MA-COM 12FC10

CORCOM Product Guide
Single Phase External Power Line Filter for Frequency Converters
FC Series
UL Recognized
FC10
FC Series
Specifications
The FC filters provide filtering for frequency inverters and
variable speed motor drives. Designed for very noisy
applications, they attenuate conducted interference at low
and high frequency ranges and protect programmable
logic controllers from RF noise on the AC power line. These
filters perform best when installed on the line side of the
motor drive. The FC filters better prevent noise from
returning to the line, enabling equipment to meet strict
European regulations on RFI.
Suited for field wiring applications, these filters are ideal for
EMC troubleshooting and field refurbishing. The FC filters
feature side flanges for easy mounting and DIN type
terminals which eliminate live metal parts, allowing safer
and easier connection. The filters could also be sold as an
accessory to motor drives marketed into Europe.
Electrical Schematics
6 & 12 Amps
Maximum leakage current,each line-to-ground
@ 120 VAC 60 Hz:
@ 250 VAC 50 Hz:
Hipot rating (one minute):
line-to-ground
line-to-line
Operating frequency:
3.8 mA
6.7 mA
2250 VDC
1450 VDC
50/60 Hz
Rated voltage (max.):
250 VAC
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current
Rating
.01
06A
12A
16A
25A
36A
9
5
4
2
0
.03 .05
19
17
15
14
6
26
25
22
22
14
Frequency–MHz
.1
.5
1
5
10
30
50
65
70
70
70
40
60
70
70
70
35
35
35
48
50
Frequency–MHz
.1
.5
1
5
10
30
50
70
70
70
70
45
45
45
50
50
37
37
36
36
27
65
65
65
75
68
65
65
65
75
75
Line-to-line in 50 ohm circuit
LINE
LOAD
16, 25 & 36 Amps
Current
Rating
.01
.03 .05
06A
12A
16A
25A
36A
10
14
14
14
14
10
14
14
14
14
35
30
29
17
17
60
51
55
42
42
75
75
75
75
75
75
75
75
75
75
60
75
75
70
70
LOAD
LINE
Resistor location for reference only.
58
Catalog 1654001
Revised 05-07
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
Germany:
49-89-6089-0
www.corcom.com
www.tycoelectronics.com
CORCOM Product Guide
Single Phase External Power Line Filter for Frequency Converters (Continued)
FC Series
Case Dimensions
6, 12, 16FC10
A
Part No. (max)
Hole: .203 x .156
5.16 x 3.96 (4)
LINE
LOAD
B
C
This hole indicates the "Line"
side and may be on either flange.
D
F
E
A
B
(max)
C
(max)
D
± .020
± .51
E
(max)
RFI Power Line Filters
Case Styles
F
± .010
± .254
6FC10
4.60
116.8
3.10
78.7
1.78
45.21
2.677
67.8
3.70
94.0
2.00
50.8
12FC10
5.95
151.3
3.96
100.6
2.18
55.4
3.50
88.9
4.53
114.8
2.00
50.8
16FC10
5.95
151.3
3.96
100.6
2.18
55.4
3.50
88.9
4.53
114.8
2.00
50.8
25FC10
6.90
175.3
5.48
139.2
2.55
64.77
4.90
124.5
5.94
150.9
2.756
70.0
36FC10
6.90
175.3
5.48
139.2
2.55
64.77
4.90
124.5
5.94
150.9
2.756
70.0
8-32 Screws (2)
6FC10, 12FC10, 16FC10
Phoenix contact VDFK4
Accepts 10 AWG solid wire, 12 AWG stranded wire
Torque Spec: 5.5 - 7.0 in.lb
Part Numbers
06FC10
12FC10
16FC10
25, 36FC10
This hole indicates the "Line" side
and may be on either flange.
25FC10
36FC10
Slots: .260 x .156
6.60 x 3.96 (4)
D
B
C
F
E
A
8-32 Screws (2)
25FC10, 36FC10
Phoenix contact VDFK6
Accepts 8 AWG solid wire, 10 AWG stranded wire
Torque Spec: 13.5 - 16 in.lb
59
Catalog 1654001
Revised 05-07
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
Germany:
49-89-6089-0
www.corcom.com
www.tycoelectronics.com