SYSTEMSENSOR DNRW

Intelligent Non-Relay
Photoelectric Duct
Smoke Detector
The InnovairFlex™ Series are the only duct smoke
detectors flexible enough to fit configurations from
square to rectangular and everything in between.
Features
•Photoelectric, integrated low-flow technology
•Air velocity rating from 100 ft/min to 4000ft/min (0.5m/s to 20.32m/sec)
•Versatile mounting options: square or rectangular configuration
•Broad ranges for operating temperature (-4F to 158F) and humidity
(0% to 95% non-condensing)
•Patented sampling tube installs from front or back of the detector
with no tools required
•New Cover tamper signal
•Increased wiring space with a newly added 3/4-inch conduit
knockout
•Available space within housing to accommodate mounting of relay
module
•Easily accessible code wheels on sensor head (sold separately)
•Clear cover for convenient visual inspection
•UL 268A listed
•Remote testing capability
•Requires com line power only
•NEMA Type 4 UL listed for non-hazardous indoor and outdoor
applications (DNRW only)
•UV Resistant, UL listed housing and cover material
(DNRW only)
The InnovairFlex DNR intelligent non-relay photoelectric duct
smoke detector and DNRW watertight non-relay photoelectric duct
smoke detector feature a pivoting housing that fits both square and
rectangular footprints capable of mounting to a round or
rectangular duct.
DNRW duct smoke detector, with its NEMA 4 rating, is listed as a
watertight enclosure providing protection against falling dirt, rain,
and windblown dust, splashing and hose directed water, allowing
operators to use the detector in the most extreme environments.
These units sense smoke in the most challenging conditions,
operating in airflow speeds of 100 to 4000 feet per minute,
temperatures of -4F to 158F, and a humidity range of 0 to 95 percent
(non-condensing).
An improved cover design isolates the sensor head from the lowflow feature for simple maintenance. A cover tamper feature was
added to indicate a trouble signal for a removed or improperly
installed sensor cover. The InnovairFlex housing provides a 3/4-inch
conduit knockout and ample space to facilitate easy wiring and
mounting of relay module.
The InnovairFlex duct smoke detector can be customized to meet
local codes and specifications without additional wiring. The new
InnovairFlex product line is compatible with all previous Innovair
models, including remote test accessories.
WARNING: Duct smoke detectors have specific limitations.
Agency Listings
2911
DUCT SMOKE DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional duct smoke detector
application information.
InnovairFlex Duct Smoke Detector Specifications
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ DNR Intelligent Non-Relay Photoelectric Duct Smoke Detector and DNRW Watertight
NEMA4 Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct
smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec).
The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing
via magnetic switch or remote testing using the RTS451KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12–18
AWG wiring.
Physical Specifications
Size: (Rectangular)
(Square)
Weight:
Environmental Rating:
Operating Temperature Range:
Storage Temperature Range:
Operating Humidity Range:
Air Duct Velocity:
14.38 in (37 cm) Length; 5in (12.7 cm) Width; 2.5 in (6..6 cm) Depth
7.75 in (19.7cm) Length; 9 in (22.9cm) Width ; 2.5 in (6.35cm) Depth
1.6 lb (0.73 kg)
NEMA4 (DNRW only)
–4°F to 158°F (–20°C to 70°C)
–22ºF to 158ºF (–30ºC to 70º C)
0% to 95% relative humidity (non-condensing)
100 to 4000 ft/min (0.5 to 20.32 m/s)
Electrical Ratings
Please see detector head installation manual for electrical specifications
Accessory Current Loads at 24 VDC
Device
Standby
Alarm
RA400Z
0 mA
12 mA Max.
RTS451/RTS451KEY
0 mA
12 mA Max.
Installing the InnovairFlex Sampling Tube
The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing
the front or rear locking tab (front locking tab shown below right).
A05-0422-000
Wiring for Intelligent Non-Relay Duct Smoke Detector
System wiring diagram for DNR:
COMM.
LINE (+)
COMM.
LINE
COMM.
LINE (–)
1ST
DETECTOR
IN LOOP
UL/FM LISTED
CONTROL
PANEL
2ND
DETECTOR
IN LOOP
DNR to RA400Z:
+ RA
– RA
(+)
RA400Z
(-)
REMOTE ALARM LED
OPTION 1 PER UNIT
DNR to RTS451/RTS451KEY:
TEST COIL +
TEST COIL –
COMM +
OUT (CONV ONLY) +
COMM –
4
*
EXTERNAL
(-) POWER (+)
SUPPLY
1
5
2
3
RTS451/RTS451KEY
REMOTE TEST STATION
RA/RTS –
RA +
LED OPTION
1 PER UNIT
RTS +
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
Important Notes:
•The use of either RTS451 or RTS451KEY requires the installation of an accessory coil, DCOIL, sold separately.
Please refer to the DNR or DNRW installation manual for more information
•The RTS451/RTS451KEY test coil circuit requires an external 24 VDC power supply which must be UL listed.
A05-0422-000
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different means of visible and
audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed.
RTS451 UL S2522
RTS451KEY UL S2522
RA400Z UL S2522
Ordering Information
Part No.
DNR
DNRW
Accessories
Description
Intelligent non-relay photoelectric low-flow duct smoke detector
Watertight intelligent non-relay photoelectric low-flow duct smoke detector
DCOIL
DST1
DST1.5
DST3
DST5
DST10
DH400OE-1
Remote test coil required with RTS451/RTS451KEY
Metal sampling tube duct width up to 1ft (0.3m)
Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m)
Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)
Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m)
Weatherproof enclosure
ETX
M02-04-00
P48-21-00
RA400Z
RTS451
RTS451KEY
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Metal exhaust tube duct width 1ft (0.3m)
Test magnet
End cap for metal sampling tubes
Remote annunciator alarm LED
Remote test station
Remote test station with key lock
©2008 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0422-000 • 7/08 • #1839