00 Save flags and ADC readings 244 01 Save flags 77 10 Save ADC readings 153 11 Do not save anything VIN VOUT R MON_ EN_OUT_ — MAX16065 MAX16066 VIN VCC C MAX16065 MAX16066 GND Figure 17. Power Circuit for Shutdown During Fault Conditions required, tFAULT_SAVE. Use the following formula to calculate the capacitor size: C = (tFAULT_SAVE x ICC(MAX))/(VIN - VDIODE - VUVLO) where the capacitance is in Farads and tFAULT_SAVE is in seconds, ICC(MAX) is 14mA, VDIODE is the voltage drop across the diode, and VUVLO is 2.7V. For example, with a VIN of 14V, a diode drop of 0.7V, and a tFAULT_SAVE of 153ms, the minimum required capacitance is 202FF. Driving High-Side MOSFET Switches Up to eight of the programmable outputs (EN_OUT1– EN_OUT8) of the MAX16065/MAX16066 can be configured as charge-pump outputs to drive the gates of seriespass n-channel MOSFETS. When driving MOSFETs, these outputs act as simple power switches to turn on the voltage supply rails. Approximate the slew rate, SR, using the following formula: SR = ICP/(CGATE + CEXT) where ICP is the 4FA (typ) charge-pump source current, CGATE is the gate capacitance of the MOSFET, and CEXT is the capacitance connected from the gate to ground. If more than eight series-pass MOSFETs are required for an application, additional series-pass p-channel MOSFETS can be connected to outputs configured as Figure 18. Connection for a p-Channel Series-Pass MOSFET active-low open drain (Figure 18). Connect a pullup resistor from the gate to the source of the MOSFET, and ensure the absolute maximum ratings of the MAX16065/ MAX16066 are not exceeded. Configuring the Device An evaluation kit and a graphical user interface (GUI) is available to create a custom configuration for the device. Refer to the MAX16065/MAX16066 Evaluation Kit for configuration. Cascading Multiple MAX16065/MAX16066s Multiple MAX16065/MAX16066s can be cascaded to increase the number of rails controlled for sequencing and monitoring. There are many ways to cascade the devices depending on the desired behavior. In general, there are several techniques: U Configure a GPIO_ on each device to be EXTFAULT (open drain). Externally wire them together with a single pullup resistor. Set register bits r72h[5] and r6Dh[2] to ‘1’ so that all faults will propagate between devices. If a critical fault occurs on one device, EXTFAULT will assert, triggering the nonvolatile fault logger in all cascaded devices and recording a snapshot of all system voltages. UConnect open-drain RESET outputs together to obtain a master system reset signal. UConnect all EN inputs together for a master enable signal. Since the internal timings of each cascaded device are not synchronized, EN_OUT_s placed in the same ______________________________________________________________________________________ 51 MAX16065/MAX16066 Table 33. Maximum Write Time MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Figure 19. Graphical User Interface Screenshot slot on different devices will not come up in the desired order even if the sequence delays are identical. UConsider using an external FP to control the EN inputs or the software enable bits of cascaded devices, monitoring the RESET outputs as a power-good signal. UFor a large number of voltage rails, the MAX16065/ MAX16066s can be cascaded hierarchically by using one master device’s EN_OUT_s to control the EN inputs of several slave devices. Controlling Power Supplies Without Using the Sequencer A FP may control power supplies manually without involving the sequencing slot system by controlling EN_OUT_s configured as GPIO_. The output of a power supply controlled this way can be monitored using a MON_ input configured as “Monitoring Only(Primary Sequence)” or “Monitoring Only(Secondary Sequence)” (see the Monitoring Inputs while Sequencing section). To monitor the supply for critical faults, the FP will need to manually set the critical fault enable bit in r6Eh to r72h after turning on the EN_OUT_, and manually clear the critical fault enable bit before turning off the EN_OUT_. Monitoring Current Using the Differential Inputs The MAX16065/MAX16066 can monitor up to seven currents using the dedicated current-sense amplifier as well as up to six pairs of inputs configured in differential mode. The accuracy of the differential pairs is limited by the voltage range and the 10-bit conversions. Each input pair uses an odd-numbered MON_ input in combination with an even-numbered MON_ input to monitor both the voltage from the odd-numbered MON_ to ground and the voltage difference between the two MON_ inputs. 52 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Figure 20 shows how to connect a current-sense resistor to a pair of MON_ inputs for monitoring both current and voltage. For best accuracy, set the voltage range on the evennumbered MON_ to 1.4V. Since the ADC conversion results are 10 bits, the monitoring precision is 1.4/1024 = 1.4mV. For more accurate current measurements, use larger current-sense resistors. The application requirements should determine the balance between accuracy and voltage drop across the current-sense resistor. Layout and Bypassing RS POWER SUPPLY MONODD ILOAD MONEVEN MAX16065 MAX16066 Figure 20. Current Monitoring Connection Bypass DBP and ABP each with a 1FF ceramic capacitor to GND. Bypass VCC with a 10FF capacitor to ground. Avoid routing digital return currents through a sensitive analog area, such as an analog supply input return path or ABP’s bypass capacitor ground connection. Use dedicated analog and digital ground planes. Connect the capacitors as close as possible to the device. ______________________________________________________________________________________ 53 MAX16065/MAX16066 This way a single pair of inputs can monitor the voltage and the current of a power-supply rail. The overvoltage threshold on the even-numbered MON_ inputs can be used as an overcurrent flag. MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Register Map FLASH ADDRESS REGISTER ADDRESS READ/ WRITE DESCRIPTION ADC VALUES, FAULT REGISTERS, GPIO_s AS INPUT PORTS—NOT IN FLASH — 000 R MON1 ADC output, MSBs — 001 R MON1 ADC output, LSBs — 002 R MON2 ADC output, MSBs — 003 R MON2 ADC output, LSBs — 004 R MON3 ADC output, MSBs — 005 R MON3 ADC output, LSBs — 006 R MON4 ADC output, MSBs — 007 R MON4 ADC output, LSBs — 008 R MON5 ADC output, MSBs — 009 R MON5 ADC output, LSBs — 00A R MON6 ADC output, MSBs — 00B R MON6 ADC output, LSBs — 00C R MON7 ADC output, MSBs — 00D R MON7 ADC output, LSBs — 00E R MON8 ADC output, MSBs — 00F R MON8 ADC output, LSBs — 010 R MON9 ADC output, MSBs — 011 R MON9 ADC output, LSBs — 012 R MON10 ADC output, MSBs — 013 R MON10 ADC output, LSBs — 014 R MON11 ADC output, MSBs — 015 R MON11 ADC output, LSBs — 016 R MON12 ADC output, MSBs — 017 R MON12 ADC output, LSBs — 018 R Current-sense ADC output — 019 R CSP ADC output, MSBs — 01A R CSP ADC output, LSBs — 01B R/W Fault register—failed line flags — 01C R/W Fault register—failed line flags/overcurrent — 01D R Failing slot during secondary sequence — 01E R GPIO data in (read only) — 01F R EN_OUT_ as GPIO data in (read only) — 020 R/W — 021 R Flash status/reset output monitor Current state of the FSM 54 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers FLASH ADDRESS REGISTER ADDRESS READ/ WRITE DESCRIPTION GPIO AND OUTPUT DEPENDENCIES/CONFIGURATIONS 230 030 R/W OUT configuration 231 031 R/W OUT configuration 232 032 R/W OUT configuration 233 033 R/W Charge-pump configuration, bits 234 034 R/W EN_OUT_ as GPIO data out 235 035 R/W SMBALERT pin configuration 236 036 R/W Fault1 dependencies 237 037 R/W Fault1 dependencies 238 038 R/W Fault2 dependencies 239 039 R/W Fault2 dependencies 23A 03A R/W Fault1/Fault2 secondary overcurrent dependencies 23B 03B R/W RESET output configuration 23C 03C R/W RESET output dependencies 23D 03D R/W RESET output dependencies 23E 03E R/W GPIO data out 23F 03F R/W GPIO configuration 240 040 R/W GPIO configuration 241 041 R/W GPIO configuration 242 042 R/W GPIO push-pull/open drain ADC—CONVERSIONS 243 043 R/W ADCs voltage ranges—MON_ monitoring 244 044 R/W ADCs voltage ranges—MON_ monitoring 245 045 R/W ADCs voltage ranges—MON_ monitoring 246 046 R/W Differential pairs enables 247 047 R/W Current-sense gain-setting (CSP, HV, or LV) 048 R/W MON1 secondary selectable UV/OV INPUT THRESHOLDS 248 249 049 R/W MON1 primary OV 24A 04A R/W MON1 primary UV 24B 04B R/W MON2 secondary selectable UV/OV 24C 04C R/W MON2 primary OV 24D 04D R/W MON2 primary UV 24E 04E R/W MON3 secondary selectable UV/OV 24F 04F R/W MON3 primary OV 250 050 R/W MON3 primary UV 251 051 R/W MON4 secondary selectable UV/OV 252 052 R/W MON4 primary OV 253 053 R/W MON4 primary UV ______________________________________________________________________________________ 55 MAX16065/MAX16066 Register Map (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Register Map (continued) FLASH ADDRESS REGISTER ADDRESS READ/ WRITE 254 054 R/W MON5 secondary selectable UV/OV 255 055 R/W MON5 primary OV 256 056 R/W MON5 primary UV 257 057 R/W MON6 secondary selectable UV/OV 258 058 R/W MON6 primary OV 259 059 R/W MON6 primary UV 25A 05A R/W MON7 secondary selectable UV/OV DESCRIPTION 25B 05B R/W MON7 primary OV 25C 05C R/W MON7 primary UV 25D 05D R/W MON8 secondary selectable UV/OV 25E 05E R/W MON8 primary OV 25F 05F R/W MON8 primary UV 260 060 R/W MON9 secondary selectable UV/OV 261 061 R/W MON9 primary OV 262 062 R/W MON9 primary UV 263 063 R/W MON10 secondary selectable UV/OV 264 064 R/W MON10 primary OV 265 065 R/W MON10 primary UV 266 066 R/W MON11 secondary selectable UV/OV 267 067 R/W MON11 primary OV 268 068 R/W MON11 primary UV 269 069 R/W MON12 secondary selectable UV/OV 26A 06A R/W MON12 primary OV 26B 06B R/W MON12 primary UV 26C 06C R/W Secondary overcurrent threshold 26D 06D R/W 26E 06E R/W Save after EXTFAULT fault control Faults causing store in flash 26F 06F R/W Faults causing store in flash 270 070 R/W Faults causing store in flash 271 071 R/W Faults causing store in flash 272 072 R/W Faults causing store in flash 273 073 R/W Overcurrent debounce, watchdog mode, secondary threshold type, software enables 274 074 R/W ADC fault deglitch/autoretry configuration 275 075 R/W WDI toggle, power-up fault timer, reverse sequence 276 076 R/W Watchdog reset output enable, watchdog timers 277 077 R/W Sequence delay for Slot 0 and Slot 1 FAULT SETUP TIMEOUTS 56 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers FLASH ADDRESS REGISTER ADDRESS READ/ WRITE 278 078 R/W Sequence delay for Slot 2 and Slot 3 279 079 R/W Sequence delay for Slot 4 and Slot 5 27A 07A R/W Sequence delay for Slot 6 and Slot 7 27B 07B R/W Sequence delay for Slot 8 and Slot 9 27C 07C R/W Sequence delay for Slot 10 and Slot 11 27D 07D R/W Primary sequence final slot, sequence delay for Slot 12 27E 07E R/W MON1/MON2 slot assignment 27F 07F R/W MON3/MON4 slot assignment 280 080 R/W MON5/MON6 slot assignment 281 081 R/W MON7/MON8 slot assignment 282 082 R/W MON9/MON10 slot assignment 283 083 R/W MON11/MON12 slot assignment 284 084 R/W EN_OUT1/EN_OUT2 slot assignment 285 085 R/W EN_OUT3/EN_OUT4 slot assignment 286 086 R/W EN_OUT5/EN_OUT6 slot assignment 287 087 R/W EN_OUT7/EN_OUT8 slot assignment 288 088 R/W EN_OUT9/EN_OUT10 slot assignment 289 089 R/W EN_OUT11/EN_OUT12 slot assignment 28A 08A R/W Customer use (version) 28B 08B R/W PEC enable/SMBus address 28C 08C R/W Lock bits 28D 08D R DESCRIPTION MISCELLANEOUS NONVOLATILE FAULT LOG — 200 201 202 203 204 205 206 207 208 209 20A 20B 20C 20D 20E 20F R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W — R/W Revision code Sequence state Fault flags, MON1–MON8 Fault flags, MON9–MON12, OC, EXTFAULT MON1 ADC output MON2 ADC output MON3 ADC output MON4 ADC output MON5 ADC output MON6 ADC output MON7 ADC output MON8 ADC output MON9 ADC output MON10 ADC output MON11ADC output MON12 ADC output Current-sense ADC output ______________________________________________________________________________________ 57 MAX16065/MAX16066 Register Map (continued) MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers Register Map (continued) USER FLASH 300 39F R/W User flash 3A0 3AF — Reserved 3B0 3FF R/W User flash Typical Operating Circuits VSUPPLY +3.3V OUT IN DC-DC GND VCC MON1 MAX16065 MAX16066 OUT IN MON2–MON11 DC-DC SCL SDA GND OUT IN µC MON12 RESET RESET FAULT INT WDI I/O WDO INT DC-DC GND AO GND 58 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers VSUPPLY +3.3V OUT IN DC-DC GND MON1 VCC MON2 LOAD OUT IN µC MAX16065 MAX16066 SDA MONODD DC-DC GND MONEVEN LOAD OUT IN SCL RESET RESET FAULT INT WDI I/O WDO INT MON11 DC-DC GND AO MON12 LOAD GND NOTE: MONODD = MON1, MON3, MON5, MON7, MON9, MON11 MONEVEN = MON2, MON4, MON6, MON8, MON10, MON12 ______________________________________________________________________________________ 59 MAX16065/MAX16066 Typical Operating Circuits (continued) GPIO6 EN_OUT12 EN_OUT11 EN_OUT10 EN_OUT9 EN_OUT8 EN_OUT7 EN_OUT6 EN_OUT5 EN_OUT4 TOP VIEW EN_OUT3 EN_OUT2 Pin Configurations 36 35 34 33 32 31 30 29 28 27 26 25 EN_OUT1 37 24 GPIO5 EN 38 23 GPIO4 DBP 39 22 GPIO3 VCC 40 21 GPIO2 ABP 41 20 GPIO1 GND 42 19 GPIO8 MON7 43 18 GPIO7 MON8 44 17 GND MON9 45 16 SCL MON10 46 15 AO 14 SDA 13 TDO 9 10 11 12 TDI 8 TCK 7 TMS 6 RESET MON4 5 CSM 4 CSP 3 MON6 2 MON5 1 MON3 48 MON2 47 MON12 *EP + MON1 MON11 MAX16065 GPIO5 GPIO6 EN_OUT8 EN_OUT7 EN_OUT6 EN_OUT5 EN_OUT4 EN_OUT3 EN_OUT2 TOP VIEW EN_OUT1 THIN QFN (7mm x 7mm) 30 29 28 27 26 25 24 23 22 21 EN 31 20 GPIO4 DBP 32 19 GPIO3 VCC 33 18 GPIO2 ABP 34 17 GPIO1 16 GND GND 35 MAX16066 MON7 36 15 SCL 14 AO MON8 37 MON9 38 13 SDA *EP + MON10 39 12 TDO 11 TCK 5 6 7 8 9 10 CSM RESET TMS TDI MON4 4 CSP 3 MON6 2 MON5 1 MON3 MON1 40 MON2 MAX16065/MAX16066 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers THIN QFN (6mm x 6mm) 60 ������������������������������������������������������������������������������������� 12-Channel/8-Channel, Flash-Configurable System Managers with Nonvolatile Fault Registers PROCESS: BiCMOS Package Information For the latest package outline information and land patterns, go to www.maxim-ic.com/packages. PACKAGE TYPE PACKAGE CODE DOCUMENT NO. 48 TQFN-EP* T4877-6 21-0144 40 TQFN-EP* T4066-5 21-0141 Maxim cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim product. No circuit patent licenses are implied. Maxim reserves the right to change the circuitry and specifications without notice at any time. Maxim Integrated Products, 120 San Gabriel Drive, Sunnyvale, CA 94086 408-737-7600 © 2009 Maxim Integrated Products 61 Maxim is a registered trademark of Maxim Integrated Products, Inc. MAX16065/MAX16066 Chip Information