Circuit Breaker Selector Guide

Circuit Breaker Selector Guide
Hydraulic / Magnetic
M-Series
A-Series
B-Series
C-Series
Number of Poles
1-2
1-6 (handle); 1-3 (rocker)
1-6
1-6 (handle); 1-3 (rocker)
Available Delays
Instant, Short
Medium & High Inrush
AC/DC
Instantaneous, Ultra-short,
Short, Medium & Long, AC,
DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
Instantaneous, Ultra-short,
Short, Medium & Long, AC,
DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
Instantaneous, Ultra-short,
Short, Medium & Long, AC,
DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
Maximum Current &
Voltage Ratings
0.02 -15FLA, 32VDC, 125
VAC, 1-pole;
15.1-30GPA, 32VDC,
125VAC, 1-pole;
0.02-15FLA, 65VDC,
250VAC, 2-pole;
15.1-30GPA, 65VDC,
250VAC,2-pole;
0.02-12FLA, 250VAC,
1-pole;
0.02-7.5GPA, 50VDC,
1-pole
0.02-30A 80VDC Polarity
Sensitive (1 pole)
0.02 -30A@277VAC,
80VDC
31.0-50A@125/250VAC,
65VDC
0.02 -30A@277VAC,
80VDC
31.0-50A@125/250VAC,
65VDC
UL Listed
0.02-250A@80VDC
0.02-60A@125VDC
0.02-70A@120VAC
0.02-20A@240VAC
UL Recognized
0.02-30A@480WYE
/277VAC 2-pole, 1Ø,
3-pole, 3Ø
0.02-50A@277VAC
0.02-100A@250VAC,
80VDC
0.02-100A@120/240VAC,
65VDC
Maximum Interrupting
Capacity
1000A @ 65 VDC, 2-pole
1000A @ 32 VDC, 1-pole
1000A @ 250VAC, 2-pole
1000A @ 125VAC, 1-pole
1000A @ 65VDC, 1-pole
(polarity sensitive)
600A@80VDC 1-pole (polarity sensitive)
3000A @ 65 VDC, UL only
3500A @ 65 VDC, w/fuse
backup
3000A @ 125/250VAC, UL
only
5000A @ 277VAC, w/fuse
backup
3000A @ 65 VDC, UL only
3500A @ 65 VDC, w/fuse
backup
3000A @ 125/250VAC, UL
only
5000A @ 277VAC, w/fuse
backup
UL Listed
50000A@80VDC,
10,000A@120VAC,
5000A@125VDC, 240VAC
UL Recognized
7500A@80VDC
3000A@125/250VAC, UL
only
5000A @ 250VAC
5000A@480WYE/277VAC
w/fuse backup
Auxilary Switch
Ratings
7A@ 250VAC
0.1A@125VAC (gold contacts)
7A(res.)@28VDC
4A(Ind.)@28VDC
10.1A@125VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
10.1A@125VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
10.1A@250VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
Available Circuits
Series, Switch Only
Series, Shunt, Relay, Switch
Only, Series w/Remote
Shutdown, Relay & Shunt
Trip Dual Coil
Series, Shunt, Relay, Switch
Only, Series w/Remote
Shutdown, Relay & Shunt
Trip Dual Coil, Mid-Trip with
Alarm Switch
Series, Shunt, Relay, Switch
Only, Series w/Remote
Shutdown, Relay & Shunt
Trip Dual Coil, Mid-Trip with
Alarm Switch
Terminal Options
.250” Tab w/ QC,
8-32 Screw
.250” Tab w/ QC,
8-32 & 10-32 Screw
(& metric), PCB
.250” Tab w/ QC,
8-32 & 10-32 Screw
(& metric), PCB
10-32 Stud, 1/4-20 Stud,
0-32 Screw w/ saddle
clamp, Clip Terminal,
1/4 & 7/16 Push-In
Mounting Method
Rocker: Front Panel Snap-In
Handle: Threaded Bushing,
Push-Pull
Threaded inserts: Front
Panel Snap-In
Threaded inserts: Front
Panel Snap-In
Threaded inserts
Agency Approvals
UL, CSA, VDE(rocker),
UL489A
UL, CSA, VDE, TUV(rocker),
UL1500, UL489A
UL, CSA, VDE, TUV(rocker),
UL1500, UL489, UL489A
UL, CSA, VDE, TUV,
UL1500, UL489, UL489A
Dimensions
2
www.carlingtech.com
Circuit Breaker Selector Guide
Hydraulic / Magnetic
D-Series
E-Series
F-Series
Number of Poles
1-4 (handle); 1-3 (rocker)
1-6
1-3
Available Delays
Instantaneous, Ultra-short,
Short, Medium & Long, AC,
DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
Instant, Short, Medium &
Long - AC, DC, and AC/DC
High Inrush - Short, Medium
& Long- AC, DC, and
AC/DC
Short, Medium & Long DC
Maximum Current &
Voltage Ratings
0.02 -50A@277VAC,
65VDC
0.02-30A@480WYE
/277VAC, 2 pole, 1Ø,
3 pole 3Ø
UL Listed
0.02-100A@240VAC,
65VDC, 125VDC
UL Recognized
0.02-100A@277VAC,
160VDC, 1-pole
0.02-100A@600VAC, 2-pole
1Ø, 3 pole 3Ø
0.02-120A@125VDC, 1pole
Maximum Interrupting
Capacity
1500A without fuse, 5000A
with fuse @ 65 VDC,
250VAC, VDE only
5000A @ 65 VDC
5000A @ 480WYE/277VAC,
w/fuse backup,UL only
3000A @ 125/250VAC, UL
only
UL Listed
25000A@65VDC
5000A@125VDC & 240VAC
UL Recognized
5000A @ 125VDC
5000A @ 600VAC, without
fuse backup
10000A @ 600VAC, w/fuse
backup
50000A@125VDC
Auxilary Switch
Ratings
n/a
10.1A@ 250VAC
1.0A@65VDC
0.1A@80VDC
10.1A@ 250VAC
0.5A@65VDC
0.1A@80VDC
Available Circuits
Series, Switch Only, Series
w/Remote Shutdown
Series, Shunt, Relay, Switch
Only, Series w/Remote
Shutdown
Series & Switch Only with or
without Metering Shunt
Terminal Options
Recessed Wire-ready,
Pressure Plate Type Screw
Terminals
10-32 Stud, 1/4-20 Stud
0-32 Screw, 1/4-20 Screw
Box Wire Connector
3/8-16 Stud, 3/8-16 Screw &
Box Wire Connector
Mounting Method
Rear Mounted on DIN Rail
or Front Panel
Rear or Front Panel
Rear or Front Panel
Agency Approvals
UL, CSA, VDE
UL, CSA, VDE, UL1500,
UL489
CUL,TUV, UL489, UL489A
Dimensions
www.carlingtech.com
UL489 Listed:
50-250A@125VDC
UL489A Listed
250-700A@125VDC
3