Hydraulic Magnetic Circuit Breakers Selector Guide

Circuit Protection
Hydraulic/Magnetic Circuit Breakers
Selector Guide
Product Selector Guide
M-SERIES
MS-SERIES
H-SERIES
A- SERIES
NUMBER OF POLES
1-2
1
1-3
1-6 (handle);
1-3 (rocker & metal toggle)
ACTUATOR STYLE
Solid Color Angled Rocker
Two Color Visi-Rocker
Illuminated Angled Rocker
Illuminated Flat Rocker
Solid Color Paddle
Solid Color Baton
Solid Color Push-to-Reset Pushbutton
Solid Color Push-Pull Pushbutton
Sealed Metal Toggle
Handle, Rocker, Curved & Flat
Sealed Metal Toggle, Handle, Rocker,
Paddle
AVAILABLE DELAYS
Instant, Short, Medium AC/DC, Hi-Inrush
Instantaneous, Short & Medium DC
Instantaneous, Ultra-short,
Short, Medium & Long, AC, DC
Instantaneous, Ultra-short,
Short, Medium & Long, AC,
DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
MAXIMUM
CURRENT
& VOLTAGE
RATINGS
0.02-15FLA, 32VDC, 125VAC, 1 pole
15.1-25GPA, 32VDC, 125VAC, 1-pole
0.02-15FLA, 65VDC, 250VAC, 2-pole
15.1-25GPA, 65VDC, 250VAC, 2-pole
0.02-12FLA, 250VAC, 1-pole
0.02-7.5GPA, 50VDC, 1-pole
0.02-30GPA, 65VDC, 80VDC, 1 pole
31-50GPA, 80VDC, Parallel
.2-30A 50VDC
1-32A@65VDC, 80VDC, 250VAC
0.02 -30A@277VAC, 80VDC
MAXIMUM
INTERRUPTING
CAPACITY
1,000A @ 65VDC, 2-pole
1,000A @ 32VDC, 1-pole
1,000A @ 250VAC, 2-pole
1,000A @ 125VAC, 1-pole
600A @ 80VDC
3000A, U3@50VDC
AUXILIARY
SWITCH RATING
7A @ 250VAC
0.1A @ 125VAC (gold contacts)
7A (Res.) @ 28VDC
4A (Ind.) @ 28VDC
0.25A @ 80VDC
N/A
1.0A-65VDC/0.5A-80VDC,
0.1A-125VAC (with gold contacts)
10.1A@125VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
AVAILABLE
CIRCUITS
Series and Switch Only
Parallel Pole
Series
Series, Switch Only,
Relay Trip / V Coil
Series, Shunt, Relay, Switch
Only, Series w/ Remote
Shutdown, Relay & Shunt
Trip Dual Coil
TERMINAL
OPTIONS
.250” QC Tabs
8-32 Screw w/ Upturned Lugs
8-32, 10-32 Screw (Bus Type)
Push in Stud Terminals
8-32 Screw & Solder Type;
.250” QC Tabs
.250” QC Tabs,
8-32 & 10-32 Screw
(& metric), PCB
.250” QC Tabs,
8-32 & 10-32 Screw
(& metric), PCB
Front Panel
Threaded inserts
Threaded inserts:
Front Panel Snap-In
UL 1077
UL Recognized, CSA Accepted, TUV
Certified & CCC Certified
UL, CSA, VDE, TUV(rocker),
UL1500, UL489A
MOUNTING METHOD Snap-in Front Panel Threaded Bushing
AGENCY
APPROVALS
UL recognized, CSA,
VDE, TUV, UL489A Listed
31.0-50A@125/250VAC, 65VDC
3000A@65VDC
1000A@80VDC
1500A@250VAC
7500A @ 65 VDC, UL only
3000A @ 125/250VAC, UL only
5000A @ 277VAC, w/ fuse backup
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
Product Selector Guide
B-SERIES
C-SERIES
D-SERIES
G- SERIES
1-6
1-6 (handle);
1-3 (rocker & metal toggle)
1-4 (handle)
1-3 (rocker)
1-4
Handle, Rocker
Sealed Metal Toggle,
Handle, Rocker
Solid Color Curved Rocker (1 per unit)
Two Color Visi-Rocker (1 per unit)
Handle (1 per pole or 1 per unit)
Handle
Instantaneous, Ultra-short,
Short, Medium & Long, AC,
DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
Instantaneous, Ultrashort,
Short, Medium &
Long, AC, DC, AC/DC
High Inrush - Short, Medium
& Long AC and DC
Instant, Ultra-Short, Short, Medium,
Long (motor loads), AC, DC, AC/DC;
High Inrush - Short, Medium, Long
Instantaneous,Ultrashort,
Short, Medium &
Long, AC, DC
High Inrush - Short,
Medium & Long AC and DC
0.02 -30A@277VAC, 80VDC
UL Listed
0.02-250A@80VDC
0.1-100@125VDC
0.02-70A@120VAC
0.02-20A@240VAC
ULRecognized
0.02-30A@480WYE
/277VAC2-pole, 1Ø,
3-pole, 3Ø
0.02-50A@277VAC
0.02-100A@250VAC,80VDC
0.02-100A@120/240VAC, 65VDC
0.02-50A @ 277VAC, 65VDC
0.02-30A @ 480WYE/277VAC, 2 pole
1 phase,
3 pole 3 phase
UL Recognized
0.02-63A@80VDC
0.02-63A@240VAC
0.02-63A@480YVAC
7500A@80 VDC, UL only
3000A@125/250VAC, UL only
5000A@277VAC, w/ fuse backup
UL Listed
50000A@80VDC, single pole only
10,000A@120VAC,
5000A@125VDC,
240VAC
ULRecognized
7500A@80VDC
3000A@125/250VAC, UL only
5000A@250VAC - listed construction
5000A@480WYE/277V
AC w/fuse backup
1,500A @ 65VDC, 250VAC (VDE only)
5,000A @ 65 VDC
5,000A @ 480WYE/277VAC
w/fuse back up
3,000A @ 125/250VAC (UL only)
w/ fuse back up
UL Recognized
3000A@80VDC
3000A@240VAC
1500A@480VAC
10.1A@125VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
0.1A@80VDC
10.1A@250VAC
0.1A@125VAC (gold contacts)
0.5A@65VDC
N/A
5A@125VAC
3A@32VDC
Series, Shunt, Relay, Switch
Only, Series w/ Remote
Shutdown, Relay & Shunt
Trip Dual Coil, Mid-Trip with
Alarm Switch
Series, Shunt,Relay,
Switch Only, Series
w/ Remote Shutdown,
Relay & Shunt Trip Dual
Coil,Mid-Trip with Alarm Switch
Series, Switch Only,
Series w/ Remote Shutdown
Series, Switch Only
.250” QC Tabs,
8-32 & 10-32 Screw
(& metric), PCB
10-32 Stud, 1/4-20 Stud,
0-32 Screw w/ saddle
clamp,Clip Terminal,
1/4 & 7/16 Push-In
Recessed wire-ready, pressure plate
type screw terminals
Recessed Wire-ready,
Pressure Plate Type
Screw Terminals
Threaded inserts:
Front Panel Snap-In
Threaded inserts
Rear Mounted on DIN Rail or Front
Panel Mounted
Rear Mounted on DIN Rail
UL, CSA, VDE, TUV (rocker),
UL1500, UL489, UL489A
UL, CSA, VDE, TUV,
UL1500, UL489, UL489A
UL recognized, CSA, VDE
UL1077, CUL, TUV
31.0-50A@125/250VAC, 65VDC
NUMBER OF POLES
ACTUATOR STYLE
AVAILABLE DELAYS
MAXIMUM
CURRENT
& VOLTAGE
RATINGS
MAXIMUM
INTERRUPTING
CAPACITY
AUXILIARY
SWITCH RATING
AVAILABLE
CIRCUITS
TERMINAL
OPTIONS
MOUNTING METHOD
AGENCY
APPROVALS
Product Selector Guide
L-SERIES
CX-SERIES
E-SERIES
F- SERIES
NUMBER OF POLES
1-3
1- 2, + Auxiliary Switch Pole
1-6
1-3
ACTUATOR STYLE
Rocker, with or without guard
Handle, 1 per pole
Handle
Handle
AVAILABLE DELAYS
AC: Ultrashort, Short, Medium, Long,
Short-High Inrush, Medium-High Inrush,
Long-High Inrush
DC: Instantaneous, Ultrashort, Short,
Medium & Long
Instant, Short, Medium &
Long - AC,DC, and
AC/DC High Inrush Short, Medium& LongAC, DC, and AC/DC
Short, Medium & Long
DC, AC
MAXIMUM
CURRENT
& VOLTAGE
RATINGS
.2-32A, 120/240-240VAC
UL Recognized .2 -125A, 600VDC
UL Listed .2-15A, 250/500VDC
UL Listed
0.02-100A@240VAC,
65VDC, 125VDC
ULRecognized
0.02-100A@277VAC,
160VDC, 1-pole
0.02-100A@600VAC,
2-pole 1Ø, 3 pole 3Ø
0.02-120A@125VDC,
1-pole
UL489 Listed:
50-250A@125VDC
100-250A@120/240VAC
100-250A@277VAC
100-250A@208Y/120 3Ø
UL489A Listed
250-700A@125VDC
MAXIMUM
INTERRUPTING
CAPACITY
5000 Amps
Up to 10,000 UL Listed and
UL recognized
UL Listed
50000A@80VDC
10000A@125VDC&
240VAC-5KA
ULRecognized
5000A@125VDC
5000A@600VAC,without
fuse backup
10000A@600VAC,
w/fuse backup
50000A@125VDC
10000A, 120/240, 277, 208Y/120
AUXILIARY
SWITCH RATING
N/A
20A, 80VDC (GO circuit)
10.1A@250VAC
1.0A@65VDC
0.1A@80VDC
10.1A@250VAC
0.5A@65VDC
0.1A@80VDC
AVAILABLE
CIRCUITS
Series Trip
Series Trip
Series, Shunt,Relay,
Switch Only, Series
w/ Remote Shutdown
Series & Switch Only
with or without Metering Shunt
TERMINAL
OPTIONS
10-32, 8-32, M5 & M4 Screw
10-32 or M5 Screw Terminals 1/4-20 or
M6 Threaded Stud
10-32 Stud, 1/4-20 Stud
0-32 Screw, 1/4-20
Screw, Box Wire Connector
3/8-16 Stud, 3/8-16
Screw & Box Wire Connector
M3X0.5-6H B ISO (2 per Pole)
Threaded insert: #6-32 UNC-2B, or
M3X0.5-6H B ISO (2 per pole)
Rear or Front Panel
Rear or Front Panel
UL 489, CUL, TUV (EN60934-2)
UL489, UL1077, TUV (EN60934-2)
UL, CSA, VDE,
UL1500, UL489
CUL,TUV, UL489,
UL489A
MOUNTING METHOD Threaded Insert: #6-32 UNC-2B, or
AGENCY
APPROVALS
CB-SG_01_2014
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com