Velociti® Series B200S

Velociti® Series
B200S
Intelligent Addressable
Sensor Sounder Base
Description
•
The B200S Velociti® sounder base sets a new standard for
performance, installation, and aesthetics. It is an addressable sounder base that requires a unique, separate
sounder base address. This sounder base is available in
only Velociti protocol. The B200S is designed for new and
existing dwelling unit applications. It offers maximum flexibility in installation, configuration, and operation to meet or
exceed the UL® Standard 268 and UL® Standard 464
requirements.
One of the unique features of the B200S sounder base
offers the functionality “to capture” the communications
transmitted between the attached sensor head on the System Sensor signal line loop of the E3 Series® or S3 Series
fire alarm control panel. This new feature allows the E3
Series and S3 Series fire alarm control panels to use the
same address as the detector, but use a unique device
type on the loop. Using the CAMWorks™ Tool, the E3
Series and S3 Series control panels can then use that
same address to command and activate an individual
sounder or a group of sounders.
B200S
Features
•
•
•
•
In CAMWorks, you can program the command set from
the E3 Series or S3 Series control panel to a specific event
which allows you to select the volume, tone and group. In
addition, the E3 Series and S3 Series control panels generate synchronization pulses through the loop and enable
selectable tone patterns.
With its attractive aesthetics, the B200S is ideal to use for
applications where the appearance is critical. For example, the design eliminates unsightly surface-mount boxes
and the sounder base employs a separate mounting plate
that can be installed on various junction box sizes (see
Table 1). In addition, the mounting plate enables pre-wiring
of all connections to simplify the installation. To install the
housing, use the mounting plate, and secure two retaining
screws to lock-it in position. The retaining screws are covered by the installed sensor head for added tamper resistance.
•
•
•
•
•
•
•
Built-in supervision (no EOL relays required).
Complies with UL® Standard 268 and UL®
Standard 464.
Offers a programming option to control and activate the sounder base independently.
Programs the addressability for maximum configuration flexibility.
Broadcasts over two volume levels(75 or 85dBA).
Has multiple event-driven tone outputs and uses
custom tone capability.
Supports Continuous, ANSI Temporal 3, ANSI
Temporal 4, and March Time tones.
- Employs coded patterns that may be optionally
synchronized over the SLC and promptly
changed.
Synchronized with other System Sensor
notification devices.
Includes a pre-wire mounting plate that fits
various junction box sizes.
Uses a mechanical locking feature that prevents
the removal of the attached sensor head.
•
SIGNALING
FM
E3 Series® and Velociti® are registered trademarks and CAMWorks™
and Clip™ are trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
APPROVED
S1911
•
3035027
7135-1653:0213
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60671 Rev. C page 1 of 2
©2014 by Honeywell International Inc. All rights reserved.
•
•
•
Specifications
Ordering Information
Physical Specifications:
Base Diameter:
Base Height:
Shipping Weight:
Operating
Temperature Range:
Operating Humidity
Range:
6.875” (17.46 cm)
2.0” (5.08 cm) less sensor
0.50 lb. (227 gm)
Part Number
B200S
Description
Intelligent Addressable Sensor
Sounder Base
32° to 120° F (0° to 49° C)
10% to 93% relative humidity
(non-condensing)
Note: The B200S sounder base is compatible with the E3
Series and S3 Series fire alarm control panels.
•
Electrical Specifications:
External Supply
Voltage:
External Standby
Current:
Alarm Current:
16 to 33 VDC (VFWR)
500 µA maximum
35 mA maximum (high volume)
15 mA maximum (low volume)
SLC Operating Voltage: 15 to 32 VDC
SLC Standby Current: 300 µA maximum
Sound Output:
Greater than 85 dBA minimum –
measured in a UL reverberant
room at 10 ft. 24 Volts
(in continuous tone).
Installation Specifications:
Mounts directly to 4” (10.16 cm)
square, 4” (10.16 cm) octagon,
3 1/2” (8.9 cm) octagon, singlegang or double-gang junction
boxes.
Wire sizes up to 12 AWG.
Mounting:
Wire:
•
•
Table 1: B200S Junction Box Selection Guide
SingleGange
3.5”
Octagonal
4.0”
Octagonal
4.0”
Square
Yes
4.0” Square w/
3.0” mud ring
Yes
Yes
Yes
50 mm
60 mm
70 mm
75 mm
Yes
No
No
Yes
No
•
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60671 Rev. C page 2 of 2
www.gamewell-fci.com