Product Data and Specifications-Residential SOLA

Residential SOLATM S7910B
Local Keyboard Display Module
PRODUCT DATA
FEATURES
FUNCTIONS SUPPORTED
• Burner control state, sequence
• Rate control manual adjustment
• Lockout code
• Alert and Hold Reason
• CH set point
• DHW set point
• Communication interface with R7910B.
• First out and system status and diagnostics provided
through the LCD.
• Local communication of operation and
fault information.
APPLICATION
The S7910B Local Operator interface provides setpoint and
control adjustments to parameters of the R7910B SOLA
Hydronic Control. The R7910B SOLA is programmed to
provide a level of safety, functional capabilities, and features
beyond the capacity of conventional controls.
All data is displayed on an LCD with backlight. The S7910B
has four function buttons. The function of the bottom two
buttons varies according to the operation mode and screen
displayed. The right two buttons are used to adjust settings
and navigate up and down the displayed data.
Contents
Application ........................................................................
Features ...........................................................................
Ordering Information ........................................................
Specifications ...................................................................
Installation ........................................................................
Wiring ...............................................................................
Operation ..........................................................................
1
1
2
2
2
3
3
• Control Temperatures
• Outlet temperature
• Inlet temperature
• Delta T (Outlet-Inlet)
• DHW temperature
• Stack temperature
• Outdoor temperature
• Set-up
• Degree F/C toggle
• Outdoor reset parameter settings
• Remote firing rate control enable/disable
• Anti-Short Cycle enable/disable and setting
• Modbus address setting (1–250)
• Lead Lag Control
• LL on/off hysteresis
• LL baseload %
• Warm weather shutdown
• PIM Operation
• Diagnostics
• Flame signal measurement (µA)
• Previous Alert
• Previous Lockout code displayed
• Outlet Temp high limit
• Stack temp high limit
• DHW temp high limit
• Min/Max/Manual firing rate testing
68-0295-02
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
SPECIFICATIONS
[2] 5-43/64 (144)
4-29/64 (113)
[2] 9/32 (7)
All power and application requirements are controlled by the
R7910B controller.
1/64 (.5) MAX
31/16
(87)
WARNING
[2] 9/32 (7)
[2] 1/2
(13)
[2] 11/16 (17)
[2] 1-1/2
(38)
Do not attempt to use this display in applications
connecting to devices other than a R7910B.
For information on appropriate environmental
requirements see Honeywell Product Data 68-0290EF.
31/32
(25)
39/64 (15)
Boilers or other equipment provided with these interface
devices need to have appropriate instruction sheets issued by
the equipment OEM giving instructions on use. Or a copy of
the Honeywell Product Data 68-0290EF needs to be included
with the appliance.
[4] 1/4 (6)
M27488
Fig. 1. Approximate Panel Cutout dimensions of
S7910B in inches (millimeters).
INSTALLATION
Electrical Ratings:
Voltage and Frequency: 24 VAC powered from R7910B.
Environmental Ratings:
Ambient Temperature Ranges:
Operating: 32°F to +120°F (-0°C to +49°C).
Storage: -60°F to +150°F (-51°C to +66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or
property damage.
Disconnect the power supply before beginning
installation to prevent electrical shock and equipment
damage. More than one power supply may have
to be disconnected.
Mechanical:
Dimensions: See Fig. 1.
Weight: 4 oz. (124 grams), unpacked.
When Installing This Product…
Display:
LCD
1.
Approvals:
Underwriters Laboratories Inc. (UL)(cUL) Listed: File No.
MH20613 (MCCZ).
Federal Communications Commission:
Part 15, Class B emissions.
2.
3.
Mounting:
Snap-in model, See Figure 1 for Panel
Cutout dimensions.
4.
5.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced, flame
safeguard service technician.
After installation is complete, check out the product
operation as provided in these instructions.
Be sure wiring complies with all applicable codes,
ordinances and regulations.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0295—02
2
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
IMPORTANT
1. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
in accordance with the instructions, can cause interference to radio communications. It has been tested
and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are
designed to provided reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a residential area can cause interference, in which case,
users, at their own expense, can be required to take
whatever measures are required to correct this interference.
2. This digital apparatus does not exceed the Class B
limits for radio noise for digital apparatus set out in the
Radio Interference Regulations of the Canadian
Department of Communications.
The S7910B includes four keys. The bottom two keys vary
depending on what commands are displayed above them. The
two keys on the right adjust the displayed information.
OPERATING
MODE ICONS
NUMERICAL DISPLAY
UP
Outlet
Max
LBTHODLOOTOD
Inlet
F Min
AT
C Rate
DHW
M Rmt
Stack
V Adr
Outdoor
A ASC
Stby Check Prepurge
Ignition Run Postpurge
Setup diag Lockout Pilot Hold Alert
Home Done
Reset
Confirm Next
Humidity
Install the S7910B where the relative humidity never reaches
the dew point (condensation). The S7910B is designed to
operate in a maximum 85% RH continuous, noncondensing,
moisture environment.
HOME/DONE/RESET
CONFIRM/NEXT
DOWN
M27489
Fig. 3. S7910B user interface.
Three operation modes are available: User Mode, Setup
Mode, and Diagnostic Mode.
Vibration
Do not install the S7910B where it can be subjected to
vibration in excess of 0.5G continuous maximum vibration.
Startup
Weather
At startup, all text on the LCD will be displayed for 2 seconds,
followed by the software version number for an additional 2
seconds.
The S7910B is not designed to be weather tight. If installed
outdoors, the S7910B must be protected by a NEMA approved
weather-tight enclosure.
Next the S7910B will switch to outlet temperature display and
try to communicate with the R7910B. During this time, dashes
will be displayed in the numerical part of the LCD, along with
“Outlet” and “°F” or “°C.” When the S7910B communicates with
an R7910B, it switches to User Mode. If an error occurs, the
system switches to Error Mode.
WIRING
Wire the S7910B as shown in Fig. 2 using the wiring backplate
provided.
a
b
c
a
b
c
1
2
3
J3
R7910
HYDRONIC CONTROL
1
2
User Mode
In User Mode, the S7910B displays operating data of an
R7910B such as Outlet temperature, CH setpoint, or boiler
firing rate. The user can change screens by pressing the Next
button. Depending on R7910B mode of operation, the S7910B
distinguishes between three home screens:
• If CH call for heat is active, the S7910B considers outlet
water to be the home screen.
• If DHW call for heat is active, then DHW water temp will be
the home screen.
• If lead lag master call for heat is active, then lead lag
temperature will be the home screen.
3
S7910
LOCAL
DISPLAY
M27092
Fig. 2. S7910B wiring diagram.
User Mode consists of the items listed in Table 1. Pressing the
Next button progresses through the User Mode screens.
OPERATION
If limits are shown, pressing the up down buttons increases or
decreases the setpoints.
• Pressing the button changes setpoints in one degree
increments.
• Pressing and holding the button changes setpoints in five
degree increments.
All data from the S7910B is displayed on an LCD with
backlight. The LCD has two main zones:
• the Numerical Display contains numbers (degrees,
percentages, etc.).
• the Operating Mode Icons indicate what mode the S7910B
is in.
See Fig. 5 for the User Mode screen flow chart.
3
68-0295—02
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
Table 1. User Mode Screens.
Screen
Displays
Outlet Water Temp
Display current outlet water temperature
Outlet Setpoint
Display and modify current Outlet (CH) setpoint temperature
Inlet Water Temp
Display current inlet water temperature
Delta Temp
Display delta T temperature ([outlet temperature] - [inlet temperature])
DHW Temp
Display current DHW water temperature
DHW Setpoint
Display and modify current DHW setpoint temperature
Stack Temp
Display current stack temperature
Outdoor Temp
Display current outdoor temperature
Firing Rate
Display current boiler firing rate value
Lead Lag Header Temp
Current LL temp is displayed
Setpoint Temp
Display and modify current LL setpoint temp
0
TIMEOUT
888
Outlet LBTHODLODTOD
Max
˚F Min
Inlet
˚C Rate
T
% Rmt
DHW
Stack
V Adr
μA ASC
Outdoor
Stby Check Prepurge
Ignition Run Postpurge
Setup Diag Lockout Pilot Hold Alert
Home Done
Reset
DC
POWER-UP
Confirm Next
TIMEOUT
87
Outlet
Stby
˚F
Inlet
NEXT
Stby
68
˚F
Stby
Next
Next
DONE /
TIMEOUT
Outlet
Stby
17
˚F
T
NEXT
138
˚F
NEXT
DHW
Stby
Next
DHW
Stby
Next
NEXT /
TIMEOUT
Next
UP/DOWN
UP/DOWN
90
86
˚F
NEXT
120
˚F
˚F
TIMEOUT
TIMEOUT
DONE /
TIMEOUT
DHW
Stby
Done
DONE /
TIMEOUT
Done
DONE /
TIMEOUT
DONE /
TIMEOUT
TIMEOUT
120
˚F
Stby
Done
DONE /
TIMEOUT
TIMEOUT
UP/DOWN
138
˚F
NEXT /
TIMEOUT
Stby
NEXT
Stack
Stby
LL
TIMEOUT
Stby
Next
Next
10
%
NEXT
TIMEOUT
NEXT
Outdoor
Stby
Next
50
˚F
Rate
NEXT
Next
M31206
Fig. 4. User Mode screen flow.
After a certain period of user inactivity the S7910B times out
and switches to the current home screen. Setpoint changes
made prior to the timeout will be saved. Pressing the Done
button after changing a setpoint also saves the new setpoint.
68-0295—02
Timeouts for the different screens of the User Mode are shown
in Table 2.
4
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
Table 3. Setup Mode Features. (Continued)
Table 2. Timeouts in User Mode.
Screen Displayed
Setting
Length of Inactivity that
Causes Timeout
Outlet water temp
1 minute
CH water setpoint temp
10 seconds
Inlet water temp
1 minute
Remote Firing
Control
Remote Firing
Address
Display and modify current remote firing
control (On or OFF).
If On, Set Modbus Address (1 to 250).
Lead Lag
Current status of LL is shown "Ldr' (leader or
Master), SLA (slave) or OFF along with the
setup icon. Pressing the up and down key
toggles through the lead lag options.
Pressing 'Next' goes to the next setup
screen. The Rmt Adr icon indicates SLA
configuration, Rmt icon indicates Ldr
(Master) configuration.
Hysteresis
H5 is displayed to indicate current On/Off
hysteresis. Pressing the up/down key
increments/decrements the displayed value
with 1 degree step.
Baseload
Bl is displayed to indicate current baseload in
%. Pressing the up/down key increments/
decrements the displayed value with 1 %
step.
Delta T
DHW water temp
DHW water setpoint temp
10 seconds
Stack temp
1 minute
Outdoor temp
Firing Rate
Lead Lag Header Temp
Lead Lag Setpoint Temp
10 seconds
Setup Mode
Pressing and holding both the Up and Down buttons for 3
seconds changes the S7910 from User Mode to Setup Mode.
Warm Weather Sd is displayed to indicate warm weather
Shutdown
temperature. Pressing the up/down key
increments/decrements the displayed value
with 1 degree step.
The 'Sd' icon will blink when waiting for the
current WWSD value from the R7910.
The Setup icon will be displayed in the Operating Mode portion
of the display. The user can change screens by pressing the
Next button.
NOTE: Entering Setup Mode will put the R7910 system into
Standby. If the system is firing, the R7910 will postpurge and go to Standby. The system will remain in
Standby until the Done button is pressed or the inactive timeout time has elapsed.
Anti-short cycle The Min and ASC icon is displayed to
indicate anti-short cycle. Pressing the up/
down key increments/decrements the
displayed value within range 0.0 to 10.0.
Anti-short time display format
“LBTHODLOD” in the Numerical display section refers to
Outdoor Reset. When Outdoor Reset is Off, pressing the Next
button will move to the Rmt icon. When Outdoor Reset is On,
pressing the Next button will move into the LBT, HOD, and
LOD displays, which will allow setting of the Low Boiler Reset
Temperature, High Outdoor Reset Temperature, and Low
Outdoor Reset Temperatures.
Table 3. Setup Mode Features.
Definition
°F/°C
Set display to either degrees Fahrenheit or
degrees Celsius.
LBTHODLOD
LBTHODLOD (Outdoor Reset) Off or ON.
• If Off go to Remote Firing Control.
• If On go to Low Boiler Reset Temp.
Low Boiler
Temp
Display and modify current LBT
setpoint temperature
High Outdoor
Reset Temp
Display and modify current HOD
setpoint temperature.
Low Outdoor
Reset Temp
Display and modify current LOD
setpoint temperature .
Displayed
value
Anti-short cycle time in
seconds
0
0
0.1
6
0.2
12
---
See Fig. 5 for the Setup Mode screen flow chart.
Setting
Definition
1.0
60
1.1
66
1.2
72
---
5
10
600
PIM
operation
Up/down key selects bAC
(backup) or rES (restore)
68-0295—02
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
Table 3. Setup Mode Features. (Continued)
Setting
Password
After a certain period of user inactivity or if the Done button is
pressed, the S7910B switches to the current home screen and
the system switches from Standby to normal operation.
Definition
PAS informs the user that a three digit
password needs to be entered to complete
the selected operation. Up/down key
increments the flashing digit of the three digit
pass code. Next key switches the editable
digits. Done key enters the pass code and
the selected action (backup or restore) will
be exercised.
NOTE: This passcode is supplied from the
OEM and is maintained within the R7910
device. If performing multiple backup/restore
operations, the pass code entry screen is
required for each operation.
Timeouts for the Setup Mode are shown in Table 4.
Table 4. Timeouts in Setup Mode.
Screen Displayed
Temperature scale
Outdoor reset temperatures
Remote firing control
Remote firing address
Description
E81
Provided password not
recognized
E82
PIM not detected in socket
E83
PIM busy/not available
E84
Data Invalid
E85
PIM vs. Sola mismatch (e.g.
model)
E86
PIM memory not sufficient
E87
Fatal error occurred
E88
Command from S7910 not
recognized
E89
Initial scan not finished
E98
Timeout, no response
Lead Lag control
LL on/off hysteresis
LL Baseload
Anti-short-cycle
PIM operations
Pressing 'next' returns back to the command
screen to repeat the operation that failed.
Pressing 'done' exits the setup mode.
68-0295—02
1 minute
Outdoor reset setting
PIM Error Codes
Code
Length of Inactivity That
Causes Timeout
6
5 minutes
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
ENTER SETUP MODE
ICP MMI-SETUP MODE (1)
LBT
LBTHODLOD
NEXT
Setup
NEXT
Setup
Setup
Done
Next
Done
Next
UP/DOWN
NEXT
68
HOD
Setup
Done
Next
Next
UP/DOWN
LBTHODLOD
Setup
68
˚F
˚F
Setup
Done
Done
Next
Next
NEXT
NEXT
14
LOD
ANY SETUP
SCREEN
NEXT
Setup
Rmt
Adr
Setup
Done
Next
DONE /
TIMEOUT
LEAVE SETUP MODE
3
˚F
Done
Next
NEXT
CONTINUE ON
NEXT PAGE
M31208
Fig. 5. Setup Mode screen flow Setup mode 1
7
68-0295—02
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
ICP MMI-SETUP MODE (2)
CONTINUED
FROM PREVIOUS
SETUP SCREENS
NEXT
Setup
Done
Next
hs
UP/DOWN
LL
SLA
NEXT
Setup
Setup
Setup
Done
Setup
Done
Next
NEXT
Done
Next
NEXT
Next
NEXT
Setup
Done
Done
Next
17
Next
UP/DOWN
NEXT
Setup
DONE /
TIMEOUT
NEXT
˚F
Setup
Done
Next
81
%
Setup
Done
ANY SETUP
SCREEN
66
˚F
Next
NEXT
Done
Next
NEXT
Setup
Done
2.5
Next
LEAVE SETUP MODE
NEXT
Min
ASC
Setup
Done
CONTINUE ON
NEXT PAGE
M31214
Fig. 6. Setup Mode screen flow Setup mode 2
68-0295—02
Next
8
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
ICP MMI-SETUP MODE (3)
ERROR
RECEIVED/
20S TIMEOUT
CONTINUED
FROM PREVIOUS
SETUP SCREENS
E87
ANY SETUP
SCREEN
DONE /
TIMEOUT
AC
1S
Setup
NEXT
Setup
Done
Done
Next
Next
LEAVE SETUP MODE
AC
A
PAS
NEXT
Setup
AC
Setup
Done
UP/DOWN
Done
Next
ES
000
Setup
Next
OK
RECEIVED
B
Setup
Setup
Done
Next
UP/DOWN
ES
B
A
Setup
Done
Next
OK
RECEIVED
Done
Done
Next
Next
“bAC” = BACKUP
“rES” = RESTORE
LEGEND
FLASHING
ITEM
E87
NEXT CHANGES
FLASHING DIGIT
ERROR
RECEIVED/
20S TIMEOUT
ES
1S
Setup
NEXT
Setup
Done
Next
Done
Next
M31210
Fig. 7. Setup Mode screen flow Setup mode 3
Diagnostic Mode
Table 5. Diagnostic Mode Features.
Pressing and Holding the Next button for 3 seconds changes
the S7910B from User Mode to Diagnostic Mode.
Setting
The Diag icon will be displayed in the Operating Mode portion
of the display. The user can change screens by pressing the
Next button.
Flame Signal
Display current flame signal strength value.
Flame signal in µA.
Alert
Display last Alert code number
(See R7910 Product Data Sheet 68-0290EF
for description).
Lockout
Display last Lockout code number
(See R7910 Product Data Sheet 68-0290EF
for description).
See Fig. 8 for the Diagnostic Mode screen flow chart.
9
Definition
68-0295—02
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
Table 5. Diagnostic Mode Features. (Continued)
Setting
After a certain period of user inactivity or when the Done button
is pressed, the R7910B is forced to accept all calls for heat and
the S7910B leaves the Diagnostic Mode and switches to the
User Mode’s current home screen.
Definition
Outlet Temp
High Limit
Display current outlet temperature
high limit setting.
Stack Temp
High Limit
Display current stack temperature
high limit setting.
DHW Temp
High Limit
Display current DHW temperature
high limit setting.
Firing Rate
Adjustment
Display and modify boiler firing rate value.
If the Next button is pressed, it causes S7910B to display the
next screen of the Diagnostic Mode.
Firing Rate Adjustment—Maximum Rate
The Max icon is flashing and the Diag icon is solid. In this
mode a demand is sent to the R7910B and the burner will start
(if not already operating) and is forced to run at 90% of firing
rate.
Alerts
The Firing rate value display is alternated with the outlet
temperature display.
Alerts are abnormal events that do not require manual
intervention to reset the R7910. Alerts can be faults from nonsafety functions such as a temperature sensor out of range or
AC Frequency out of range.
After a certain period of user inactivity or when the Done button
is pressed, the R7910B is forced to accept all calls for heat and
the S7910B leaves the Diagnostic Mode and switches to the
User Mode’s current home screen.
The last received Alert number is displayed with the Diag icon.
Pressing the Reset button clears the Alert number.
If the Next button is pressed, it causes S7910B to display the
next screen of the Diagnostic Mode.
When a new Alert is received, the Alert icon is displayed, and
the S7910B is in User Mode. To clear the Alert number, change
to the Diagnostic Mode and press the Reset button. After a
certain period of user inactivity or when the Done button is
pressed, the S7910B leaves Diagnostic Mode and returns to
the User Mode’s current home screen.
Firing Rate Adjustment—Manual Rate
The Rate icon is flashing and the Diag icon is solid. In this
mode a demand is sent to the R7910B and the burner will start
(if not already operating) and is forced to run at 90% of firing
rate.
Lockouts
The Firing rate value display is alternated with the outlet
temperature display. Pressing the Up or Down buttons
changes the displayed firing rate value in 1% increments within
a range 10% to 90%.
Lockouts cause the R7910 to shutdown and require manual or
remote reset to clear the lockout. Lockouts always cause the
Alarm contacts to close.
The last received Lockout number is displayed with the Diag
icon. Pressing the Reset button clears the Lockout number and
resets the R7910.
After certain period of user inactivity or when the Done button
is pressed, the R7910B is forced to accept all calls for heat and
the S7910B leaves the Diagnostic Mode and switches to the
User Mode’s current home screen.
After certain period of user inactivity or when the Done button
is pressed, the S7910B leaves Diagnostic Mode and switches
to the User Mode’s current home screen.
Timeouts for the Diagnostic Mode are shown in Table 6.
Pressing the Next button causes the S7910B to display the
next screen of the Diagnostic Mode.
Table 6. Timeouts in Diagnostic Mode.
Firing Rate Adjustment—Initial Screen
The Min icon is displayed with the Diag icon. This screen
indicates that the S7910B is going to enter firing rate
adjustment mode.
Screen Displayed
Flame signal
Previous Alert
Pressing the Next button forces the R7910B to enter the state
where all calls for heat are ignored and the S7910B switches to
the next screen of the Diagnostic Mode.
Previous Lockout
Outlet temp high limit
Stack temp high limit
Firing Rate Adjustment—Minimum Rate
DHW temp high limit
The Min icon is flashing and the Diag icon is solid. In this mode
a demand is sent to the R7910B and the burner will start (if not
already operating) and is forced to run at 10% of firing rate.
Firing rate adjustment—initial screen
Firing rate adjustment—minimum rate
Firing rate adjustment—maximum rate
The Firing rate value display is alternated with the outlet
temperature display.
68-0295—02
Firing rate adjustment—manual rate
10
Length of Inactivity
That Causes
Timeout
5 minutes
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
ENTER DIAGNOSTIC MODE
0
5
NEXT
µA
Diag
Alert
Diag
Done
Next
120
NEXT
µA
Reset
NEXT
Max
Diag
Diag Lockout
Done
Next
104
Outlet
Done
Next
Next
NEXT
DHW
NEXT
122
˚F
NEXT
Done
10
Run
Diag
Diag
Done
Next
Min
%
NEXT
Done
Run
Diag
90
Done
Done
Next
Max
%
NEXT
Next
Stack
Max
Diag
Diag
Min
104
˚F
90
%
NEXT
Run
Diag
Next
Next
Done
Rate
Next
DONE
ANY SCREEN
DONE / RESET
TIMEOUT
LEAVE DIAGNOSTIC MODE
Fig. 8. Diagnostic Mode screen flow.
11
M28168
68-0295—02
RESIDENTIAL SOLATM S7910B LOCAL KEYBOARD DISPLAY MODULE
Error Modes
Incompatible Model of R7910B Detected
Hold
A Hold code is displayed in the numerical part of the display
when a Hold state is received. Burner state sequence icons
reflect the current state of the R791BA burner. There is no way
to leave this state through user intervention on the S7910B.
Lockout
A Lockout code is displayed in the numerical part of the display
when a Lockout state is received. When the Reset button is
pressed, the R7910B is forced to leave the Lockout state.
Alert code 980 is displayed as an S7910B internal Alert when
an incompatible version of R7910B is detected. For example:
• S7910A commercial model: R7910B residential
model found.
• S7910B residential model: R7910A commercial
model found.
There is no way to take S7910B out of this state other than
connecting the right device and cycling power to the S7910B.
Communication Timeout
Alert code 981 is displayed as an S7910B internal Alert when
the R7910B repeatedly does not respond to message queries
sent by the S7910B. The S7910B continues polling the
R7910B in this state to determine when it starts to
communicate again. When the communication is restored, the
S7910B switches to the User Mode home page and continues
normal operation.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2009 Honeywell International Inc.
68-0295—02 E.K. Rev. 12-09
Printed in U.S.A.