■ Features
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage
■ Applications
Industrial control system
Factory automation
Electro-mechanical apparatus
/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
■ Description
NDR-480 is one economical slim 480W Din rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 85.5mm in width, which allows space saving inside the
c a b i n e t s . T h e e n t i r e s e r i e s a d o p t s th e f u l l r a n g e AC i n p u t f r o m 9 0 V A C t o 2 6 4 V A C a n d c o n f o r m s t o
EN61000-3-2, the norm the European Union regulates for harmonic current.
NDR-480 is designed with metal housing that enhances the unit's power dissipation. With working efficiency
up to 92.5%, the entire series can operate at the ambient temperature between -20℃ and 70℃ under air
convection. It is equipped with constant current mode for over-load protection, fitting various inductive
or capacitive applications. The complete protection functions and relevant certificates for industrial control
apparatus (UL508, TUV EN60950-1, and etc.) make NDR-480 a very competitive power supply solution
for industrial applications.
■ Model Encoding
NDR - 480 - 24
Output voltage
Output wattage
Series name
File Name:NDR-480-SPEC 2015-05-23
NDR-480
480W Single Output Industrial DIN RAIL
series
SPECIFICATION
MODEL
OUTPUT
NDR-480-24
NDR-480-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
RIPPLE & NOISE (max.) Note.2 150mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
±1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 ±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±1.0%
SETUP, RISE TIME
1500ms, 100ms/230VAC
16ms/230VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
INPUT
Note.4 90 ~ 264VAC
47 ~ 63Hz
PF>0.98/115VAC, PF>0.94/230VAC at full load
EFFICIENCY (Typ.)
92.5%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
4.8A/115VAC
20A/115VAC
LEAKAGE CURRENT
<2mA / 240VAC
105 ~ 130% rated output power
92.5%
2.4A/230VAC
35A/230VAC
Protection type : Constant current limiting, unit will shut down after 3 sec., re-power on to recover
OVER VOLTAGE
29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP.
-20 ~ +70℃ (Refer to "Derating Curve")
EMC IMMUNITY
MTBF
DIMENSION
PACKING
NOTE
16ms/115VAC at full load
127 ~ 370VDC
POWER FACTOR (Typ.)
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
OTHERS
±1.0%
3000ms, 100ms/115VAC at full load
FREQUENCY RANGE
OVERLOAD
PROTECTION
±0.5%
56 ~ 65V
20 ~ 95% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03%/℃ (0 ~ 50℃)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
146.8K hrs min. MIL-HDBK-217F (25℃)
85.5*125.2*128.5mm (W*H*D)
1.5Kg; 8pcs/13Kg/0.9CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
5. Derating may be needed under low input voltage. Please check the derating curve for more details.
6. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:NDR-480-SPEC 2015-05-23
NDR-480
480W Single Output Industrial DIN RAIL
series
Block Diagram
PFC fosc : 85KHz
PWM fosc : 65KHz
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.C.P.
UVP
O.L.P.
FG
PFC
CONTROL
DETECTION
CIRCUIT
PWM
CONTROL
O.V.P.
O.T.P.
Derating Curve
Output derating VS input voltage
100
100
90
80
80
70
50
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
40
50
AMBIENT TEMPERATURE (℃)
60
70 (VERTICAL)
60
50
40
90
100
125
135
145
155 165
175
180
200
230
264
INPUT VOLTAGE (V) 60Hz
File Name:NDR-480-SPEC 2015-05-23
NDR-480
480W Single Output Industrial DIN RAIL
series
Mechanical Specification
Case No.984D
Unit:mm
Top View
85.5
128.5
12 3 4
125.2
39
TB2
DC OK
+
Side View
+V ADJ
TB1
1 2 3
Front View
Side View
Terminal Pin No. Assignment (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N or DC AC/L or DC +
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT-V
Bottom View
Installation Instruction
35
This series fits DIN-RAIL TS35/7.5 or TS35/15.
For installation details, please refer to the USER MANUAL on
http://www.meanwell.com/search/NDR-480/NDR_manual.pdf
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
Back View
File Name:NDR-480-SPEC 2015-05-23