2-Wire Photoelectric Duct Smoke Detector

2-Wire Photoelectric
Duct Smoke Detector
The InnovairFlex™ Series are the only duct smoke
detectors flexible enough to fit configurations from
square to rectangular and everything in between.
Features
The InnovairFlex D2 2-wire photoelectric duct smoke detector
features a pivoting housing that fits various applications: both square
and rectangular footprints mount to round or rectangular duct work.
•Photoelectric, integrated low-flow technology
•Air velocity rating from 100 ft/min to 4,000 ft/min
(0.5 m/s to 20.32 m/sec)
•Versatile mounting options in square or rectangular configuration
with modular construction
•Plug-in sensor
•Superb false alarm immunity with the latest sensor technology
•Broader ranges for operating temperature (−4°F to 158°F) and
humidity (0% to 95% non-condensing)
•Patented sampling tube installs from front or back of the detector
with no tools required
•A cover tamper feature to indicate a trouble condition for removed
or improperly installed sensor cover
•Increased wiring space with a newly added ¾ inch conduit
knockout
•Improved LED status
•24 VDC
•Backward compatibility with existing Innovair products, including
remote accessories
This new duct smoke detector senses airflow speeds ranging
from 100 to 4,000 feet per minute with proven System Sensor
precision. The enhancements built into this model improve false
alarm immunity (with plug-in sensor head); broaden operating
temperature (−4°F to 158°F) and humidity (0 to 95 percent noncondensing) ranges; while simplifying installation and maintenance.
These advance features can detect smoke even in the harshest duct
applications.
The new design provides more wiring space with an added ¾ inch
conduit knockout. Numbers and labels for terminal designations are
consistent with previous Innovair models. The new sampling tube
can be clicked into position with one smooth motion from either the
front or the back of the detector.
The InnovairFlex D2 duct smoke detector has signals to indicate
trouble and maintenance conditions. Additionally, a cover tamper
feature is incorporated to indicate a trouble condition for removed
or improperly installed sensor cover. An improved cover design, with
an integrated the low-flow feature, isolates the sensor head from the
low-flow technology for simple maintenance.
The InnovairFlex series is designed for greater flexibility and reliable
smoke detection to simplify installation and maintenance. The new
InnovairFlex product line is backward compatible to existing Innovair
models, including remote test accessories
WARNING: Duct smoke detectors have specific limitations.
Agency Listings
S911
3029700
3242-1653:206
2202
DUCT SMOKE DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional duct smoke detector
application information.
InnovairFlex Duct Smoke Detector Specifications
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ D2 Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per UL
268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector
shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that
the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS451KEY remote test
station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring.
Physical Specifications
Size: (Rectangular)
(Square)
Weight:
Operating Temperature Range:
Storage Temperature Range:
Operating Humidity Range:
Air Duct Velocity:
14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.36 cm) Depth
7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
1.8 lb (0.82 kg)
-4°F to 158°F (-20°C to 70°C)
–22°F to 158°F (–30°C to 70°C)
0% to 95% relative humidity non-condensing
100 to 4000 ft/min (0.5 to 20.32 m/sec)
Electrical Ratings
Power supply voltage:
8.5-35 VDC
Input capacitance:
0.1 µF max.
Reset voltage:
2.5 VDC min.
Reset time: (with RTS451)
0.03 to 0.3 sec.
Reset time: (by power down)
0.3 sec. max.
Power up time:
35 sec. max.
Alarm response time:
15 sec.
Sensitivity Test:
See detector label
Current Requirements: (Using No Accessories)
Peak standby current:
120µA
Max. standby current:
60 µA (average)
Max. alarm current:
130 mA
Accessory Current Loads at 24 VDC
Device
Standby
RA100Z
0 mA
RTS151
0 mA
RTS151KEY
12 mA
Installing the InnovairFlex Sampling Tube
Alarm
12 mA Max.
12 mA Max.
12 mA Max.
The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing
the front or rear locking tab (front locking tab shown below right).
A05-0421-002
Wiring for 2-wire Duct Smoke Detector
System wiring diagram for 2-wire duct smoke detectors (powered from initiating device circuit):
UL/FM LISTED
COMPATIBLE 2-WIRE
CONTROL PANEL
(+) OUT
(+) RA
ALARM
INITIATION
LOOP
(–) RA
(+) IN
(+)
RA100Z (OPTIONAL)
REMOTE ALARM LED
(–)
4.4 VDC NOM.
IN ALARM
(+) OUT
(+) RA
(–) RA
LAST DETECTOR
IN LOOP D2
~
~
(+) IN
~
~
(+)
2ND DETECTOR
IN LOOP D2
1ST DETECTOR
IN LOOP D2
(+) IN
(+)
RA100Z (OPTIONAL)
REMOTE ALARM LED
(–)
4.4 VDC NOM.
IN ALARM
(+) RA
(–) RA
(+)
(–)
RA100Z (OPTIONAL) E
REMOTE ALARM LED O
L
R
4.4 VDC NOM.
IN ALARM
~
~
~
~
(–)
(+) OUT
(–)
(–)
(–)
EOL RESISTOR
SPECIFIED
BY PANEL
MANUFACTURER
STYLE D OPTIONAL WIRING
Wiring diagram for 2-wire duct smoke detector to RTS151/RTS151KEY Remote Test Station
MAGNET
TEST
SWITCH
4
– TEST COIL
5
2
ALARM
LED (RED)
+ TEST COIL
1
(–)
(+)
RTS151/RTS151KEY
(OPTIONAL) REMOTE
TEST STATION
+ IN
+ OUT
–
– RA
+ RA
+ RTS
D2
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
(–)
(+)
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
MAGNET
TEST
SWITCH
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
– TEST COIL
5
2
ALARM
LED (RED)
+ TEST COIL
4
1
+ IN
(–)
(+)
RTS151/RTS151KEY
(OPTIONAL) REMOTE
TEST STATION
+ OUT
–
– RA
+ RA
+ RTS
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
D2
NOTE: THE USE OF EITHER THE RTS151 OR RTS151KEY REQUIRES THE INSTALLATION OF AN ACCESSORY COIL, DCOIL, SOLD
SEPARATELY. SEE FIGURE 9 ABOVE FOR REFERENCE.
Important Note
The use of either RTS151 or RTS151KEY requires the installation of an accessory coil, DCOIL, sold separately.
Please refer to the D2 installation manual for more information
A05-0421-002
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different means of visible and
audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed.
RTS151 UL S2522
RTS151KEY UL S2522
RA100Z UL S2522
Ordering Information
Part No.
D2
Accessories
Description
2-wire photoelectric low-flow duct smoke detector
2151
DCOIL
DST1
DST1.5
DST3
DST5
DST10
2-wire conventional photoelectric sensor head
2-wire remote test coil required with RTS451/RTS451KEY
Metal sampling tube duct width up to 1ft (0.3m)
Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m)
Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)
Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m)
DH400OE-1
ETX
M02-04-00
P48-21-00
RA100Z
RTS151
RTS151KEY
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Weatherproof enclosure
Metal exhaust tube duct width 1ft (0.3m)
Test magnet
End cap for metal sampling tubes
Remote annunciator alarm LED
Remote test station
Remote test station with key lock
©2010 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0421-002 • 9/10 • #2498