65-0229-2 - 7800 SERIES Relay Modules

7800 SERIES
Relay Modules
CHECKOUT AND TEST
This publication provides general checkout and troubleshooting procedures for the 7800 SERIES Relay Modules.
SYSTEM CHECKOUT
IMPORTANT
Perform all Static Checkout Procedures in the applicable relay module installation instructions before
starting these procedures.
WARNING
Explosion Hazard.
Can cause serious injury or death.
Do not allow fuel to accumulate in the combustion
chamber for longer than a few seconds without igniting
to prevent danger of forming explosive mixture. Close
manual fuel shutoff valve(s) if flame is not burning at
end of specified time.
WARNING
Electric Shock Hazard.
Can cause serious injury or death.
Use extreme care while testing system. Line voltage is
present on most terminal connections when power is on.
Limit trial for pilot to ten seconds. Limit the attempt to light
main burner to two seconds after fuel reaches burner nozzle.
Do not exceed manufacturer nominal lightoff time.
CAUTION
Equipment Malfunction or Damage Hazard.
Each relay module type is unique. Using existing
wiring on a relay module change can cause equipment
damage. Make wiring changes when a relay module is
replaced with a different 7800 SERIES Relay Module
to sequence burner.
IMPORTANT
1. If the system fails to perform properly, note the fault code,
fault message, equipment status, and sequence time on
the display. Then refer to the Troubleshooting section.
2. Repeat all required Checkout tests after all adjustments are made. All tests must be satisfied with the
flame detector(s) in their final position.
Equipment Recommended
S7800A Keyboard Display Module
Open master switch before removing or installing 7800 SERIES
Relay Module or Keyboard Display Module connector.
Volt-ohmmeter (1M ohm/volt minimum sensitivity) with: 0-300
Vac capability. 0-6000 ohm capability. 0-10 Vdc capability.
Make sure all manual fuel shutoff valves are closed before
starting initial lightoff check and Pilot Turndown tests.
Checkout Summary
Do not put the system in service until you have satisfactorily
completed all applicable tests in this section and any others
recommended by the original equipment manufacturer.
Table 1 provides an overview of checkout steps performed for
each applicable system.
See Installation Instructions for location of component parts
and/or Q7800 Specifications for terminal locations.
65-0229-2
7800 SERIES RELAY MODULES
Table 1. Checkout Steps and Applicable 7800 SERIES Systems.
Piloted
Systems
DSI
Systems
Infrared Flame
Detectors
Flame Rod
Systems
Ultraviolet Flame
Detectors
Preliminary Inspection
X
X
X
X
X
Flame Signal Measurement
X
X
X
X
X
Initial Lightoff Check for Proved Pilot
X
Checkout Step
Initial Lightoff Check for Direct Spark Ignition
Pilot Turndown Test
X
X
Ignition Interference Test
X
Hot Refractory Saturation Test
Hot Refractory Hold-in Test
X
X
X
X
X
X
Ignition Spark Pickup
X
Response to Other Ultraviolet Sources
X
Flame Signal with Hot Combustion Chamber
X
X
X
X
X
Safety Shutdown Tests
X
X
X
X
X
Preliminary Inspection
Perform the following inspections to avoid common problems.
Make certain that:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Wiring connections are correct and all terminal screws
are tight.
Flame detector(s) is clean, installed and positioned
properly. Consult the applicable Instructions.
Combination of amplifier and flame detector(s) is
correctly used. See the amplifier specifications.
Plug-in amplifier and purge card (if required) are
securely in place.
Burner is completely installed and ready to fire; consult
equipment manufacturer instructions. Fuel lines are
purged of air.
Combustion chamber and flues are clear of fuel and fuel
vapor.
Power is connected to the system disconnect switch
(master switch).
Lockout is reset (reset button) only if the Relay Module
is powered.
Run/Test Switch (if present) is in RUN position.
System is in STANDBY condition. STANDBY message
is displayed in the S7800 Keyboard Display Module.
All limits and interlocks are reset.
Flame Signal Measurement
See instructions provided with the amplifier.
INITIAL LIGHTOFF CHECKS
Proved Pilot Systems
Perform this check on all installations that use a pilot. It should
immediately follow the preliminary inspection.
NOTE: Low fuel pressure limits, if used, could be open. If so,
bypass them with jumpers during this check.
1.
2.
Open the master switch.
Make sure that the manual main fuel shutoff valve(s) is
closed. Open the manual pilot shutoff valve. If the pilot
takeoff is downstream from the manual main fuel shutoff
65-0229—2
2
3.
4.
5.
6.
valve(s), slightly open the manual main valve to supply
pilot gas flow. Make sure the main fuel is shut off just
upstream from the burner inlet, or disconnect power
from the automatic main fuel valve(s).
Close the master switch and start the system with a call
for heat by raising the setpoint of the operating controller;
see the relay module sequence. The 7800 SERIES
Relay Module should start the INITIATE sequence.
Let the sequence advance to PILOT IGN (status is displayed on the Keyboard Display Module, if used),
PILOT LED turns on, ignition spark should occur and
the pilot should light. If the pilot ignites, the FLAME LED
is energized. Go to step 7.
If the pilot flame is not established in ten seconds (four
seconds if configuration jumper JR1 is clipped), safety
shutdown occurs. Let the sequence complete its cycle.
Push the reset pushbutton, and let the system recycle
once. If the pilot still does not ignite, make the following
ignition/pilot adjustments:
a. Open the master switch and remove the 7800
SERIES Relay Module from the subbase.
b. On the subbase, jumper L1 to the ignition terminal;
refer to the appropriate wiring diagram to determine
the proper terminal. Disconnect the leadwire to the
pilot valve if it is connected to the same terminal.
c. Close the master switch to energize only the ignition
transformer.
d. If the ignition spark is not strong and continuous,
open the master switch and adjust the ignition electrode spark gap setting to the manufacturer recommendation.
e. Make sure the ignition electrodes are clean.
f. Close the master switch and observe the spark.
g. After a continuous spark is obtained, open the master switch and add a jumper on the subbase from
terminal L1 power to the pilot terminal 8 or 21.
Reconnect the leadwire from the pilot valve if it was
disconnected in step b.
h. Close the master switch to energize both the ignition
transformer and the pilot valve.
i. If the pilot does not ignite and if the ignition spark is
still continuous, adjust the pressure regulator until a
pilot is established.
7800 SERIES RELAY MODULES
j.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
When the pilot ignites properly and stays ignited,
open the master switch and remove the jumper(s)
from the terminals of the subbase.
k. Check for adequate bleeding of the fuel line.
l. Reinstall the 7800 SERIES Relay Module on the subbase, close the master switch and then return to step 4.
When pilot ignites, measure the flame signal. If the pilot
flame signal is unsteady or approaching the 1.25 Vdc
minimum value, adjust the pilot flame size or detector
sighting to provide a maximum and steady flame signal.
Recycle the system to recheck lightoff and pilot flame signal.
When the MAIN LED turns on, make sure the automatic
main fuel valve is open; then smoothly open the manual
main fuel shutoff valve(s) and watch for main burner
flame ignition. When the main burner flame is established, go to step 16.
If the main burner flame is not established within five
seconds or the normal lightoff time as specified by the
equipment manufacturer, close the manual main fuel
shutoff valve(s).
Recycle the system to recheck the lightoff and pilot
flame signal.
Smoothly open the manual fuel shutoff valve(s) and try
lightoff again. (The first re-attempt may have been required
to purge the lines and bring sufficient fuel to the burner.)
If the main burner flame is not established within five
seconds or the normal lightoff time specified by the
equipment manufacturer, close the manual main fuel
shutoff valve(s). Check all burner adjustments.
If the main burner flame is not established after two attempts:
a. Check for improper pilot size.
b. Check for excess combustion air at low fire.
c. Check for adequate low fire fuel flow.
d. Check for proper gas supply pressure.
e. Check for proper valve operation.
f. Check for proper pilot flame positioning.
Repeat steps 8 and 9 to establish the main burner
flame; then go to step 16.
With the sequence in RUN, make burner adjustments
for flame stability and Btu input rating.
Shut down the system by opening the burner switch or
by lowering the setpoint of the operating controller.
Make sure the main flame goes out. There may be a
delay due to gas trapped between the valve(s) and
burner. Make sure all automatic fuel valve(s) close.
Restart the system by closing the burner switch and/or
raising the setpoint of the operating controller. Observe
that the pilot is established during PILOT IGN and the
main burner flame is established during MAIN IGN
within the normal lightoff time.
Measure the flame signal. Continue to check for the
proper signal through the RUN period. Check the signal
at both High and Low Firing Rate positions and while
modulating, if applicable.
Run the burner through another sequence, observing
the flame signal for:
a. Pilot flame alone.
b. Pilot and main flame together.
c. Main flame alone (unless monitoring an intermittent
pilot). Also observe the time it takes to light the main
flame. Ignition of main flame should be smooth.
Make sure all readings are in the required ranges
before proceeding.
Return the system to normal operation.
NOTE: After completing these tests, open the master switch
and remove all test jumpers from the subbase terminals, limits/controls or switches.
3
Direct Spark Ignition Systems
This check applies to gas and oil burners not using a pilot. It
should immediately follow the preliminary inspection. Refer to
the appropriate sample block diagram of field wiring for the
ignition transformer and fuel valve(s) hookup.
NOTE: Low fuel pressure limits, if used, could be open. If so,
bypass them with jumpers during this check.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
Open the master switch.
Complete the normal ready-to-fire checkout of the fuel
supply and equipment as recommended by the equipment manufacturer.
Close all manual main fuel shutoff valve(s). Check that
the automatic fuel valve(s) is closed. Make sure fuel is
not entering the combustion chamber.
Close the master switch and start the system with a call
for heat by raising the setpoint of the operating controller; see the relay module sequencing. The program
sequence should start the INITIATE sequence.
Let the sequence advance through PREPURGE (if applicable). Ignition spark should occur when the PILOT LED turns
on. Listen for the click of the first stage fuel solenoid valve(s).
The Relay Module locks out and the ALARM LED turns on.
Let the 7800 SERIES Relay Module complete its cycle.
Open the manual fuel shutoff valve(s).
Push the reset button and the relay module recycles the
program sequence through PREPURGE (if applicable).
When the PILOT LED turns on, make sure that the first
stage burner flame is established. If it is, go to step 15.
If the first stage burner flame is not established within
four seconds, or within the normal lightoff time specified
by the equipment manufacturer, close the manual fuel
shutoff valve(s), and open the master switch.
Check all burner adjustments.
Wait about three minutes. Close the master switch,
open the manual fuel shutoff valve(s), and try to light off
the burner again. The first attempt may be required to
purge the lines and bring sufficient fuel to the burner.
If the first stage burner flame is not established within
four seconds, or within the normal lightoff time specified
by the equipment manufacturer, close the manual fuel
shutoff valve(s), and open the master switch.
If necessary, repeat steps 11 through 13 to establish
the first stage burner flame. Then go to step 15.
When the first stage burner flame is established, the
sequence advances to RUN. Make burner adjustments
for flame stability and input rating. If a second stage is
used, go to step 18.
Shut down the system by opening the burner switch or
by lowering the setpoint of the operating controller.
Make sure the burner flame goes out and all automatic
fuel valves close.
If used, remove the bypass jumpers from the low fuel
pressure limit and subbase.
If a second stage is used, make sure the automatic second stage fuel valve(s) opened. Check the lightoff as
follows (or go to step 19):
a. Open the manual second stage fuel valve(s).
b. Restart the system by raising the setpoint of the
operating controller.
c. When the first stage burner flame is established,
watch for the automatic second stage fuel valve(s)
to open. Observe that the second stage lights off
properly.
d. Make burner adjustments for flame stability and
input rating.
65-0229—2
7800 SERIES RELAY MODULES
19.
20.
21.
e. Shut down the system by lowering the setpoint of
the operating controller. Make sure the burner flame
goes out and all automatic fuel valves close.
f. Go to step 19.
Restart the system by closing the burner switch and/or raising the setpoint of the operating controller. Observe that the
burner flame is established during PILOT IGN, within the normal lightoff time specified by the equipment manufacturer.
Measure the flame signal. Continue to check for the proper
signal through the RUN period. Check the signal at both
high and low firing rate positions and while modulating. Any
pulsating or unsteady readings require further attention.
Make sure all readings are in the required ranges
before proceeding.
NOTE: On completing these tests, open the master switch
and remove all test jumpers from the subbase terminals, limits/controls or switches.
22.
If using AMPLI-CHECK™ or self-checking amplifier and
1M ohm/voltmeter, the flame signal fluctuates every time the
amplifier does a self-check or a shutter check.
NOTE: Low fuel pressure limits, if used, could be open. If so,
bypass them with jumpers during this test.
6.
Open the master switch.
Close the manual main fuel shutoff valve(s).
Connect a manometer (or pressure gauge) to measure
pilot gas pressure during the turndown test.
Open the manual pilot shutoff valve(s).
Close the master switch and start the system with a call
for heat. Raise the setpoint of the operating controller.
The 7800 SERIES sequence should start, and
PREPURGE (if applicable) should begin.
After the PILOT LED turns on in interrupted pilot applications, set the Run/Test Switch to the TEST position to
stop the sequence. The FLAME LED comes on when
the pilot ignites.
NOTE: If the sequence does not stop, reset the system and
make sure you set the Run/Test Switch to TEST
within the first eight seconds of the PILOT IGN
sequence.
IMPORTANT
You have 0.8 second or three seconds, depending
on PFEP selected, to position the Run/Test Switch to
the TEST position to stop the sequence after the
start of the PILOT IGN period.
7.
8.
9.
10.
Turn down the pilot pressure very slowly, reading the
manometer (or pressure gauge) as it drops. Stop
instantly when the FLAME LED goes out. Note the pres-
65-0229—2
If there is no flame for 15 seconds with the Run/Test
switch in the TEST position, the relay module locks out.
Repeat step 7 to verify the pilot gas pressure reading at
the exact point the FLAME LED light goes out.
Increase the pilot pressure immediately until the FLAME
LED comes on, and then turn it down slowly to obtain a
pressure reading just above the dropout point or until
the flame signal increases to 1.25 Vdc.
Set the Run/Test Switch in the RUN position (if used)
and let the sequence proceed. When the MAIN LED
turns on, make sure the automatic main fuel valve(s)
opens; then smoothly open the manual main fuel shutoff
valve(s) (or any other manually-opened safety shutoff
valve(s), if used) and watch for main burner ignition. If
the main burner flame is established, go to step 18.
NOTE: This step requires two people, one to open the manual valve(s) and one to watch for ignition.
Perform this check on all installations that use a pilot. The
purpose of this test is to verify that the main burner can be lit
by the smallest pilot flame that can hold in the flame amplifier
and energize the FLAME LED. Clean the flame detector(s) to
make sure that it detects the smallest acceptable pilot flame.
4.
5.
NOTE:
Return the system to normal operation.
PILOT TURNDOWN TEST (ALL
INSTALLATIONS USING A PILOT)
1.
2.
3.
sure. The pilot is at the minimum turndown position.
Immediately turn up the pilot pressure until the FLAME
LED comes on again or the flame signal increases to
1.25 Vdc.
4
11.
12.
13.
14.
15.
16.
17.
18.
If the main burner flame is not established within five
seconds, or within the normal lightoff time specified by
the equipment manufacturer, close the manual main
fuel shutoff valve(s) and open the master switch. If the
lightoff is rough, the pilot flame size is too small.
Close the master switch to recycle the burner and stop
the sequence in the PILOT period by using the
Run/Test Switch.
Increase the pilot flame size by increasing its fuel flow
until a smooth main flame is accomplished.
Reposition the flame scanner sight tube or use orifices
until the pilot flame signal voltage is in the range of 1.25
to 1.50 Vdc.
When the main burner lights reliably with the pilot at
turndown, disconnect the manometer (or pressure
gauge) and turn up the pilot gas flow to that recommended by the equipment manufacturer.
If used, remove the bypass jumpers from the subbase
terminals, limits/controls, or switches.
Run the system through another cycle to check for
normal operation.
Return the system to normal operation.
IGNITION INTERFERENCE TEST (ALL
FLAME RODS)
Ignition interference can subtract from (decrease) or add to
(increase) the flame signal. If it decreases the flame signal
enough, it causes a safety shutdown. If it increases the flame
signal, it could cause the FLAME LED to come on when the
true flame signal is below the minimum acceptable value.
Start the burner and measure the flame signal with both
ignition and pilot (or main burner) on, and then with only the
pilot (or main burner) on. Any significant difference (greater
than 0.5 Vdc) indicates ignition interference.
7800 SERIES RELAY MODULES
To Eliminate Ignition Interference
1.
2.
3.
4.
5.
6.
Make sure there is enough ground area.
Be sure the ignition electrode and the flame rod are on
opposite sides of the ground area.
Check for correct spacing on the ignition electrode:
a. 6000V systems—1/16 to 3/32 in. (1.6 to 2.4 mm).
b. 10,000V systems—1/8 in. (3.2 mm).
Make sure the leadwires from the flame rod and ignition
electrode are not too close together.
Replace any deteriorated leadwires.
If the problem cannot be eliminated, consider changing
the system to an ultraviolet flame detection system.
Hot Refractory Saturation Test (All Infrared
Detectors)
Start the burner and monitor the flame signal during the
warmup period. A decrease in signal strength as the refractory
heats up indicates hot refractory saturation. If saturation is
extreme, the flame signal drops below 1.25 Vdc and the
system shuts down as though a flame failure occurred.
If hot refractory saturation occurs, the condition must be corrected.
Add an orifice plate in front of the cell to restrict the viewing area,
lengthen the sight pipe or decrease the pipe size (diameter).
Continue adjustments until hot refractory saturation is eliminated.
Hot Refractory Hold-in Test (Rectifying
Photocell, Infrared Detectors, Ultraviolet
Detectors)
bustion chamber. This reduces a buildup of fuel
vapors in the combustion chamber caused by oil line
purging.
5.
If the detector is sensing hot refractory, correct the condition by one or more of the following procedures:
a. Add an orifice plate in front of the cell to restrict the
viewing area of the detector.
b. Resight the detector at a cooler, more distant part of
the combustion chamber. Make sure the detector
properly sights the flame.
c. Try lengthening the sight pipe or decreasing the
pipe size (diameter).
For details, refer to the detector Instructions and the
equipment Operating Manual. Continue adjustments until hot
refractory hold-in is eliminated.
IGNITION SPARK RESPONSE TEST
(ALL ULTRAVIOLET DETECTORS)
Test to make certain that the ignition spark is not actuating the
FLAME LED:
1.
2.
3.
This condition can delay response to flame failure and also
can prevent a system restart if hot refractory is detected.
Infrared (lead sulfide) detectors can respond to infrared rays
emitted by a hot refractory, even when the refractory has
visibly ceased to glow. Infrared radiation from a hot refractory
is steady, but radiation from a flame has a flickering
characteristic. The infrared detection system responds only to
flickering infrared radiation; it can reject a steady signal from
hot refractory. The refractory steady signal can be made to
fluctuate if it is reflected, bent or blocked by smoke or fuel mist
within the combustion chamber. Be careful when applying an
infrared system to verify its response to flame only.
The ultraviolet detector can respond to hot refractory above
2300°F (1371°C).
1.
2.
3.
4.
Operate the burner until the refractory reaches its maximum temperature (infrared only). If the installation has a
multi-fuel burner, burn the heavier fuel that is most likely
to reflect, bend or obscure the hot refractory steady
infrared radiation.
When the maximum refractory temperature is reached,
close all manual fuel shutoff valves, or open the electrical
circuits of all automatic fuel valves.
Visually observe when the burner flame or FLAME LED
goes out. If this takes more than three seconds, the
infrared detector is sensing hot refractory.
Immediately terminate the firing cycle. Lower the setpoint to the operating controller, or set the Fuel Selector
Switch to OFF. Do not open the master switch.
NOTE: Some burners continue to purge oil lines between
the valves and nozzles even though the fuel valves
are closed. Terminating the firing cycle (instead of
opening the master switch) allows purging the com5
Close the pilot and main burner manual fuel shut-off valve(s).
Start the burner and use the Run/Test Switch (if available) to stop the sequence in the PILOT IGN period.
Ignition spark should occur, but the flame signal should
not be more than 0.5 Vdc.
If the flame signal is higher than 0.5 Vdc and the FLAME
LED does come on, consult the equipment operating
manual and resight the detector farther out from the
spark, or away from possible reflection. It may be necessary to construct a barrier to block the ignition spark from
the detector view. Continue adjustments until the flame
signal due to ignition spark is less than 0.5 Vdc.
NOTE: The Honeywell Q624A and Q652A,B Solid State
Spark Generators prevent detection of ignition spark
when properly applied with C7027, C7035, C7044 or
C7061 Ultraviolet Flame Detectors. The Q624A and
Q652B are only for use with gas pilots; the Q652A is
only for oil applications.
Response To Other Ultraviolet Sources
Some sources of artificial light (such as incandescent or
fluorescent bulbs, mercury sodium vapor lamps and daylight)
produce small amounts of ultraviolet radiation. Under certain
conditions, an ultraviolet detector responds to these sources as
if it is sensing a flame. To check for proper detector operation,
check the Flame Failure Response Time (FFRT) and conduct
Safety Shutdown Tests under all operating conditions.
Flame Signal With Hot Combustion Chamber
(All Installations)
1.
2.
3.
4.
With all initial start-up tests and burner adjustments
completed, operate the burner until the combustion
chamber is at the maximum expected temperature.
Observe the equipment manufacturer warm-up instructions.
Recycle the burner under these hot conditions and
measure the flame signal. Check the pilot alone, the
main burner flame alone, and both together (unless
monitoring only the pilot flame when using an intermittent pilot, or only the main burner flame when using
DSI). Check the signal at both High and Low Firing Rate
positions and while modulating, if applicable.
Check the FFRT of the flame amplifier and relay module.
65-0229—2
7800 SERIES RELAY MODULES
5.
6.
7.
8.
9.
Lower the setpoint of the operating controller and
observe the time it takes for the burner flame to go out.
This should be within the maximum FFRT.
If the flame signal is too low or unsteady, check the
flame detector temperature. Relocate the detector if the
temperature is too high.
If necessary, realign the sighting to obtain the proper
signal and response time.
If the response time is still too slow, replace the Plug-In
Flame Signal Amplifier.
If the detector is relocated or resighted, or the amplifier
is replaced, repeat all required Checkout tests.
6.
SAFETY SHUTDOWN TESTS (ALL
INSTALLATIONS)
Perform these tests at the end of Checkout, after all other
tests are completed. If used, the external alarm should turn
on. Press the RESET pushbutton on the relay module to
restart the system.
1.
2.
3.
4.
5.
Opening a Pre-Ignition Interlock during the STANDBY or
PREPURGE period (only for RM7800, EC/RM7840,
RM7838B, EC7810, EC7820, EC/RM7830, EC/ RM7850).
a. *Pre-Ignition ILK* fault is displayed on the Keyboard
Display Module. Fault code 10 or 33 is displayed to
denote the fault.
b. Safety shutdown occurs.
Opening a Lockout Interlock during PREPURGE,
PILOT IGN, MAIN IGN or RUN period (only for
RM7800, EC/RM7840, RM7838B, EC7810, EC7820,
EC/RM7830, EC/RM7850).
a. *Lockout ILK* fault is displayed on the Keyboard
Display Module. Fault code 11 or 12 or 21 or 29 is
displayed to denote the fault.
b. Safety shutdown occurs.
Detection of flame 40 seconds after entry to STANDBY
from RUN, fault code 9. Detection of flame from 10 seconds
up to 30 seconds into PREPURGE time.
a. Simulate a flame to cause the flame signal voltage
level to be at least 1.25 Vdc for 40 seconds after
entry to STANDBY from RUN and also simulate a
flame signal for 10 seconds to 30 seconds for
PREPURGE.
b. *Flame Detected* fault is displayed on the Keyboard
Display Module. Fault code 9 or 15 or 18 is displayed
to denote the fault.
c. Safety shutdown occurs.
Failure to ignite pilot.
a. Close pilot and main fuel manual shutoff valve(s).
b. Cycle burner on.
c. Automatic pilot valve(s) should be energized but the
pilot cannot ignite.
d. *Pilot Flame Fail* fault is displayed on the Keyboard
Display Module. Fault code 28 is displayed four or ten
seconds, depending on the jumper configuration
selection for Pilot Flame Establishing Period (PFEP)
after the pilot valve(s) is energized to denote the fault.
e. Safety shutdown occurs.
Failure to ignite main (only interrupted pilot application).
a. Open the manual pilot valve(s); leave the main fuel
manual shutoff valve(s) closed.
b. Depress the RESET button.
c. Start the system.
65-0229—2
6
7.
d. The pilot should ignite and the flame signal should
be at least 1.25 Vdc but the main burner cannot light.
e. The flame signal should drop below 1.25 Vdc within
the FFRT of the amplifier and the relay module after
the interrupted pilot goes out.
f. *Main Flame Ign.* fault is displayed on the Keyboard Display Module. Fault code 19 is displayed to
denote the fault.
g. Safety shutdown occurs.
Loss of flame during RUN.
a. Open the main fuel manual shutoff valve(s) and
open manual pilot shutoff valve(s).
b. Depress the RESET button.
c. Start the system. Start-up should be normal and the
main burner should light normally.
d. After the sequence is in the normal RUN period for at
least ten seconds with the main burner firing, close
the manual main fuel shutoff valve(s) to extinguish
the main burner flame. (On intermittent pilot applications, also, close the pilot manual shutoff valve.)
e. The flame signal should drop below 1.25 Vdc within
the FFRT of the amplifier and the relay module after
the main flame and/or pilot goes out.
f. *Main Flame Fail* fault is displayed on the Keyboard
Display Module. Fault code 17 is displayed to
denote the fault.
g. Safety shutdown occurs. (EC/RM7890, EC/ RM7895,
RM7896 relay modules will recycle if jumper JR2 is
intact, then lock out on failure to light the pilot.)
Opening a Pre-Ignition Interlock after the first five
seconds of POSTPURGE.
a. Open the main fuel manual shutoff valve(s) and
open manual pilot shutoff valve(s).
b. Depress the RESET button.
c. *Pre-Ignition ILK* fault is displayed on the Keyboard
Display Module. Fault code 33 is displayed to
denote the fault.
d. Safety shutdown occurs.
IMPORTANT
If the relay module fails to shut down on any of these
tests, take corrective action; refer to Troubleshooting
and the relay module diagnostics and return to the
beginning of all Checkout tests.
When all Checkout tests are completed, reset all switches to
the original status.
TROUBLESHOOTING
System Diagnostics
Troubleshooting control system equipment failures is easier with
the relay module self-diagnostics and first-out annunciation. In
addition to an isolated spst alarm relay (audible annunciation),
the relay module provides visual annunciation by displaying a
fault code and fault or hold message at the S7800 Keyboard
Display Module (standard on RM7800 and RM7838A,B devices;
optional on all others). The relay module provides 127 diagnostic
messages for troubleshooting the system (see Table 3).
Self-diagnostics of the relay module enable it to detect and
annunciate both external and internal system problems. Fault
messages, such as interlock failures, flame failures and false
flame signals are displayed at the KDM, and annunciated at
the 7800 SERIES Relay Module by the ALARM LED.
7800 SERIES RELAY MODULES
The KDM displays a sequence status message indicating:
STANDBY, PURGE, PILOT IGN, MAIN IGN, RUN and
POSTPURGE. The selectable messages also provide visual
indication of current status and historical status of the equipment
such as: Flame Signal, Total Cycles, Total Hours, Fault History,
Diagnostic Information and Expanded Annunciator terminal
status (if used). With this information, most problems can be
diagnosed without extensive trial and error testing.
Table 2 provides the sequence and status hold messages.
Table 3 is a summary of all relay module fault messages, fault
codes, and troubleshooting suggestions. In addition,
Diagnostic Information and History Data are available to assist
in troubleshooting the relay module.
The relay module provides diagnostic information to aid the
service mechanic in obtaining information when troubleshooting the system. Information available in the Diagnostic
Information includes Device Type, Device Suffix, Software
Revision, Manufacturing Code, Flame Amplifier Type, Flame
Failure Response Time, Selectable Jumper Configuration
Status, Run/Test Switch Status and Terminal Status.
Diagnostic Information Index
The relay module monitors input/output terminals and can
display the status of the terminal at the KDM (see Table 2)
(example: Pilot Valve T8 1). See the applicable relay module
installation instructions for a complete terminal description
and number. The display shows the actual status of the
terminal. If voltage is detected at the terminal, 1 is displayed,
but if no voltage is detected at the terminal, 0 is displayed.
Historical Information Index
The relay module has nonvolatile memory that allows the Relay
Module to retain historical information for the six most recent
lockouts. Each of the six lockout files retains the cycle when the
fault occurred, the hour of operation when the fault occurred, a fault
code, a fault message and burner status when the fault occurred.
IMPORTANT
Some older relay modules cannot operate without a
KDM, extension cable assembly with KDM or a Data
ControlBus Module™ installed.
SERVICE NOTES:
1. If the KDM is scrambled, remove and reinstall the KDM,
and reset the 7800 Relay Module.
2. Reset the 7800 SERIES Relay Module by pressing the
RESET pushbutton on the 7800 SERIES Relay Module,
or pressing a remote reset pushbutton wired through
the KDM, Data ControlBus Module™ or Remote Reset
Module. A power-up reset causes an electrical reset of
the relay module but does not reset a lockout condition.
3. Use the access slots on the sides of the Q7800A,B to
check terminal voltage.
4. Maximum ambient operating temperature of a
C7012E,F; Series 1 through 6, is reduced to 125°F
because of the duty cycle operation of the relay module.
Table 2. Keyboard Display Module Sequence and Status Hold Messages.
Sequence
INITIATE mm:ss
Status
The Keyboard Display Module (KDM) indicates the burner status, INITIATE, a stabilization period for
the relay module to check for any fluctuations in ac line voltage inputs or control inputs on powerup or
during normal operation. The timing of the INITIATE period is either two seconds or ten seconds,
depending on the model, before entering STANDBY.
If the relay module is in an INITIATE HOLD status, the following conditions could exist:
INITIATE HOLD:
(AC Frequency/Noise)
The KDM indicates the burner status and that it is waiting for excess line noise to clear up, which
prevents sufficient reading of the line voltage inputs. The burner sequence does not advance into
STANDBY until the excess line noise ceases or a line frequency error occurs; this is caused by using
a 60 Hz device on a 50 Hz line, or vice versa on devices with a date code earlier than 9804.
INITIATE HOLD:
(AC Line Dropout)
The KDM indicates the burner status and that ac line power has momentarily dropped out. The burner
sequence does not advance into STANDBY until the ac line voltage has stabilized throughout the
INITIATE sequence.
INITIATE HOLD:
(AC Frequency)
The KDM indicates the burner status and that line frequency is faster than the expected value. The
burner sequence does not advance into STANDBY until the line frequency returns to the proper
value; this is perhaps caused by using a 60 Hz device on a 50 Hz line for devices with a date code
earlier than 9804.
INITIATE HOLD:
(Low Line Voltage)
The KDM indicates the burner status and that low line voltage (10% lower than rated voltage) has
occurred. The burner sequence does not advance into STANDBY until the line voltage is at a
sufficient level for proper operating parameters.
STANDBY
The KDM indicates the burner status, STANDBY. The burner can be placed in STANDBY by opening
the burner switch or if the operating controller indicates its setpoint is satisfied. If a demand is present
for burner operation, the burner sequence does not advance from STANDBY to PURGE until the
recycle limits close. If an Expanded Annunciator is connected, the display messages are enhanced.
If the relay module is in a STANDBY HOLD status, the following conditions could exist:
STANDBY HOLD:
F/G (Flame Detected)
The KDM indicates the burner status and that a flame is detected. A demand is present for burner
operation. The sequence does not advance to PREPURGE until the flame signal clears. If the flame
signal does not clear within 40 seconds, the relay module locks out.
STANDBY HOLD: T20
(Pre-Ignition Interlock)
The KDM indicates the burner status and that the Pre-Ignition Interlock is not closed. A demand is
present for burner operation but the burner sequence does not advance to PREPURGE until the PreIgnition Interlock proves closed. If this time exceeds a 30 second hold, the relay module locks out.
7
65-0229—2
7800 SERIES RELAY MODULES
Table 2. Keyboard Display Module Sequence and Status Hold Messages. (Continued)
Sequence
Status
STANDBY HOLD: T7
(Lockout Interlock)
The KDM indicates the burner status and that the Lockout Interlock is closed. A demand is present for
burner operation but the burner sequence does not advance to PREPURGE until the Lockout Interlock
proves open. If this time exceeds the 120 second hold, the relay module locks out.
STANDBY HOLD: T7
(Running Interlock) T17
for EC/RM7810, 7820,
7830, 7850 devices
The KDM indicates the burner status and that the Running Interlock is closed. A demand is present for
burner operation, but the burner sequence does not advance to PREPURGE until the Running Interlock
proves open. If this time exceeds the 120 second hold, the relay module locks out.
PURGE
The KDM indicates the burner status, PURGE, which is the period of time the blower motor is running
before the Ignition period. The timing of the PURGE period is selectable.
If the relay module is in a PURGE HOLD status, the following conditions could exist:
PURGE HOLD: T19
(High Fire Switch)
The KDM indicates the burner status and that the High Fire Switch is not closed. The firing rate motor
is driving to its PURGE rate position. If this time exceeds 4 minutes 15 seconds, the relay module
locks out.
PURGE DELAY: T19
(High Fire Switch
Jumpered)
The KDM indicates the burner status and that the High Fire Switch is jumpered. The High Fire Switch
is bypassed, welded or otherwise prematurely closed. The system automatically adds 30 seconds to
allow the firing rate motor additional drive time to reach or near the open damper position before
starting the PURGE sequence.
PURGE HOLD: TEST
(Run/Test Switch)
The KDM indicates the burner status and that the Run/Test Switch is in the TEST position. The
sequence does not continue until the Run/Test Switch is placed in the RUN position.
If the relay module is in a PURGE HOLD status, the following conditions could exist:
PURGE HOLD: T18
(Low Fire Switch
Jumpered)
The KDM indicates the burner status and that the Low Fire Switch is jumpered. The Low Fire Switch
is bypassed, welded or otherwise prematurely closed. The system automatically adds 30 seconds to
allow the firing rate motor additional drive time to reach or near the closed damper position before
starting the ignition sequence.
PURGE HOLD: F/G
(Flame Detected)
The KDM indicates the burner status and that a flame is detected. The burner sequence does not
advance through PREPURGE because a flame is detected as being present. The sequence holds
waiting for the flame signal to clear. If the time exceeds 30 seconds, the relay module locks out.
PURGE HOLD: T18
(Low Fire Switch)
The KDM indicates the burner status and that the Low Fire Switch is not closed. The firing rate motor
is driving to its Low Fire position in preparation for Ignition Trials. If this time exceeds 4 minutes 15
seconds, the relay module locks out.
PURGE HOLD: T7
(Running Interlock)
The KDM indicates the burner status and that the Running Interlock is not closed. The sequence
does not advance to Ignition until the Running Interlock proves closed. If this time exceeds 30
seconds, the relay module locks out.
PILOT IGN mm:ss
The KDM indicates the burner status, PILOT IGN, and the timing of the PILOT IGN trial begins, in seconds.
During this period, the relay module permits the pilot valve to open and the pilot flame to establish.
If the relay module is in a PILOT HOLD status, the following condition could exist:
PILOT HOLD: TEST
(Run/Test Switch)
The KDM indicates the burner status, PILOT IGN, and that the Run/Test Switch is in the TEST
position. The sequence does not continue until the Run/Test Switch is placed in the RUN position.
MAIN IGN mm:ss
The KDM indicates the burner status, MAIN IGN, and the timing of the MAIN IGN trial begins, in seconds.
During this period, the relay module permits the main valve to open and the main flame to establish.
RUN
The KDM indicates the burner status, RUN, which is the period of time after the Ignition Trials and
before the operating controller setpoint is reached. During this time, the burner is firing under control
of the firing rate control.
If the relay module is in a RUN HOLD status, the following condition could exist:
RUN LOWFIRE: TEST
(Run/Test Switch)
The KDM indicates the burner status and that the Run/Test Switch is in the TEST position. Normal
modulation or operation does not continue until the Run/Test Switch is placed in the RUN position.
POSTPURGE mm:ss
The KDM indicates the burner status, POSTPURGE, which is the period of time after the RUN period
when the blower motor continues to run. The timing of the POSTPURGE period is fifteen seconds.
Waiting for connection... The KDM has power but is waiting to receive a signal from the relay module to continue operation.
RESET/ALARM TEST
The KDM indicates the burner status, RESET/ALARM TEST. This condition indicates that the reset
button is pressed. If it is held for more than four seconds, the alarm output is energized. The alarm
output is de-energized when the reset button is released.
Additional sequence status information when an expanded annunciator is connected to the relay module:
BURNER OFF: T6
(Burner Switch)
STANDBY
65-0229—2
The KDM indicates the Burner Switch is not closed. The burner sequence does not advance to
PREPURGE until the Burner Switch closes.
8
7800 SERIES RELAY MODULES
Table 2. Keyboard Display Module Sequence and Status Hold Messages. (Continued)
Sequence
Status
STANDBY
The KDM indicates the burner status, STANDBY, and that the Operating Control is not closed. The
burner sequence does not advance to PREPURGE until the Operating Control closes.
STANDBY HOLD: T6
(EA Hold Message)
The KDM indicates the burner status, STANDBY, and that a limit is not closed. The burner sequence
does not advance to PREPURGE until one or all limits close downstream from the Operating Control.
STANDBY HOLD: T6
(Circuit Fault)
The KDM indicates the burner status, STANDBY, and that the control input is not closed. The burner
sequence does not advance to PREPURGE until the control input closes.
NOTE: Normal sequences are in bold type, while abnormal sequences are in regular type. This table is for all 7800 SERIES
Relay Modules, so all listed steps may not apply to the unit installed.
Table 3. Hold and Fault Message Summary.
Fault Code
Fault 1
*No Purge Card*
System Failure
No card is plugged into the
purge card slot.
Fault 2
Excess noise or device
*AC Frequen/Noise* running on slow ac.
Recommended Troubleshooting
1. Make sure the purge card is seated properly.
2. Inspect the purge card and connector on the relay module for damage or
contaminants.
3. Reset and sequence the relay module.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the relay module.
6. If the fault persists, replace the relay module.
1. Check the relay module and display module connections.
2. Reset and sequence the relay module.
3. Check the relay module power supply and make sure that both frequency and voltage meet the specifications.
4. Check the backup power supply, as appropriate.
Fault 3
*AC Line Dropout*
Ac line dropout detected.
Fault 4
*AC Frequency*
Device running on fast ac.
Fault 5
*Low Line Voltage*
Low ac line detected.
Fault 6
*Purge Card Error*
Purge card timing changed
since card was initially read.
1. Make sure the purge card is seated properly.
2. Inspect the purge card and connector on the relay module for damage or
contaminants.
3. Reset and sequence the relay module.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the relay module.
6. If the fault persists, replace the relay module.
Fault 7
*Flame Amplifier*
Flame sensed when flame
not present.
1. Check wiring and correct any errors. Make sure that flame sensor
wires are in separate conduits. Check for noise coupling into the flame
detector leadwires.
2. Make sure that flame detector and flame amplifier are compatible.
3. Remove the flame amplifier and inspect connections. Reseat the amplifier.
4. Reset and sequence the relay module.
5. If the code reappears, replace the amplifier and/or the flame detector.
6. If the fault persists, replace the relay module.
Fault 8
Flame sensed when no
*Flame Amp/Shutr* signal expected during
shutter-check or
Ampli-Check versions.
Fault 9
*Flame Detected*
Flame sensed when shutter
open and no flame is
expected during STANDBY.
1. Check that flame is not present in the combustion chamber; correct
any errors.
2. Check wiring and correct any errors. Make sure that flame sensor
wires are in separate conduits. Check for noise coupling into flame
detector leadwires.
3. Remove the flame amplifier and inspect its connections.
4. Reseat the amplifier. Reset and sequence the relay module.
5. If the code reappears, replace the amplifier and/or the flame detector.
6. If the fault persists, replace the relay module.
Fault 10
*Pre-Ignition ILK*
Pre-Ignition Interlock fault
during STANDBY *EC/
RM7800, 7840, 7838B only).
1.
2.
3.
4.
Check wiring and correct any errors.
Check Pre-Ignition Interlock switches to assure proper functioning.
Check fuel valve operation.
Reset and sequence the relay module; monitor the Pre-Ignition Interlock status.
5. If the code persists, replace the relay module.
9
65-0229—2
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
System Failure
Recommended Troubleshooting
Fault 11
*Running ILK On*
Running Interlock powered
at improper sequence point.
Fault 12
*Lockout ILK On*
Lockout Interlock powered at
improper point in sequence.
Fault 13
*Airflow Sw. On*
Combustion airflow interlock
fault during STANDBY.
Fault 14
*High Fire Sw.*
High Fire Interlock Switch
failure to close during
PREPURGE.
1. Check wiring and correct any errors.
2. Reset and sequence the relay module.
3. Use either the manual motor potentiometer to drive the motor to the High
Fire position or use the Run/Test Switch option, if available. Sequence to
Prepurge drive to High Fire and place in the Test position. Adjust the High
Fire Switch while in this state to make sure that it closes properly.
4. Measure the voltage between terminal 19 and G (ground) while in the
Prepurge drive to High Fire state. Line supply voltage should be
present. If not, the switch adjustment is incorrect and/or the switch is
defective and needs replacing.
5. Reset and sequence the relay module. If line supply voltage was
present between the High Fire Switch and terminal 19, and the fault
still persists, replace the relay module.
Fault 15
*Flame Detected*
Flame sensed when no
flame is expected during
STANDBY.
1. Check that the flame is not present in the combustion chamber; correct
any errors.
2. Make sure that the flame amplifier and flame detector are compatible.
3. Check wiring and correct any errors.
4. Remove the flame amplifier and inspect the connections. Reseat the amplifier.
5. Reset and sequence the relay module.
6. If the code reappears, replace the amplifier and/or the flame detector.
7. If the fault persists, replace the relay module.
Fault 16
*Flame-Out Timer*
No flame detected during
Pilot Flame Establishing
Period.
1. Measure the flame signal. If one exists, make sure it meets specifications.
2. Make any necessary burner adjustments using manufacturer instructions.
Make sure that the flame amplifier and flame detector are compatible.
3. If the code reappears, replace the amplifier and/or the flame detector.
4. If the fault persists, replace the relay module.
Fault 17
*Main Flame Fail*
Main flame failure during
RUN after flame is
established and on for at
least 10 seconds.
1. Inspect the main fuel valve(s) and connection(s).
2. Make sure that the fuel pressure is high enough to supply fuel to the
combustion chamber.
3. Check the flame detector sighting for adequate flame signal throughout the burner firing rate.
Fault 18
*Flame Detected*
Flame sensed when shutter
is open and no flame is
expected during
PREPURGE.
1. Check that flame is not present in the combustion chamber. Correct
any errors.
2. Make sure that the flame amplifier and flame detector are compatible.
3. Check the wiring and correct any errors. Make sure F and G wires are
in individual conduits and protected from stray noise pickup.
4. Remove the flame amplifier and inspect the connectors. Reseat the
flame amplifier.
5. Reset and sequence the relay module.
6. If the code reappears, replace the flame amplifier and/or the flame detector.
7. If the fault persists, replace the relay module.
Fault 19
*Main Flame Ign.*
Flame was lost during MFEP
or the first 10 seconds of the
RUN state.
1. Inspect the main fuel valve(s) and connection(s).
2. Make sure that the fuel pressure is high enough to supply fuel to the
combustion chamber.
3. Make sure the flame detector is positioned to obtain the required
flame signal strength; reset and recycle.
65-0229—2
1. Check wiring to make sure that interlocks are connected properly
between terminals 6 and 7. Correct any errors.
2. Reset and sequence the relay module.
3. If the fault persists, measure the voltage between terminals 6 and G (ground),
then terminals 7 and G. If there is line supply voltage present at terminal 6
when the controller is off, the controller switch may be bad or is jumpered.
4. If steps 1 through 3 are correct and there is line supply voltage present
at terminal 7 when the controller is closed and the fault persists, check
for a welded or jumpered Running Interlock, Lockout Interlock, or Airflow Switch. Correct any errors.
5. If steps 1 through 4 are correct and the fault persists, replace the relay
module.
10
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
System Failure
Recommended Troubleshooting
Fault 20
*Low Fire Sw. Off*
Low Fire Interlock switch
failure to close during
PREPURGE.
1. Check wiring and correct any errors.
2. Reset and sequence the relay module.
3. Use either the manual motor potentiometer to drive the motor to the
Low Fire position or use the Run/Test Switch option, if available.
Sequence to Prepurge drive to Low Fire and place in the Test position.
Adjust the Low Fire Switch to make sure that it closes properly.
4. Measure the voltage between terminal 18 and G (ground) while in the
Prepurge drive to Low Fire state. Line supply voltage should be
present. If not, the switch adjustment is incorrect and/or the switch is
defective and needs replacing.
5. Reset and sequence the relay module. If line supply voltage was
present between the Low Fire Switch and terminal 18, and the fault
still persists, replace the relay module.
Fault 21
*Running ILK*
Running Interlock fault
during PREPURGE.
Fault 22
*Lockout ILK*
Lockout Interlock fault during
PREPURGE.
Fault 23
*Airflow Switch*
Combustion airflow interlock
fault during PREPURGE.
1. Check wiring; correct any errors.
2. Inspect the fan; make sure there is no blockage of the air intake and
that it is supplying air.
3. Make sure the Interlock Switches are working properly and that all
switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE (place the
Run/Test Switch in the Test position, if available). Measure the voltage
between terminals 7 and G (ground). Line voltage should be present.
5. If steps 1 through 4 are correct and the fault persists, replace the relay
module.
Fault 24
*Call Service*
The flame interlock (relay
module) was on when it
should be off.
Fault 25
*Call Service*
The flame interlock (relay
module) was off when it
should be on.
1. Check for F leadwire routing. Make sure routing is in its conduit and
isolated from noise-producing circuits.
Fault 26
The Manual Open Valve
*Man-Open Sw. Off* Switch was off when it
should be on (RM7838B
only).
1. Check wiring and correct any errors.
2. Make sure that the Manual Open Valve Switch is fully open.
3. Make sure that the Manual Open Valve Switch is functioning properly
and that the switch contacts are free from contaminants.
4. Reset and sequence the relay module.
5. Make sure that the Manual Open Valve Switch provides an electrical path
when closed. Verify that the relay module is receiving power at terminal 17.
6. If steps 1 through 5 are correct and the fault persists, replace the relay
module.
Fault 27
*Start Switch On*
Start Switch was on during
PREPURGE (RM7838A,
RM7838B only).
1. Start Switch held on too long.
2. Check wiring; verify that Start Switch is correctly connected.
3. Make sure that the Start Switch is functioning properly and that the
switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE; set the
Run/Test Switch to Test.
5. Make sure there is no power at terminal 6 during PREPURGE.
6. If steps 1 through 3 are correct and the fault persists, replace the relay
module.
Fault 28
*Pilot Flame Fail*
Pilot flame failure.
1.
2.
3.
4.
Check pilot valve wiring and operation. Correct any errors.
Check fuel supply.
Check pilot pressure and repeat pilot turndown test.
Check ignition transformer electrode, flame detector, flame detector
sighting and flame amplifier.
5. If steps 1 through 4 are correct and the fault persists, replace the relay
module.
11
65-0229—2
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
System Failure
Recommended Troubleshooting
Fault 29
*Lockout ILK*
Lockout Interlock fault.
1. Check wiring; correct any errors.
2. Inspect the fan; make sure that there is no blockage of the air intake
and that it is supplying air.
3. Make sure that the Lockout Interlock Switches are working properly
and that all switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE (place the
Run/Test Switch in the Test position, if available). Measure the voltage
between terminals 7 and G (ground). Line voltage should be present.
5. If steps 1 through 4 are correct and the fault persists, replace the relay
module.
Fault 30
*Running ILK*
Running Interlock fault.
1. Inspect the Running Interlocks, including the Airflow Switch, and the
connections.
2. Make sure that the Running Interlocks, including the Airflow Switch, are
functioning properly and that switch contacts are free of contaminants.
3. Reset and sequence the relay module to PREPURGE. Set the
Run/Test Switch, if available, to Test. Measure the voltage between
terminal 7 and G (ground). Line voltage should be present.
4. If steps 1 through 3 are correct and the fault persists, replace the relay
module.
Fault 31
*Low Fire Sw. Off*
Low Fire Interlock Switch
failure to close during RUN
(RM7838B only).
1. Check wiring; correct any errors.
2. Reset and sequence the relay module.
3. Use either the manual motor position to drive the motor to the Low Fire
position, or use the Run/Test Switch option, if available. Sequence to
Run drive to Low Fire and place in the Test position. Adjust the Low Fire
Switch while in this state to make sure it is closing properly.
4. While in Run, drive to Low Fire state, measure the voltage between terminal
18 and G (ground). Line voltage should be present. If not, the switch adjustment is incorrect and/or the switch is defective and needs replacement.
5. Reset and sequence the relay module. If line voltage was present
between the Low Fire Switch and terminal 18 and the fault persists,
replace the relay module.
Fault 32
*Airflow Switch*
Combustion Airflow Interlock
fault.
1. Check wiring; correct any errors.
2. Inspect the fan; make sure there is no blockage of the air intake and it
is supplying air.
3. Make sure the Airflow Interlock Switches are working properly and all
switch contacts are free of contaminants.
4. Reset and sequence the relay module to PREPURGE. Place the
Run/Test Switch in the Test position, if available. Measure the voltage
between terminals 7 and G (ground). Line voltage should be present.
5. If steps 1 through 4 are correct and the fault persists, replace the relay
module.
Fault 33
*Pre-Ignition ILK*
Pre-Ignition interlock fault.
1. Check wiring; correct any errors.
2. Inspect the Pre-Ignition Interlock switches and make sure they function properly.
3. Check fuel valve operation. Valve must close within five seconds.
4. Reset and sequence the relay module.
5. During STANDBY or PREPURGE, measure the voltage between terminal
20 and G (ground). For EC/RM7810, 7820, 7830, 7850, check voltage
between terminal 17 and G. Line voltage should be present. If not, the
Pre-Ignition Interlock switches could be defective and need replacing.
6. If the fault persists, replace the relay module.
Fault 34
*Control On*
CTL input was energized at
the wrong time for the relay
module. This fault implies a
field wiring error.
1. Check wiring; correct any errors.
2. Reset and sequence the relay module.
3. If fault persists, replace the relay module.
65-0229—2
12
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
System Failure
Recommended Troubleshooting
Fault 35
*Call Service*
Safety relay was off when it
should be on or a fuse has
blown.
Fault 36
*Call Service*
Main valve terminal was off
when it should be on.
Fault 37
*Call Service*
Pilot (ignition) valve terminal
was off when it should be on.
Fault 38
*Call Service*
Ignition terminal was off
when it should be on.
Fault 39
*Call Service*
V2S valve terminal (usually
terminal 21) was off when it
should be on.
Fault 40
*Call Service*
Safety relay was on when it
should be off.
Fault 41
*Main Valve On*
Main valve terminal was on
when it should be off.
Fault 42
*Pilot Valve On*
Pilot (ignition) valve terminal
was on when it should be off.
Fault 43
*Ignition On*
Ignition terminal was on
when it should be off.
Fault 44
*Pilot Valve 2 On*
V2S valve terminal, used as
a pilot, is on when it should
be off.
Fault 45
*Low Fire Sw. Off*
Low Fire Interlock switch
failure to close or stay
closed.
1. Check wiring; correct any errors.
2. Reset and sequence the relay module.
3. Use either the manual motor position to drive the motor to the Low Fire
position, or use the Run/Test Switch option, if available. Sequence to
Run, drive to Low Fire and place in the Test position. Adjust the Low
Fire Switch while in this state to make sure it is closing properly.
4. While in Run, drive to Low Fire state, measure the voltage between terminal
18 and G (ground). Line voltage should be present. If not, the switch adjustment is incorrect and/or the switch is defective and needs replacement.
5. If steps 1 through 4 are correct and the fault still persists, replace the
relay module.
Fault 46
*Flame Amp Type*
This fault indicates:
a. The Flame Failure
Response Time (FFRT) or
TYPE input from the
amplifier changed while the
device was powered; or
b. A standard amplifier was
used in a pilot valve
application; or
c. A three-second FFRT
Amplifier was used with the
relight option on the RM7890
Relay Module.
1. Remove power to the device.
2. Reseat the flame amplifier and reset and sequence the relay module.
3. For EC/RM7890 only; make sure that Jumper JR2 is completely
clipped if a three-second FFRT amplifier is being used. If Jumper JR2
is intact (relight option is selected), use 0.8 second FFRT amplifier.
4. For RM7838B only; make sure that a Shutter Check Flame Amplifier
is being used with the Pilot Valve Hold option selected.
Fault 47
The configuration jumpers
*Jumpers Changed* differ from the sample taken
at startup.
1. Reset and sequence the relay module. If fault repeats, replace relay
module, but be sure to test for excessive loads on appropriate terminals
described by fault code.
2. If fault does not repeat on next cycle, check for electrical noise being coupled into the relay module through the loads on appropriate terminals
described by the fault code.
3. If fault persists, replace the relay module.
WARNING
Explosion Hazard.
Can cause explosion, serious injury or death.
1. Remove system power, turn off fuel supply.
2. Check for wiring errors that could provide power to terminals
described by the fault. Correct any errors.
3. Re-power system; reset and sequence the relay module.
4. If fault persists, replace the relay module.
5. When fault is corrected, turn on fuel supply.
1. Inspect the jumper connections. Make sure that clipped jumpers are
completely removed.
2. Reset and sequence the relay module.
3. If fault persists, replace the relay module.
13
65-0229—2
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
Fault 48
*Delayed MV On*
System Failure
Recommended Troubleshooting
V2S valve terminal, used as
a delayed main valve, was
on when it should be off.
Fault 49
*Man-Open Sw.
On.*
The manual open switch
was on when it should be off.
Fault 50
*Jumpers Wrong*
The sequence logic detected a
combination of jumpers that is
illegal for the sequence e.g., if it
is correct to clip Jumper JR1 or
Jumper JR2, but not both, this
fault would be used when both
are clipped (RM7888 only).
WARNING
Explosion Hazard.
Can cause explosion, serious injury or death.
1. Remove system power, turn off fuel supply.
2. Check wiring; correct any errors.
3. Inspect the V2S Fuel Valve and its connections. Make sure the
switch is working correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If fault persists, replace the relay module.
WARNING
Explosion Hazard.
Can cause explosion, serious injury or death.
1. Remove system power, turn off fuel supply.
2. Check wiring; correct any errors.
3. Inspect the Manual-Open Switch and its connections. Make sure
the switch is working correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If fault persists, replace the relay module.
1. Inspect the jumpers and refer to the installation instructions for compatible jumper configurations.
2. Make sure that clipped jumpers are completely removed.
3. Reset and sequence the relay module.
4. If fault persists, replace the relay module.
Fault 51
Flame signal value is too
*Flame Too Strong* high to be valid.
1.
2.
3.
4.
5.
6.
7.
Fault 52
*Call Service*
Pilot Valve 2 (terminal 21)
was off when it should be on.
1. Inspect terminal 21 and connections.
2. Make sure that the valve is operating properly.
3. Reset and sequence the relay module. If the fault persists, replace the
relay module.
Fault 53
*Lockout Switch*
Lockout Input fault (EC/
RM7810, 7820, 7830, 7850
only).
1.
2.
3.
4.
Fault 54
*Comb. Pressure*
Combustion pressure switch
fault (Fulton pulse only).
1.
2.
3.
4.
Fault 55
Purge fan switch is on when
*Purge Fan Sw. On* it should be off (Fulton pulse
only).
65-0229—2
Make sure that flame detector and flame amplifier are compatible.
Remove the flame amplifier and inspect the connections.
Reset the flame amplifier. Reset and sequence the relay module.
Check the flame detector sighting position, reset and cycle.
Verify that no ignition noise is present in the F lead due to wire routing.
Measure the flame strength. Verify it meets specifications.
If not, refer to the flame amplifier and/or flame detector checkout procedures.
If the code reappears, replace the flame amplifier and/or the flame detector.
8. If the fault persists, replace the relay module.
Check wiring; correct any errors.
Inspect the Lockout Switch to make sure it is working properly.
Reset and sequence the relay module.
During STANDBY or PREPURGE, measure the voltage between
terminal 20 and G (ground). Supply voltage should be present. If not,
the lockout switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
Check wiring; correct any errors.
Inspect the Combustion Pressure Switch to make sure it is working correctly.
Reset and sequence the relay module.
During STANDBY or PREPURGE, measure the voltage between
terminal 20 and G (ground). Supply voltage should be present. If not,
the Combustion Pressure Switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
1. Check wiring; correct any errors.
2. Inspect the Purge Fan Switch terminal 18 and its connections. Make
sure the switch is working correctly and is not jumpered or welded.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
14
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
Fault 56
*Block Intake*
System Failure
Block intake fault (Fulton
pulse only).
Fault 57
Purge Fan Switch is off
*Purge Fan Sw. Off* when it should be on (Fulton
pulse only).
Recommended Troubleshooting
1.
2.
3.
4.
Check wiring; correct any errors.
Inspect the Block Intake Switch and make sure it is working properly.
Reset and sequence the relay module.
During PREPURGE, measure the voltage between terminal 7 and G
(ground). Supply voltage should be present. If not, the Block Intake
Switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
1. Inspect the Prepurge Fan Switch terminal 18 and the connections.
2. Make sure the switch is working properly. Reset and sequence the
relay module.
3. If the fault persists, replace the relay module.
Faults 58–66
*Call Service*
Unused faults.
—
Fault 67
*AC Phase*
L1 and L2 miswired/
exchanged (EC/RM7810,
7820, 7830, 7850 only).
1. Check L1 and L2 for proper line phasing.
Fault 68
*Pre-Ignition ILK*
Pre-Ignition Interlock fault.
1. Check wiring; correct any errors.
2. Inspect the Pre-Ignition Interlock switches and make sure they work
properly.
3. Check fuel valve operation. Valve must close within five seconds.
4. Reset and sequence the relay module.
5. During STANDBY or PREPURGE, measure the voltage between terminal 17 and G (ground). Supply voltage should be present. If not, the
Pre-ignition Interlock switches are defective and need replacing.
6. If the fault persists, replace the relay module.
Fault 69–70
*Call Service*
Unused faults.
Fault 71
*Dynamic LFS*
Low Fire Switch closed, High
Fire Switch must be open
(EC/RM7850 only).
1. Check firing rate position switches (usually in Modutrol® Motor) for
proper operation.
2. Check wiring, correct any errors.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 71
*Limits Complete*
Limit input (terminal 7) is off
when it should be on
(RM7888 only).
1.
2.
3.
4.
Fault 72
*Dynamic HFS*
High Fire Switch closed; Low
Fire Switch must be open
(EC/RM7850 only).
1. Check firing rate position switches (usually in Modutrol® Motor) for
proper operation.
2. Check wiring, correct any errors.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 72
*Spec.Func.2*
Special Function 2 Input
(terminal 17) is off when it
should be on.
1. Check operation of Special Function 2 of PLC.
2. Check electrical connection to terminal 17 of wiring subbase and confirm
presence of supply power when Special Function 2 is activated.
3. Reset relay module.
4. If the fault persists, replace the relay module.
Fault 73
*Spec.Func.3*
Special Function 3 Input
(terminal 19) is off when it
should be on.
1. Check operation of Special Function 3 of PLC.
2. Check electrical connection to terminal 19 of wiring subbase and confirm
presence of supply power when Special Function 3 is activated.
3. Reset relay module.
4. If the fault persists, replace the relay module.
Fault 75
*Flame Proven
Feedback*
Flame Indication Feedback
(terminal 21) either on when
it should be off or off when it
should be on.
1. Remove wire to terminal 21 and reset relay module.
2. If the fault persists, replace relay module.
3. Reconnect wire to terminal 21. If the fault returns, verify wiring.
Fault 76–87
*Accessory Fault*
—
—
Check limits to make sure they are satisfied after resetting.
Check electrical connections to terminal 7 of wiring subbase.
Reset relay module.
If the fault persists, replace the relay module.
—
15
65-0229—2
7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary. (Continued)
Fault Code
System Failure
Recommended Troubleshooting
Fault 88
*Accessory Fault*
T17 powered without Valve
Proving feature setup.
1. Follow Valve Proving Selection Setup in Appendix B on selected
Relay Module.
2. If No Valve Proving (NEVER) is required, connect controller (Demand)
to terminal 6.
Fault 89
*Accessory Fault*
T6 and T17 powered at the
same time.
1. Correct wiring error.
Fault 90
*Accessory Fault*
T7 opens on RM7890 with
VPS Feature.
1. Determine what interrupted terminal 7.
2. Correct any wiring issues.
3. Reset Relay Module.
Faults 91-93
*Accessory Fault
—
—
Fault 94–104
*Call Service*
—
—
Fault 105
*Call Service*
Relay Module self-test
failure.
Fault 106 *Call
Service*
Relay Module self-test
failure.
Fault 107
*Call Service*
Relay Module flame signal
crosscheck failure.
Fault 109
*Call Service*
Negative cycle test failed,
earth ground absent or line
voltage phasing improper.
1. Make sure a good earth ground connection exists at the installation
site and all earth ground connections are complete and correct.
2. Make sure the relay module and all loads operate at the same line
voltage phase.
3. Reset and sequence the relay module.
4. If the fault persists, replace the relay module.
Fault 110
*Call Service*
The configuration jumpers
differ from stored values.
1. Inspect the jumper connections. Make sure they match the original
selection and clipped jumpers are completely removed.
2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
4. Configuration jumpers must be selected prior to 200 hours of operation.
If configuration jumpers are changed after 200 hours of operation, lockout 110 occurs. Relay module cannot be reset and must be replaced.
Fault 111
*Call Service*
Relay Module configuration
jumper test failure.
1. Inspect the jumper connections. Make sure they match the original
selection and clipped jumpers are completely removed.
2. Reset and sequence the relay module.
3. If the fault persists, replace the relay module.
Fault 112–126
*Call Service*
Relay Module self-test
failure.
1. Reset and sequence the relay module.
2. If the fault persists, replace the relay module.
Fault 127
*Call Service*
Safety relay feedback circuit
was in an improper state.
1. Reset and sequence the relay module.
2. If the fault persists, replace the relay module.
1. Reset and sequence the relay module.
2. If the fault reappears, remove power from the relay module and
reapply the power; reset and sequence the relay module.
3. If the fault persists, replace the relay module.