MEANWELL SDR-240-48

SDR-240 series
240W Single Output Industrial DIN RAIL with PFC Function
Features :
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
SE
PQ
M
IF
SPECIFICATION
Marine
MODEL
OUTPUT
SDR-240-24
SDR-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
PEAK CURRENT
15A
7.5A
PEAK POWER Note.6
360W (3sec.)
RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
LOAD REGULATION
1.0%
0.5%
1.0%
SETUP, RISE TIME
1500ms, 60ms/230VAC
HOLD UP TIME (Typ.)
20ms/230VAC
VOLTAGE RANGE
88 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
0.93/230VAC
POWER FACTOR (Typ.)
INPUT
EFFICIENCY (Typ.)
GL
47
3000ms, 60ms/115VAC at full load
20ms/115VAC at full load
124 ~ 370VDC
0.99/115VAC at full load
Note.8 94%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
2.6A/115VAC
33A/115VAC
1.3A/230VAC
65A/230VAC
<1mA / 240VAC
Normally works within 110 ~ 150% rated output power for more than 3 sec and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
56 ~ 65V
29 ~ 33V
Protection type : Shut down o/p voltage with auto-recovery
95
5 (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
WORKING TEMP.
Note.5 -25 ~ +70 (Refer to output load derating curve)
20 ~ 95% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25
SAFETY & ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
EMC
(Note 4)
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A, SEMI F47, GL approved
MTBF
169.3Khrs min.
DIMENSION
63*125.2*113.5mm (W*H*D)
1.03Kg; 12pcs/13.4Kg/1.06CUFT
PACKING
NOTE
O/P-DC OK:0.5KVAC
/ 70% RH
MIL-HDBK-217F (25
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. After 30 min. of burn-in.
File Name:SDR-240-SPEC 2008-12-17
240W Single Output Industrial DIN RAIL with PFC Function
SDR-240 series
Mechanical Specification
Unit:mm
113.5
Case No. 979A
125.2
TB1
DC OK
1
63
DC OK
3
+V ADJ.
2
TB2
1
2
3
4
5
6
+
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Assignment
FG
AC/N
AC/L
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
5,6
Assignment
Relay Contact
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
DC OK
I/P
EMI FILTER
&
RECTIFIERS
POWER
SWITCHING
PFC
CIRCUIT
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
FG
PFC
CONTROL
O.L.P.
PWM & PFC
CONTROL
DETECTION
CIRCUIT
O.V.P.
DC OK Relay Contact
Contact Close
When the output voltage reaches the adjusted output voltage.
Contact Open
When the output voltage drop below 90% output voltage.
Contact Ratings (max.) 30V/1A resistive load
File Name:SDR-240-SPEC 2008-12-17
SDR-240 series
240W Single Output Industrial DIN RAIL with PFC Function
Peak Loading
(1)
(2)
360W
360W
240W
120W
100 sec.
3 sec.
10 sec. 3 sec.
Derating Curve
Output derating VS input voltage
100
150
90
For 3sec. (typ.)
112.5
80
70
LOAD (%)
LOAD (%)
100
Continuous
75
60
-25
60
50
40
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
88
100
110
135
155
230
264
INPUT VOLTAGE (V) 60Hz
File Name:SDR-240-SPEC 2008-12-17