9020-0606 - Gamewell

LCD-E3
LCD Keypad Display
Description
The LCD-E3 provides the main panel display of the E3
Series® Expandable Emergency Evacuation System with
indicating LEDs and operating switches. Up to six (6),
LCD-E3 displays may be locally or remotely located from
the panel via a local RS-485 bus of the E3 Series, ILI-MBE3/ILI95-MB-E3 or the S3 Series, SLP (Smart Loop Panel)
sub-assembly.
The LCD-E3 includes an LCD display for the system status
and the following switches and LED indicators:
Switches
• Alarm acknowledge
• System reset/lamp test
• Trouble acknowledge
• Function buttons:
- menu/back
- back space/edit
- OK
• Signal silence
• 12 button keypad
LED Indicators
• AC Power On
• Alarm
• Supervisory
• System Trouble
(green)
(red)
(yellow)
(yellow)
• Power Fault
(yellow)
• Ground Fault
(yellow)
• System Silenced (yellow)
Installation Options
The LCD-E3 is adaptable for installation in any of the
following E3 Series System cabinets.
Cabinet
Part Number
• “A” size cabinet, inner door E3ID2-A
• “A2” flush cabinet
E3BB-FLUSH-LCD
• “A2” size cabinet, inner door E3ID-A2
• “B” size cabinet, inner door E3ID2-B
• B-Slim cabinet, outer door
E3BB-RBSLIM
• 7200 B Retrofit, inner door
7200-B-RETROFIT
• IF600 Retrofit, outer door
IF600-RETROFIT
• “C” size cabinet, inner door E3ID2-C
• 600XL Retrofit, inner door
600XL-RETROFIT
• 7200 C Retrofit, inner door
7200-C-RETROFIT
• “D” size cabinet, inner door E3ID2-D
LCD-E3
Features
• Listed under UL Standard 864, 9th Edition.
• Provides an 80-character display of system events
together with indicating LEDs and control switches.
• The E3 Series, ILI-MB-E3/ILI95-MB-E3 or S3 Series,
SLP can support up to six LCD-E3 displays, any or all
of which may be remotely located via the RS-485 serial
interface.
• Offers a legible backlit LED display, with low power consumption.
Ordering Information
Part Number
Description
LCD-E3
LCD keypad display
Specifications
Operating Voltage:
24 VDC FWR
(from PM-9 power supply)
Operating Current:
0.024 amp
Alarm Current:
0.028 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93%, non-condensing at
90° F (32° C)
SIGNALING
FM
APPROVED
S1869
E3 Series® is a registered trademark of Honeywell International Inc.
3025415
MEA
Approved
FDNY: 7165-1703:0125
COA #6077
City of
Chicago
Approved
Class1
Class2
High Rise
City of
Denver
Approved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0606 Rev. I page 1 of 1