MEANWELL SDR-480P

480W Single Output Industrial DIN RAIL with PFC and Parallel Function
SDR-480P series
Features :
Current sharing up to 3840W(7+1)
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.94
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
150% peak load capability
3 years warranty
SE
PQ
M
IF
47
GL
SPECIFICATION
MODEL
OUTPUT
SDR-480P-24
SDR-480P-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
PEAK CURRENT
30A
15A
PEAK POWER Note.6
720W (3sec.)
RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.2%
LINE REGULATION
0.5%
LOAD REGULATION
1.0%
Note.7 90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.94/230VAC
EFFICIENCY (Typ.)
94%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
5A/115VAC
40A/115VAC
127 ~ 370VDC
0.99/115VAC at full load
2.5A/230VAC
80A/230VAC
<0.6mA / 240VAC
LEAKAGE CURRENT
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
56 ~ 65V
29 ~ 33V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
OVERLOAD
PROTECTION OVER VOLTAGE
105
OVER TEMPERATURE
FUNCTION
3000ms, 150ms/115VAC at full load
14ms/230VAC at full load
HOLD UP TIME (Typ.)
INPUT
1.0%
1500ms, 150ms/230VAC
SETUP, RISE TIME
VOLTAGE RANGE
0.5%
5
(TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
Please see the Function Manual
CURRENT SHARING
WORKING TEMP.
WORKING HUMIDITY
Note.5 -25 ~ +70
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
(Refer to output load derating curve)
20 ~ 95% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25
SAFETY & ISOLATION RESISTANCE
Compliance
to EN55022 (CISPR22) Class B
EMI
CONDUCTION
&
RADIATION
EMC
(Note 4)
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
O/P-DC OK:0.5KVAC
/ 70% RH
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A , SEMI F47, GL approved
112.9Khrs min. MIL-HDBK-217F (25 )
85.5*125.2*128.5mm (W*H*D)
1.6Kg; 8pcs/13.8Kg/0.9CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:SDR-480P-SPEC 2010-12-07
480W Single Output Industrial DIN RAIL with PFC and Parallel Function
SDR-480P series
Mechanical Specification
Unit:mm
128.5
Case No.984A
125.2
TB2
+
1
2
3
DC OK
85.5
DC OK
+V ADJ
TB1
1
2
3
4
5
6
7
8
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
5,6
7
8
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Assignment
DC OUTPUT +V
DC OUTPUT -V
Relay Contact
P+ (currene share)
P- (currene share)
Block Diagram
DC OK
I/P
EMI FILTER
&
RECTIFIERS
POWER
SWITCHING
PFC
CIRCUIT
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
FG
PFC
CONTROL
O.L.P.
PWM & PFC
CONTROL
DETECTION
CIRCUIT
O.V.P.
DC OK Relay Contact
Contact Close
PSU turns on / DC OK.
Contact Open
PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
File Name:SDR-480P-SPEC 2010-12-07
480W Single Output Industrial DIN RAIL with PFC and Parallel Function
SDR-480P series
Peak Loading
(1)
(2)
720W
720W
480W
240W
50 sec.
3 sec.
15 sec. 3 sec.
Derating Curve
Output derating VS input voltage
100
150
90
For 3 sec. (typ.)
120
80
70
LOAD (%)
LOAD (%)
100
Continuous
80
60
60
50
40
-25
0
10
20
30
40
50
60
70 (VERTICAL)
90
100
AMBIENT TEMPERATURE ( )
110
135
155
230
264
INPUT VOLTAGE (V) 60Hz
Function Manual
1. Current sharing
(1)Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel) :
(2)The voltage difference among each output should be minimized that less than 2% is required.
(3)The total output current must not exceed the value determined by the following equation (Output current at parallel operation)
=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 8 units is the maximum, please consult the manufacture for other applications.
(5) When in parallel operation, the minimum output load should be greater than 3% of total output load.
(Min. load > 3% rated current per unit x number of unit)
+
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
-
LOAD
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
File Name:SDR-480P-SPEC 2010-12-07