E3 Series Classic

E3 Series®
Classic
E3 Series Classic
Description
The E3 Series® Classic Emergency Voice Evacuation System is a combination of the E3 Series® Expandable Emergency Evacuation System and the NetSOLO® Classic
System. The E3 Series Classic uses the latest generation
of fire alarm control panel sub-assemblies that include the
Intelligent Loop Interface-Main Board (ILI-MB-E3/ILI95MB-E3), Addressable Node Expander (ANX), Repeater
(RPT-E3), and the Power Supply (PM-9/PM-9G). The E3
Series Classic draws on 100 or 120 watt amplifiers for powerful, bulk amplification that can be used in a variety of
large-scale facilities such as industrial, university, or highrise complexes.
The E3 Series Classic is a peer-to-peer, self-regenerating
token ring passing network consisting of up to (64) nodes.
In addition, the Addressable Node Expander (ANX) board
expands the network to (122) nodes. The E3 Series Classic System is a modular design. This design allows a wide
range of configurations from three basic assemblies to
form an integrated, distributed fire alarm system with bulk
audio evacuation and fire command capability.
The E3 Series Classic System can have multiple command
centers. Each command center can occupy one node on
the network. These multiple command centers can either
serve as a remote command centers duplicating the functions of a main command center or operate as an independent command center for each location in a large-scale
facility.
A node may consist of an Intelligent Network Command
Center (INCC-C) comprised of Intelligent Network Interface-Voice Gateways (INI-VGE), fully programmable
Addressable Switch (ASM-16) sub-assemblies, a microphone for paging, and a telephone handset for fire fighter
communications. The E3 Series Classic includes the following components:
• Intelligent Network Interface-Voice Gateway
(INI-VGE-FO or INI-VGE-UTP)
• Addressable Switch Sub-Assembly (ASM-16)
• Amplifier-100 watt (AA-100) or Amplifier-120 watt
(AA-120)
• Remote LED Driver (ANU-48)
• ILI-E3 and ILI95-E3 Series loop modules
E3 Series Classic
Features
• IBC Seismic Certified.
• Listed under UL® Standard 864, 9th Edition.
• UL® Listed for smoke control (dedicated and non-dedicated) when properly configured.
• FM/UL® Listed for Pre-action/Deluge use.
• Provides up to (20), (100) or (120) watt amplifiers per
INI-VGE sub-assembly.
• Accommodates up to (122) nodes.
• Network communications convey all fire alarm
communication over unshielded, twisted-pair or
fiber-optic cable.
• Wires can extend up to 3,000 feet (8890 cm) between
each node while the fiber-optic cable can tolerate up to
8 dB loss between each node.
SIGNALING
FM
®
MEA
Approved
City of
Chicago
City of
Denver
FDNY #: 6175
Approved Approved
1
S1869 3025415 COA # 231-06-E 7165-1703:125 Class
Class 2
®
APPROVED
E3 Series and NetSOLO are registered trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
High Rise
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0641 Rev. K page 1 of 2
©2014 by Honeywell International Inc. All rights reserved.
Installation
Ordering Information (Continued)
An array of cabinets allows for neat, compact, attractive
installations. There are several cabinet options available
in the E3 Series Classic System.
Note: the INCC Inner Door is used to install the ASM-16/
ANU-48 sub-assemblies and microphone.
INCC-C Intelligent Network Command Center
Classic
Part Number
INCC-IDT
The E3 Series Classic System offers the following
enclosure:
• Amplifier Enclosure (CAB-B3, CAB-D3) that houses the
AA-100 and AA-120 amplifiers. The enclosures are
available in three (C3) or four D3 tiers, with one
amplifier occupying one tier.
For additional information on the cabinets, refer to the
E3 Series Cabinets data sheet (Part Number: 9020-0649).
E3 Series Classic
ILI-MB-E3
ILI-S-E3
ILI95-MB-E3
ILI95-S-E3
ANX-SR
ANX-MR-FO
ANX-MR-UTP
LCD-E3
RPT-E3
PM-9/PM-9G
Part Number
INI-VGE
INI-VGE-UTP
ASM-16
Fire fighter telephone handset
(requires INCC-IDT inner door)
Paging microphone module (occupies 1 slot on inner door)
Command center blank face plate
(occupies 1 slot on inner door)
Remote LED driver module (occupies 1 slot on inner door)
Bulk Amplification
AA-100
Description
Expandable Emergency Evacuation System
E3 Series Classic
Intelligent Loop Interface-Main
Board
Intelligent Loop InterfaceExpansion Board
Intelligent Loop Interface-Main
Board
Intelligent Loop InterfaceExpansion Board
Addressable Node ExpanderSingle Ring
Addressable Node Expander
Multi-Ring Fiber Optic
Addressable Node Expander
Multi-Ring Unshielded Twisted-Pair
LCD Keypad Display
Repeater Module
Power Supply Module
Description
Classic enabled voice gateway
Classic enabled voice gateway,
unshielded, twisted-pair
Programmable switch modules
(occupies one slot of inner door)
INCC-TEL
ANU-48
32°-120° F (0°-49° C)
0 to 93% non-condensing
at 90° F (32° C)
INCC-C Intelligent Network Command Center
- Classic
Optional INCC Accessories
INCC-BP
24 VDC
Ordering Information
Part Number
E3 Series
Dimensions:
INCC-MIC
Specifications:
Operating Voltage:
Operating
Temperature:
Relative Humidity:
INCC-ID
INCC-CABR
Description
Inner door with one double slot for
INCC-TEL handset & 4 slots
Inner door with 6 slots
INCC backbox (black) with red
outer door
(19” H x 19” W x 4” D)
(48 H x 48 W x 10 D cm)
AA-120
ACT-1
FCI-DR-C4B
FCI-DR-C4BR
FCI-DR-D4B
FCI-DR-D4BR
SBB-C4
SBB-D4
Audio Amplifier, 100W @70.7 VRMS
w/built-in tone generator, 120 VAC
Audio Amplifier, 120W @25 VRMS
w/built-in tone generator, 120 VAC
Audio coupling transformer, for
audio systems w/multiple
supplies
Blank door, lock & keys, for backbox accepting 3 chassis, (Black)
Blank door, lock & keys, backbox
accepting 3 chassis, (Red)
Blank door, lock & keys, for backbox accepting 4 chassis, (Black)
Blank door, lock & keys, backbox
accepting 4 chassis, (Red)
Backbox, 3 chassis, (Black)
Backbox, 4 chassis, (Black)
Optional Amplifier Accessories
FCI-CHG-120
FCI-LBB
Battery charger, 25-120 A/H sealed
lead-acid, mounts in FCI-LBB box
Battery box, accommodates batteries up to 55 A/H, black
Seismic Battery Bracket Kits
For information on the types of Seismic Battery Bracket
Kits that are available and the Seismic Battery Bracket Kit
Part Numbers and the installation instructions, refer to the
following documents:
• Seismic Battery Bracket Installation Guide, P/N: 53839
• E3 Series Cabinets Data Sheets, P/N: 9020-0649
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0641 Rev. K page 2 of 2
www.gamewell-fci.com