Velociti® Series ATD-L2F, ATD-RL2F

Velociti® Series
ATD-L2F, ATD-RL2F
Description
Addressable Thermal Sensor
The Gamewell-FCI Velociti® Series, addressable plug-in
thermal sensors with integral communication provide features that surpass conventional sensors. Point ID capability allows each sensor’s address to be set, providing exact
locations for pinpointing alarm locations and for selective
maintenance. ATD thermal sensors use an innovative
thermistor sensing circuit to produce 135°F/57°C fixedtemperature (ATD-L2F). The ATD-RL2F provides a combination 15°/minute rate-of-rise with 135° fixed thermal
detection that is included in a low-profile package. The
ATD-HL2F provides fixed high-temperature detection at
190°F/88°C. These thermal sensors provide cost-effective,
addressable property protection in a variety of applications.
ATD-L2F
The Velociti® Series uses a communication protocol that
substantially increases the speed of communication
between the sensors and Gamewell-FCI analog addressable fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and identifies the single device with the status change.
The net effect is response speed up to five times greater
than earlier designs.
Features
• Sleek, low-profile design
• Visual rotary switch addressing
• Built-in functional test switch activated by an external
magnet
Installation
• Bicolor LEDs flash green whenever the sensor is
ATD plug-in sensors use a separate base to simplify installation, service, and maintenance. A special tool allows
maintenance personnel to plug-in and remove sensors
without using a ladder.
• Optional relay, isolator, or sounder bases
Mount the base on a box which is at least 1.5" (3.8 cm)
deep. Suitable mounting base boxes include:
• 4.0" (10.2 cm) square box.
• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.
• Single-gang box (except relay or isolator base).
• With B200S or B200SR base, mounted on a 4.0"
(10.2 cm) octagonal or square box.
• With B224RB or B224BI base, mounted on a 3.5" (8.9
cm) octagonal box, or a 4.0" (10.2 cm) octagonal or
square box.
NOTE: Because of the inherent supervision provided by
the SLC, end-of-line resistors are not required. Wiring “Ttaps” or branches are permitted for Style 4 (Class “B”)
wiring.
addressed, and light steadily red on alarm*
• Low standby current
• Addressable communication
• Stable communication technique with noise immunity
• Optional remote, single-gang LED accessory
(RA-100Z)
• Suitable for installation in ducts
Note: *Only the red LED is operative in panels that do not operate
in Velociti® mode.
Velociti® and E3 Series® are registered trademarks of Honeywell
International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
ULC® is a registered trademark of Underwriters Laboratories Canada Inc.
An ISO 9001-2000 Company
SIGNALING
FM
APPROVED
S2332
MEA
Approved
3023594 219-02-E Vol.VI 7270-1703:0115
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0620 Rev. E page 1 of 2
©2011 by Honeywell International Inc. All rights reserved.
Specifications
ATD-L2F/ATD-RL2F
Dimensions:
Shipping Weight:
Operating
Temperature:
ATD-L2F or
ATD-RL2F
ATD-HL2
Sensor Spacing:
Relative Humidity:
ATD-L2F
ATD-RL2F
ATD-HL2F
Specifications
2.1" (5.3 cm) Height
4.1" (10.4 cm) diameter installed in
the B501 base
6.1" (15.5 cm) diameter installed in
the B210LP base
4.8 oz. (137 g)
–4° F to 100° F (–20° C to 38°C)
–4° F to 150°F (–20 C to 66°C)
UL® approved for 50 ft. (15.2 m)
center to center
FM approved for 25 x 25 ft.
(7.6 x 7.6 m) spacing
10 – 93% (non-condensing)
Fixed-temperature setpoint
135°F (57°C)
Combination 135° F fixed
temperature and 15° F(8.3°c)/per
minute rate-of-rise°
Fixed-temperature setpoint
190°F (88°C)
Bases and Options
B501
Dimensions:
B210LP
Dimensions:
B210LPBP
Dimensions:
B224RB
Dimensions:
B224BI
Dimensions:
B200S
Dimensions:
B200SR
Dimensions:
RA-100Z
BCK-200
Electrical Specifications
Voltage Range:
15 - 32 Volts DC peak
Standby Current: 200 mA @ 24 VDC
(without communication)
(max. avg.)
.0003 A @ 24 VDC
(one communication every 5 seconds
with LED blink enabled)
LED Current
(max.)
.0065 A @ 24 VDC (LED lit)
Plug-in sensor base without flange
4.1” (10.4 cm) diameter
Flanged mounting base
6.1” (15.5 cm) diameter
Flanged mounting base bulk pack
6.1” (15.5 cm) diameter
Plug-in sensor base with auxiliary relay,
SPDT
2 coil latching relay 1 Form C contact UL/
CSA Rating:
0.9 A @ 125 VAC (inductive)
0.9 @ 110 VDC (inductive)
3.A @ 30 VDC (resistive)
6.1” (15.5 cm) diameter
Plug-in sensor isolator base for Style 7
operation
6.1” (15.5 cm) diameter
Maximum 25 devices between isolator
bases
Intelligent sensor sounder base
6.875” (17.5 cm) diameter
Standard sounder base, UL 864 9th
Edition compliant, ULC Listed
6.875” (17.5 cm) diameter
Remote LED Annunciator
Black detector covers (box of 10)
Ordering Information
Part Number Description
ATD-L2F
ATD-RL2F
ATD-HL2F
Addressable thermal sensor, fixed, 135° F
Addressable thermal sensor, combination
fixed,135° F and 15°/minute rate-of-rise.
Addressable thermal sensor, fixed, 190° F
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0620 Rev. E page 2 of 2
www.gamewell-fci.com