Data Sheet: DNR / DNRW

Intelligent Non-Relay
Photoelectric Duct
Smoke Detector
The InnovairFlex™ Series are the only duct smoke
detectors flexible enough to fit configurations from
square to rectangular and everything in between.
Features
•Photoelectric, integrated low-flow technology
(detector head sold separately)
•Air velocity rating from 100 ft/min to 4,000 ft/min
•Adjusts to square and rectangular mounting configurations
•Broad ranges for operating temperature (−4°F to 158°F) and
humidity (0% to 95% non-condensing)
•Patented tool-free, plug-in sampling tubes
•New cover tamper signal
•Increased wiring space with a new ¾-inch conduit knockout
•Housing has space for mounting a relay module
•Easily accessible code wheels on sensor head (sold separately)
•Clear cover for convenient visual inspection
•UL 268A listed
•Remote testing capability
•Requires com line power only
•NEMA Type 4 UL listed for non-hazardous indoor and outdoor
applications (DNRW only)
•UV-resistant, UL-listed housing and cover material
(DNRW only)
The InnovairFlex Series DNR and DNRW are intelligent
(addressable) non-relay photoelectric duct smoke detectors.
Like all InnovairFlex detectors, the DNR and DNRW both feature
an adjustable housing design that fits square and rectangular
installation footprints, mounts to both round and rectangular
ductwork, and utilizes tool-free, plug-in sampling tubes for increased
application flexibility and installation ease.
These units sense smoke in challenging conditions, operating in
airflow speeds of 100 to 4,000 feet per minute, temperatures of −4°F
to 158°F, and a humidity range of 0 to 95 percent (non-condensing).
For even more extreme environments like rooftops, the DNRW’s
NEMA 4-rated watertight and UV-resistant housing protects against
windblown dirt and dust, rain, and hose directed water, enabling it
to be installed without a costly enclosure, saving time and money.
The InnovairFlex housing cover isolates the sensor head from the
low-flow feature for simple maintenance, and a cover tamper feature
initiates a trouble signal for a removed or improperly installed
sensor cover. The housing also provides a ¾-inch conduit knockout
and ample space to facilitate easy wiring and mounting of a relay
module to meet specific application requirements. These detectors
can be customized to meet local codes and specifications without
additional wiring.
The InnovairFlex line is compatible with all previous Innovair models,
including remote test accessories, for easy retrofits.
WARNING: Duct smoke detectors have specific limitations.
Agency Listings
2911
3029700
3242-1653:209/210
2125
InnovairFlex Duct Smoke Detector Specifications
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ DNR Intelligent Non-Relay Photoelectric Duct Smoke Detector and DNRW Watertight NEMA
4 Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke
detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m/sec to 20.32 m/sec). The
unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via
magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12–18
AWG wiring.
Physical Specifications
Size: (Rectangular)
(Square)
Weight:
Environmental Rating:
Operating Temperature Range:
Storage Temperature Range:
Operating Humidity Range:
Air Duct Velocity:
DCOIL (if included):
14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.6 cm) Depth
7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width ; 2.5 in (6.35 cm) Depth
1.6 lb (0.73 kg)
NEMA 4 (DNRW only)
–4°F to 158°F (–20°C to 70°C)
–22°F to 158°F (–30°C to 70° C)
0% to 95% relative humidity (non-condensing)
100 to 4,000 ft/min (0.5 to 20.32 m/s)
17.5 – 26.4 VDC, 95 mA max
Electrical Ratings
Please see detector head installation manual for electrical specifications
Accessory Current Loads at 24 VDC
Device
Standby
Alarm
RA100Z
0 mA
12 mA Max.
RTS151/RTS151KEY
0 mA
12 mA Max.
Installing the InnovairFlex Sampling Tube
The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing
the front or rear locking tab (front locking tab shown below right).
A05-0422-005
Wiring for Intelligent Non-Relay Duct Smoke Detector
System wiring diagram for DNR:
COMM.
LINE (+)
COMM.
LINE
COMM.
LINE (–)
1ST
DETECTOR
IN LOOP
UL/FM LISTED
CONTROL
PANEL
2ND
DETECTOR
IN LOOP
DNR to RA100Z:
+ RA
(+)
– RA
RA100Z
(-)
REMOTE ALARM LED
OPTION 1 PER UNIT
DNR to RTS151/RTS151KEY
with “R” Remote Test Capable Detector Head Option:
DNR to RTS151/RTS151KEY with DCOIL Option*:
TEST COIL +
TEST COIL –
COMM +
TEST COIL +
RTS151/RTS151KEY
COMM +
1
RA/RTS –
4
*
EXTERNAL
(-) POWER (+)
SUPPLY
1
5
2
3
OUT (CONV ONLY) +
OUT (CONV ONLY) +
COMM –
TEST COIL –
2
3
RA +
4
RTS +
5
COMM –
JUMPER
RTS151/RTS151KEY
REMOTE TEST STATION
RA/RTS –
RA +
LED OPTION
1 PER UNIT
RTS +
TEST COIL OPTION
1 PER UNIT
95 mA CURRENT DRAW
*Important Notes
•The use of either the RTS151 or RTS151KEY requires the installation
of an accessory coil, DCOIL, sold separately. Please refer to the DNR
or DNRW installation manual for more information.
•The RTS151/RTS151KEY test coil circuit requires an external 24 VDC
power supply which must be UL listed.
A05-0422-005
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different means of visible and
audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed.
RTS151 UL S2522
RTS151KEY UL S2522
RA100Z UL S2522
Ordering Information
Part No.
DNR
DNRW
Accessories
Description
Intelligent non-relay photoelectric low-flow duct smoke detector
Watertight intelligent non-relay photoelectric low-flow duct smoke detector
DCOIL
Remote test coil required with
RTS451/RTS451KEY/RTS151/RTS151KEY
Metal sampling tube duct width up to 1ft (0.3m)
Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m)
Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)
Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m)
End cap for metal sampling tubes
DST1
DST1.5
DST3
DST5
DST10
P48-21-00
ETX
Metal exhaust tube duct width 1ft (0.3 m)
M02-04-00
RA100Z
RTS151
RTS151KEY
DH400OE-1
Test magnet
Remote annunciator alarm LED
Remote test station
Remote test station with key lock
Weatherproof enclosure
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2010 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0422-005 • 9/10 • #2470