C-Series hydraulic/magnetic circuit breakers

C-Series
Circuit Breaker
The C-Series hydraulic/magnetic circuit breakers are ideal
for applications that require higher amperage and voltage
handling capability in a smaller package. They are available
in 1-6 poles, 0.02-100amps, UL Recognized up to 480VAC or
150VDC, UL489 Listed up to 240VAC or 125VDC, with choice
of time delays, terminal options, actuator styles and colors.
Product Highlights:
The UL489 C-Series employs a unique arc chute design
which allows for higher interrupting capacities of up to
10,000 amps. New thermoset glass filled polyester half
shell construction provides for increased mechanical
and electrical strength. The wiping contacts, mechanical
linkage with two step actuation, clean contacts providing
high, positive contact pressure and longer contact life
ŠŠ Available with American Standard or Metric Threaded
Stud terminals, or Saddle Clamp screw terminals. Optional
mid-trip handle style actuator allows visual indication of
electrical overload with or without alarm feature
ŠŠ Available with new solid color rocker actuators and
unique two-color Visi-rocker® actuators, which can be
specified to indicate either the ON or TRIPPED/OFF mode
ŠŠ Exclusive Rockerguard and Push-To-Reset bezel help
prevent inadvertent actuation
ŠŠ The metal toggle option was tested to MIL-PRF-55629C
for ingress protection when mounted in a panel, and also
meets IP68 requirement.
HANDLE ACTUATOR
METAL TOGGLE ACTUATOR
ŠŠ
PARALLEL POLE ACTUATOR
Agency Certifications:
UL Recognized
UL Standard 1077 | UL Standard 508
UL Standard 1500
UL Listed
UL Standard 489 | UL Standard 489A
CSA Accepted | CSA Certified
TUV Certified | VDE Certified
* For full Agency Certifications, please see pg. 6
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: [email protected] • www.carlingtech.com
2 | C-Series – General Specifications
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary
Protector
C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
CIRCUIT
CONFIGURATION
SERIES
VOLTAGE
CURRENT RATING
NOTES
PHASE
FULL LOAD
AMPS
32
DC
---
0.02 - 100
---
---
5000
TC1, OL1, U2
TC1, OL1, U2
48
DC
---
110 - 150
---
---
5000
TC1, OL1, U2
TC1, OL1, U2
65
DC
---
0.02 - 70
---
---
5000
TC1,2, OL1,U1
TC1,2, OL1,U1
---
71 -100
---
5000
TC1,2, OL0,U1
TC1,2, OL0,U1
0.02 - 70
---
---
7500
TC1,2, OL1,U1
TC1,2, OL1,U1
---
71 -100
---
7500
TC1,2, OL0,U1
TC1,2, OL0,U1
0.02 - 70
---
---
10,000
TC1,2, OL1,U1
TC1,2, OL1,U1
Must Have Agency Code "L"
---
71 -100
---
10,000
TC1,2, OL0,U1
TC1,2, OL0,U1
Must Have Agency Code "L"
Must Have Agency Code "L"
UL
CSA
80
DC
---
80
DC
---
125
DC
---
0.02 - 50
---
5000
TC1,2,OL1,U1
TC1,2,OL1,U1
125 / 250
DC
---
0.02 - 50
---
5000
TC1,2,OL1,U1
TC1,2,OL1,U1
Must Have Agency Code "L"
250
DC
---
0.02 - 50
---
5000
TC1,2,OL1,U1
TC1,2,OL1,U1
Must Have Agency Code "L". 2 Pole Break Required for 250 Volts
125
50 / 60
1
150
DC
---
150
DC
---
250
50 / 60
1
50 / 60
3
277
50 / 60
1
480 / 277
50 / 60
3
0.02 - 100
---
---
3000
TC1, OL1, U2
TC1, OL1, U2
Per Pole Rating
0.02 - 100
---
---
5000
TC1,2,OL1,U1
TC1,2,OL1,U1
Must Have Agency Code "L"
---
80 - 100
---
5000
TC1, OL0, U3
---
Must Have Agency Code "L"
Must Have Agency Code "L" Parallel Pole
---
101 - 175
---
5000
TC1, OL0, U3
---
0.02 - 100
---
---
3500
TC1, OL1, U2
TC1, OL1, U2
0.02 - 50
---
---
3000
TC1,2,OL1,U1
TC1,2,OL1,U1
51 - 100
---
---
1000
TC1,2,OL1,U1
TC1,2,OL1,U1
2 or 3 poles breaking single phase
0.02 - 100
---
---
5000
TC1,2,OL1,U2
TC1,2,OL1,U2
2 or 3 poles breaking single phase, "L" Agency Code
0.02 - 50
---
---
3500
TC1, OL1, U2
TC1, OL1, U2
Per Pole Rating
0.02 - 100
---
---
5000
TC1,2,OL1,U1
TC1,2,OL1,U1
Must Have Agency Code "L"
51 - 70
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
---
0.02 - 100
---
3000
TC1, OL0, U2
TC1, OL0, U2
0.02 - 70
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3 poles breaking 3 phase
---
0.02 - 90
---
5000
TC1,2,OL0,U1
TC1,2,OL0,U1
Must Have Agency Code "L"
0.02 - 50
---
5000
---
TC1,2,OL1,C1
2 or 3 poles breaking single phase
TC1,2,OL1,C1
0.02 - 30
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
---
31 - 50
5000
---
TC1,2,OL0,C1
TC1,2,OL0,C1
0.02 - 30
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3 poles breaking 3 phase
2 poles breaking 1 phase
480
50 / 60
1
---
31 - 50
5000
---
TC1,2,OL0,C1
TC1,2,OL0,C1
80
DC
---
0.02 - 50
---
---
7500
TC1,2, OL1,U1
TC1,2, OL1,U1
0.02 - 50
---
---
3000
TC1, OL1, U2
TC1, OL1, U2
Per Pole Rating
0.02 - 50
---
---
3500
TC1, OL1, U2
TC1, OL1, U2
2 or 3 poles breaking single phase
0.02 - 50
---
---
3000
TC1,2,OL1,U1
TC1,2,OL1,U1
2 or 3 poles breaking single phase
0.02 - 50
---
---
3500
TC1, OL1, U2
TC1, OL1, U2
0.02 - 50
---
---
3000
TC1, OL0, U2
TC1, OL0, U2
0.02 - 50
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
125
50 / 60
1
125 / 250
50 / 60
1
DUAL COIL
1
250
SWITCH ONLY
APPLICATION CODES
FREQUENCY
1
RELAY
UL/CSA
MAX.
RATING
125 / 250
SHUNT
SHORT CIRCUIT CAPACITY (AMPS)
WITH BACKUP WITHOUT BACKUP
GENERAL
PURPOSE AMPS
FUSE
FUSE 1
50 / 60
3
277
50 / 60
1
0.02 - 50
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
80
DC
---
0.02 - 50
---
---
7500
TC1,2, OL1,U1
TC1,2, OL1,U1
277
50 / 60
1
250
50 / 60
3
480 / 277
50 / 60
3
480
50 / 60
1
0.02 - 50
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
0.02 - 50
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3 poles breaking 3 phase
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3 poles breaking 3 phase
---
31 - 50
5000
---
TC1,2,OL0,C1
TC1,2,OL0,C1
0.02 - 30
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
---
31 - 50
5000
---
TC1,2,OL0,C1
TC1,2,OL0,C1
TC1,2, OL1,U1
80
DC
---
0.02 - 50
---
---
7500
TC1,2, OL1,U1
50 / 60
1
0.02 - 50
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
250
50 / 60
3
0.02 - 50
---
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
65
DC
---
0.02 - 70
---
---
---
---
---
80
DC
---
125
50 / 60
125 / 250
50 / 60
250
50 / 60
277
50 / 60
50 / 60
---
71 -100
---
---
---
---
0.02 - 70
---
---
---
---
---
---
71 -100
---
---
---
---
1
0.02 - 100
---
---
---
---
---
1
0.02 - 100
---
---
---
---
---
1
0.02 - 100
---
---
---
---
---
3
0.02 - 70
---
---
---
---
---
1
0.02 - 50
---
---
---
---
---
0.02 - 30
---
---
---
---
---
---
31 - 50
---
---
---
---
3
3 poles breaking 3 phase
0.02 - 30
277
480 / 277
Per Pole Rating
2 poles breaking 1 phase
3 poles breaking 3 phase
2 or 3 poles breaking single phase
3 poles breaking 3 phase
Notes for Table A:
1
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and
not to exceed 175 for 51 through 100 Amp rating
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series – General Specifications | 3
Electrical Tables
Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.
RELAY
Notes for Table B:
1
UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with
series fusing as stated above in note 1.
*Series, Shunt and Relay Trip - Voltage Coil Construction not current coils
Table C: Lists UL Recognized, CSA Accepted , VDE and TUV Certified configurations and performance capabilities as a
Component Supplementary Protector.
Notes for Table C:
1
General Purpose ratings for UL/CSA only.
2
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to exceed 175 for 51 through 100 Amp rating.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
4 | C-Series – General Specifications
Electrical Tables
Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case
Circuit Breaker.
C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS
CIRCUIT
CONFIGURATION
SERIES
DUAL COIL
INTERRUPTING
CAPACITY
(AMPS)
WITHOUT
FULL LOAD
BACKUP FUSE
AMPS
CURRENT
RATING
VOLTAGE
MAX.
RATING
FREQUENCY
PHASE
80
DC
---
0.10 - 100
CONSTRUCTION NOTES
50,000 1
Limited to 2 Poles Max from 71 - 100 Amps.
10,000
Limited to 2 Poles Max from 71 - 100 Amps.
125
DC
---
0.10 - 100
5,000
1 - 3 Poles
125 / 250
DC
---
0.10 - 50
5,000
1 or 2 Poles (2 Poles Required for 250 Volts)
120
50 / 60
1
0.10 - 50
10,000
1 - 3 Poles
51 - 70
5,000
1 - 3 Poles
120 / 240
50 / 60
1
240
50 / 60
240
0.10 - 50
5,000
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
0.10 - 50
10000 1
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
1
0.10 - 30
5,000
1Pole
50 / 60
1
0.10 - 20
5,000
2 Pole
277
50 / 60
1
0.10 - 20
10,000
1Pole
120
50 / 60
1
0.10 - 30
10,000
---
Notes from Table D:
1
Special catalog number required. Consult factory.
Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series – General Specifications | 5
Mechanical
Electrical
Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz
(see Table A.)
UL489: AC,240 VAC. (See Table D),
50/60 Hz, 125 VDC
Current Rating Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 25.0, 30.0, 35.0, 40.0, 50.0, 60.0, 70.0, 80.0, 90.0 and 100 amps. Other ratings available, see Ordering Scheme.
Standard Voltage Coils DC - 6V, 12V; AC - 120V; other ratings available, see Ordering
Scheme.
Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux.
Switch 1.0A, 65 VDC. 0.5A, 80VDC,1/4 HP, 125VAC,VDE & TUV
1.0 125 VAC.
Insulation Resistance Minimum of 100 Megohms at 500 VDC.
Dielectric Strength UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically isolated terminals. C-Series Circuit
Breakers comply with the 8mm spacing and 3750V 50/60 Hz
dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per Publications EN 60950 and
VDE 0805.
Resistance, Impedance Values from Line to Load Terminal based on Series Trip Circuit Breaker.
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker )
1000
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.0
15%
20.1 - 100.0
35%
100
5.1 - 20.0
10
O
H
M
S
1
0.1
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Multiple of
Rated Current
Ir
25x
0.01
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
12x
0.001
0.01
1
0.1
10
25%
100
t
AMPERE RATING
4.165
8.33
16.67
Pulse Tolerance Curves
TOLERANCE
(%)
15%
- 20.0
60 Hz 1/25.1
Cycle
- 100
Inrush Pulse20.1
Tolerance
25%
35%
25x
Ir
1
Multiple of
Rated Current
FIGURE
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Multiple of
Rated Current
Ir
CURRENT
(AMPS)
0.100 - 5.0
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
12x
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
22x
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
10x
t
t
4.165
Ir
Multiple of
Rated Current
50 Hz 1/2 Cycle
Inrush Pulse Tolerance
8.33
5.0
16.67
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
10x
20.0
Time in
Milliseconds
50 Hz 1/2 Cycle
Inrush Pulse Tolerance
22x
10.0
Endurance Trip Free Trip Indication Physical
Number of Poles Internal Circuit Config. Weight Standard Colors 10,000 ON-OFF operations @ 6 per
minute; with rated current & voltage.
All C-Series circuit breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves positively to the OFF position when an overload causes the breaker to trip. With mid-trip, handle moves to the mid position on electrical trip of the circuit breaker. With mid trip handle with alarm switch, handle moves to the mid position and the alarm switch actuates when the
circuit breaker is electrically tripped.
1-6 poles ≤ 50A; 1-4 poles @ 5170A; 1-2 poles 71-100A. UL489
Handle: 1 pole ≤ 100A, 2 pole ≤
50A; Rocker: 1 pole ≤ 100A.
Series (with or without auxiliary
switch, mid trip & mid trip with alarm switch) Shunt & Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without aux. switch). UL489: Series (with or without auxiliary switch, mid-trip & midtrip with alarm switch).
Approx.112 grams/pole ( 3.95 oz).
Housing: Black
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Vibration Withstands 0.060” excursion from 10-55 Hz & 10 Gs 55-500 Hz, @ rated current per Method 204C, Test Cond. A. Instantaneous & ultrashort curves tested @ 90% of rated current.
Moisture Resistance Method 106D, i.e., ten 24-hour
cycles @ +25°C to +65°C,
80-98% RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (five cycles @ -55°C to +25°C to +85°C to +25°C).
Operating Temperature -40°C to +85°C
t
5.0
10.0
20.0
Time in
Milliseconds
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
6 | C-Series - Agency Certifications
Agency Certifications:
UL Recognized
UL Standard 1077
Component Recognition Program as Protectors, Supplementary (Guide CCN/QVNU2, File E75596)
UL Standard 508
Motor Controllers, Manual
(Guide CCN/NLRV2, File E135367)
UL Standard 1500
Protectors, Supplementary for Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
UL Listed
UL Standard 489
Circuit Breakers, Molded Case,
(Guide DIVQ, File E129899)
UL Standard 489A
Communications Equipment
(Guide CCN/DITT, File E189195)
CSA Accepted
Component Supplementary Protector under Class 3215 30,
File 047848 0 000
CSA Standard C22.2 No. 235
CSA Certified
Circuit Breaker Model Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
TUV Certified
EN60934, under License No. R72041016
VDE Certified
EN60934, VDE 0642 under File No.
10537
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Handle UL Recognized – Ordering Scheme | 7
C A 3
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
10
5
Aux/Alarm
Switch
6
Frequency
& Delay
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
3 POLES2
3
4
One
Two
4 CIRCUIT3
A3
B
C
D4
E4 Switch Only (no coil)
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
5
6
Three
Four
F4
G4
H4,5
K4,5
Five
Six
Relay Trip (current)
Relay Trip (voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
033
107
11
12
14
16
207
21
22
24
26
9
Actuator
Color
10
Mounting
Bezel/Barrier
C
11
Agency
Approval
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
AMPERES
020 0.020
0250.025
0300.030
0350.035
0400.040
045 0.045
0500.050
055 0.055
060 0.060
0650.065
0700.070
075 0.075
0800.080
085 0.085
0900.090
0950.095
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
4303.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
A3232DC
A4848DC
A6565DC
J066AC
J1212AC
J1818AC
J2424AC
J4848AC
J65 65AC
K20120AC
L40240AC
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
5 AUXILIARY/ALARM SWITCH
0
2
3
4
8
Terminal
7
Current Rating
CODE
2 ACTUATOR1
1
2
1 2 1
7 CURRENT RATING (AMPERES)
1 SERIES
C
A
B
S
T
450
6
8
9
30
31
32
34
36
428
448
468
528
548
56
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles
5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C.
2 Standard multipole units have all poles identical except when specifying auxiliary switch and/or mixed poles. 4 pole max w/VDE. 5th pole available as Series Trip w/
Voltage Coil only.
3 Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D, F, H & K available up to 50 amps maximum Current Rating.
5 Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
7 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
8 Available with Circuit Codes B & D only, and up to 50 amps maximum.
9 Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100 are available up to two poles maximum.
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
12 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 No marking available. Consult factory. VDE/TUV Approval requires dual
(I-O, ON-OFF) or I-O markings on all handles.
17 Single pole only.
18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
CODE
RATING
A066DC
A1212DC
A1818DC
A2424DC
8 TERMINAL15
110
211
312
411
511
612
713,15
915
A14
C11,15
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
Stud M6
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND16
Actuator Color
White
Black
Red
Green
Blue
Yellow
Gray
Orange
Black (short handle)17
I-O
ON-OFF
Dual
Legend Color
AB 1Black
CD 2White
FG 3White
HJ 4White
KL 5White
MN 6Black
PQ 7Black
RS 8Black
TU 9
White
10 MOUNTING/BARRIERS
MOUNTING STYLE
BARRIERS Threaded Insert
1
6-32 x 0.195 inches no A
6-32 X 0.195 inches yes C18 6-32 X 0.195 inches yes 2
ISO M3 x 5mm no B
ISO M3 x 5mm yes D18 ISO M3 x 5mm yes Front panel Snap-In, 1.00” [25.4mm] wide bezel
E17 with Handleguard no VOLTAGE
< 300
< 300
≥ 300
< 300
< 300
≥ 300
< 300
11 AGENCY APPROVAL
C
D
E
H
I
L
R
UL Recognized, CSA Accepted
VDE Certified, UL Recognized, CSA Accepted
TUV Certified, UL Recognized, CSA Accepted
UL489 Construction: VDE Certified, UL Recognized, CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted
UL489 Construction: UL Recognized, CSA Accepted
UL489 Construction: TUV Certified, UL Recognized, CSA Accepted
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
8 | C-Series Handle UL489A Listed / Parallel Pole – Ordering Scheme
C A 2
1
Series
2
Actuator
P 0
4
Circuit
3
Poles
D4
5
Aux/Alarm
Switch
6
Frequency
& Delay
3
6
A
2 ACTUATOR1
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
3 POLES4
1
2
One
3
P
Series Trip
Three
Series Trip (parallel pole)
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY7
D1
D2
D4
D6
DC Ultra Short
DC Short
DC Medium
DC Long
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
11
12
14
16
DC Ultra Short
DC Short
DC Medium
DC Long
7 CURRENT RATING (AMPERES)
CODE
810
811
812
912
AMPERES
100.00
110.00
120.00
125.00
9
Actuator
Color
10
Mounting
M T
11
12
Max. App. Agency
Rating
Approval
813
814
815
816
130.00
140.00
150.00
160.00
Stud 1/4-20
Stud M6
Plug-In Stud
9 ACTUATOR COLOR2
Two
4 CIRCUIT5
B
3 2 1
8
Terminal
8 TERMINAL6
1 SERIES
C
A
S
T
820
7
Current Rating
817
917
818
819
170.00
175.00
180.00
190.00
820 200.00
9224 225.00
8254 250.00
LEGEND
ON-OFF White B
Black D
Red G
Green J
Blue L
Yellow N
Gray Q
Orange S
Dual Legend Color
1 Black
2 White
3 White
4 White
5 White
6 Black
7 Black
8 Black
10 MOUNTING
1
2
Threaded Insert
6-32 x 0.195 inches
ISO M3 x 5mm
11 MAXIMUM APPLICATION RATING
M
80 DC
12 AGENCY APPROVAL8
A
J
T
K
7
Without Approval
UL489A Listed, TUV Certified
UL489A Listed
UL489A Listed, VDE Certified (up to 200 amps)
UL489A Listed, TUV Certified (up to 250 amps)
Notes:
1 Handle moves to Mid-Position only upon electrical trip of C/B when Actuator S is specified. When Actuator Code T is specified, handle moves to Mid Position and Alarm Switch actuates only upon electrical trip of C/B.
2 Standard Handle colors are White, Black, Red & Yellow.
3 Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line and Load Terminals. For Terminal Code A, Line and Load Terminals must be connected to a copper bus bar having a minimum cross-section of 0.078 square inches. Terminal code A not available on the single pole unit.
4 Rating for 101 to 125 amps are available in 1 pole size. Ratings from 110 to 200 amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size.
5 Circuit code B only available with 1 pole.
6 1 pole only available with terminal codes 3 and 6.
7 Delays 11, 12, 14, and 16 are only available with 1 pole.
8 Agency code K and 7 not available with 1 pole.
Agency code J only available with 1 pole.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Rocker UL489A Listed / Parallel Pole – Ordering Scheme | 9
C 1 2
1
Series
2
Actuator
P 0
4
Circuit
3
Poles
D4
5
Aux/Alarm
Switch
6
Frequency
& Delay
3
6
A
2 ACTUATOR
Curved Rocker, Two Color Visi, Indicate On, Vertical Legend
Curved Rocker, Two Color Visi, Indicate On, Horizontal Legend
Curved Rocker, Two Color Visi, Indicate Off, Vertical Legend
Curved Rocker, Two Color Visi, Indicate Off, Horizontal Legend
Curved Rocker, Single Color, Vertical Legend
Curved Rocker, Single Color, Horizontal Legend
Flat Rocker, Two Color Visi, Vertical Legend
Flat Rocker, Two Color Visi, Horizontal Legend
Flat Rocker, Single Color, Vertical Legend
Flat Rocker, Single Color, Horizontal Legend
Flat Rocker, Push To Reset, Two Color Visi, Vertical Legend
Flat Rocker, Push To Reset, Two Color Visi, Horizontal Legend
Flat Rocker, Push To Reset, Single Color, Vertical Legend
Flat Rocker, Push To Reset, Single Color, Horizontal Legend
3 POLES2
1
2
One
P
Series Trip
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY5
D1
D2
D4
D6
3
Two
4 CIRCUIT3
B
810
811
812
912
DC Ultra Short
DC Short
DC Medium
DC Long
AMPERES
100.00
110.00
120.00
125.00
9
Actuator
Color
10
Mounting
M T
11
12
Max. App. Agency
Rating
Approval
6
8
9
813
814
815
816
130.00
140.00
150.00
160.00
Stud 1/4-20
Stud M6
Plug-In Stud
9 ACTUATOR COLOR
LEGEND
ON-OFF White B
Black D
Red G
Green J
Blue L
Yellow N
Gray Q
Orange S
Dual Legend Color
1 Black
2 White
3 White
4 White
5 White
6 Black
7 Black
8 Black
10 MOUNTING
Three
Series Trip (parallel pole)
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
A
B
C
D
E
F
G
H
ROCKER / MOUNTING INSERT STYLE
Standard Rocker Bezel - 6-32 Inserts
Standard Rocker Bezel - M3 Inserts
Rocker Guard Bezel - 6-32 Inserts
Rocker Guard Bezel - M3 Inserts
Standard Bezel with recessed Off Side Flat Rocker - 6-32 Inserts
Standard Bezel with recessed Off Side Flat Rocker - M3 Inserts
Push to Reset Bezel - 6-32 Inserts
Push to Reset Bezel - M3 Inserts
11 MAXIMUM APPLICATION RATING
M
80 DC
12 AGENCY APPROVAL6
11
12
14
16
DC Ultra Short
DC Short
DC Medium
DC Long
7 CURRENT RATING (AMPERES) 2
CODE
3 1 A
8
Terminal
8 TERMINAL4
1 SERIES
C
C
D
F
G
J
K
1
2
3
4
5
6
7
8
820
7
Current Rating
817
917
818
819
170.00
175.00
180.00
190.00
820 200.00
922 225.00
825 250.00
A
J
T
7
Without Approval
UL489A Listed, TUV Certified
UL489A Listed
UL489A Listed, TUV Certified
Notes:
1 Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line and Load Terminals. For Terminal Code A, Line and Load Terminals must be connected to a copper bus bar having a minimum cross-section of 0.078 square inches. Terminal code A not available on the single pole unit.
2 Ratings for 101 to 125 amps are availabe in 1-pole size. Ratings from 110 to 200 amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size.
3 Circuit code B only available with 1-pole.
4 1 pole only available with terminal codes 3 and 6.
5 Delays 11, 12, 14, and 16 are only available with 1 pole.
6 Agency code K and 7 not available with 1 pole.
Agency code J only available with 1 pole.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
10 | C-Series Handle UL489 Listed – Ordering Scheme
C A 3
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
14
5
Aux/Alarm
Switch
6
Frequency
& Delay
CODE
ACTUATOR1
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
3 POLES2
1
2
One
3
Two
Three
4 CIRCUIT
B
Series Trip (current)
5 AUXILIARY/ALARM SWITCH3
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
11
12
14
16
21
22
24
1 2 1
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
K G
11
Max. App.
Rating
12
Agency
Approval
7 CURRENT RATING (AMPERES) 5
1 SERIES
C
2
450
7
Current Rating
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
26
424
444
464
524
544
564
50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker.
2 Standard multipole units have all poles identical except when specifying auxiliary switch and/or mixed poles.
2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating code C) applications, have all poles identical except when specifying auxiliary / alarm switch which is normally supplied in extreme right pole per figure B. Terminal barriers are required on all multipole breakers.
Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd pole has the same construction as poles 1 & 2.
3 On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme right pole.
VDE approval on auxiliary switch codes 2, 3 & 4 only.
Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit, only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC,
and 120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit breaker, is supplied from factory with common terminal of auxiliary / alarm switch connected to line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated 120 VAC 50 amp maximum can be supplied with Auxiliary/Alarm switch common terminal connected to breaker line terminal. Consult factory for special catalog number.
4 Available up to 50 amps maximum.
5 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
6 Terminal Codes 9 & C are not VDE approved.
7 Terminal Code 1 available to 60 amps maximum.
8 Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
9 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
10 Terminal Code A available to 100 amps maximum.
11 VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles.
12 Barriers supplied on multi-pole units only.
AMPERES
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
4303.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
8 TERMINAL6
1 7
2 8
3 9
4 8
5 8
6 9
9 9
A10
C 8
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
Stud M6
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND11
Actuator Color White Black Red Green Blue Yellow Gray Orange ON-OFF Dual Legend Color
B1 Black
D2 White
G3 White
J
4 White
L
5 White
N
6 Black
Q
7 Black
S
8 Black
10 MOUNTING/BARRIERS
1
2
MOUNTING STYLE
Threaded Insert
6-32 x 0.195 inches
ISO M3 x 5mm
BARRIERS12
yes
yes
11 MAXIMUM APPLICATION RATING
A
B
C
D
K
F
M
65 DC
125 DC
120/240 AC2
240 AC
120 AC
277 AC
80 DC
12 AGENCY APPROVAL11
A
F
G
J
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
w/o approvals
UL489 Listed, CSA Certified & VDE Certified
UL489 Listed & CSA Certified
UL489 Listed, CSA Certified & TUV Certified
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Sealed Toggle UL Recognized – Ordering Scheme | 11
C M 3
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
10
5
Aux/Alarm
Switch
6
Frequency
& Delay
CODE
ACTUATOR1
M
Sealed Toggle, one per pole
3 POLES
1
2
One
4 CIRCUIT
A2
B
C
D3
E3 Switch Only (no coil)
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
3
Two
F3
G3
H3,4
K3,4
Three
Relay Trip (current)
Relay Trip (voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
032
106
11
12
14
16
206
21
22
24
26
7
Current Rating
1 0 1
8
Terminal
9
Legend
Plate
10
Mounting
Bezel/Barrier
C
11
Agency
Approval
7 CURRENT RATING (AMPERES) 9
1 SERIES
C
2
450
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
30
31
32
34
36
427
447
467
527
547
56
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Notes:
1 Actuator Code M: Handle location as viewed from front of breaker:
2 pole - right pole
3 pole - center pole
2 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
3 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only.
4 Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only.
5 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
6 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
7 Available with Circuit Codes B & D only, and up to 50 amps maximum.
8 Consult factory for current ratings 71-100, in three pole units, available as special
catalog number only.
9 Terminal Code 1 available to 60 amps maximum.
10 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
11 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
12 Terminal Code 7 available to 25 amps maximum.
13 Terminal Code A available to 100 amps maximum.
AMPERES
020 0.020
0250.025
0300.030
0350.035
0400.040
045 0.045
0500.050
055 0.055
060 0.060
0650.065
0700.070
075 0.075
0800.080
085 0.085
0900.090
0950.095
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
4303.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
A3232DC
A4848DC
A6565DC
J066AC
J1212AC
J1818AC
J2424AC
J4848AC
J65 65AC
K20120AC
L40240AC
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
CODE
RATING
A066DC
A1212DC
A1818DC
A2424DC
8 TERMINAL
1 9
210
311
410
510
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
611
712
911
A13
C10
Stud M6
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 LEGEND PLATE
0
No Legend
10 MOUNTING/BARRIERS
1
A
MOUNTING STYLE BARRIERS
Standard Hex Nut no
Standard Hex Nut (multi-pole units only) yes
11 AGENCY APPROVAL
C
L
T
UL Recognized & CSA Accepted
UL Recognized & CSA Accepted with listed construction
UL Recognized & CSA Accepted, UL1500 ignition protection
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
12 | C-Series Rocker UL Recognized – Ordering Scheme
C C 3
1
Series
2
Actuator
14
B 0
4
Circuit
3
Poles
6
Frequency
& Delay
5
Aux/Alarm
Switch
1 SERIES
C
450
7
Current Rating
1 2 1
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
D
11
Agency
Approval
7 CURRENT RATING (AMPERES)
CODE
2 ACTUATOR1
Single color
J
Vertical legend
K
Horizontal legend
L
No legend
Push-To-Reset, Single color
R
Vertical legend
U
Horizontal legend
V
No legend
Two Color Visi-Rocker
C
Indicate ON, vertical legend
D
Indicate ON, horizontal legend
E
Indicate ON, no legend
F
Indicate OFF, vertical legend
G
Indicate OFF, horizontal legend
H
Indicate OFF, no legend
Push-To-Reset, Visi-Rocker
N
Indicate OFF,
vertical legend
O
Indicate OFF,
horizontal legend
P
Indicate OFF,
no legend
AMPERES
020 0.020
0250.025
0300.030
0350.035
0400.040
045 0.045
0500.050
055 0.055
060 0.060
0650.065
0700.070
075 0.075
0800.080
085 0.085
0900.090
0950.095
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
4303.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
A3232DC
A4848DC
A6565DC
J066AC
J1212AC
J1818AC
J2424AC
J4848AC
J65 65AC
K20120AC
L40240AC
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
CODE
3 POLES2
1
2
One
4 CIRCUIT
A3
B
C
D 4
E4 3
Two
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
Three
F4
G4
H4,5
K4,5
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
Dual Coil with Relay Trip Voltage Coil
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
30
31
32
34
36
428
448
468
528
548
568
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
5 AUXILIARY/ALARM SWITCH6
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03
107
11
12
14
16
207
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all poles identical except when specifying Aux. switch and/
or mixed poles, and have one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole.
3 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up to 50 amps maximum Current Rating.
5 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only.
6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxiliary switch codes 2, 3 & 4 are VDE approved.
7 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
8 Available with Circuit Codes B & D only, and up to 50 amps maximum.
9 Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are available up to two poles maximum.
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 Color shown is visi and legend with remainder of rocker black
17 Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered. Dual = ON-OFF/I-O legend with actuator codes C - G, and J, K, N, O, R, & U. None = no legend with actuator codes H, L, P, V. Rockerguard available with actuator codes C - L. Push-to-reset available with actuator codes N, O, P, R, U, V.
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
RATING
A066DC
A1212DC
A1818DC
A2424DC
8 TERMINAL
110
211
312
411
511
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
612
713
9
A14
C
Stud M6
0.250 Double Quick Connect
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND16,17,18
Actuator or
Visi-Color
Marking:
Color: I-O ON-OFF Dual/None White A
B
1
Black C
D
2
Red F
G
3
Green H
J
4
Blue K
L
5
Yellow M
N
6
Gray P
Q
7
Orange R
S
8
10 MOUNTING/BARRIERS1
1
2
319 4
5
619 A
C
E19 G
J
L19 B
D
F19 H
J
M19 STANDARD ROCKER BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
ISO M3 x 5mm
ISO M3 x 5mm
ROCKERGUARD BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
ISO M3 x 5mm
ISO M3 x 5mm
PUSH-TO-RESET BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
ISO M3 x 5mm
ISO M3 x 5mm
Marking Color:
Single Color
Rocker/Handle Black White White White White Black Black Black BARRIERS
no
yes
yes
no
yes
yes
no
yes
yes
no
yes
yes
no
yes
yes
no
yes
yes
11 AGENCY APPROVAL
C
D
E
H
I
L
R
Visi-Rocker
White
n/a
Red
Green
Blue
Yellow
Gray
Orange
UL Recognized & CSA Accepted
VDE Certified, UL Recognized & CSA Accepted
TUV Certified, UL Recognized & CSA Accepted
UL489 Construction: VDE Certified, UL Recognized & CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
UL489 Construction: UL Recognized & CSA Accepted
UL489 Construction: TUV Certified, UL Recognized & CSA Accepted
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Rocker UL Listed – Ordering Scheme | 13
C C 3
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
5
Aux/Alarm
Switch
14
6
Frequency
& Delay
CODE
2 ACTUATOR
1
Two Color Visi-Rocker
C
Indicate ON, vertical legend
D
Indicate ON, horizontal legend
F
Indicate OFF, vertical legend
G
Indicate OFF, horizontal legend
Single color
J
Vertical legend
K
Horizontal legend
ROCKER STYLE DESCRIPTIONS
INDICATE "ON"
INDICATE "OFF"
SINGLE COLOR
CODE "F"
CODE "J"
CODE "C"
INDICATE
COLOR
LOCATION
LINE
CODE "D"
HORIZONTAL
STYLE
VERTICAL
STYLE
LINE
LINE
3 POLES1
2
One
LINE
CODE "G"
LINE
CODE "K"
3
Two
Three
Series Trip (current)
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
11
12
14
16
21
22
24
K G
10
Mounting/
Barriers
11
Max. App.
Rating
12
Agency
Approval
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
AMPERES
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
430 3.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
15
26
37
46
56
Stud 10-32
Screw 10-32 w/saddle &
washer clamps
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8 w/saddle &
washer clamps
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
67
97,8
A7,8
C6,8
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
Stud M6
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND11
5 AUXILIARY/ALARM SWITCH2
0
2
3
4
9
Actuator
Color
8 TERMINAL
LINE
4 CIRCUIT
B
1 2 A
8
Terminal
7 CURRENT RATING (AMPERES) 4
1 SERIES
C
1
450
7
Current Rating
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
26
428
448
468
528
548
56
50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Notes:
1 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker.
2 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
3 Available up to 50 amps maximum.
4 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
5 Terminal Code 1 available to 60 amps maximum.
6 Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
7 Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
8 Terminal Codes 9 & C are not VDE approved.
9 Color shown is visi and legend with remainder of rocker black
10 Dual = ON-OFF/I-O legend on actuator.
11 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
12 Rockerguard available with all actuator codes.
13 Barriers supplied on multi-pole units only.
14 2 & 3 pole circuit breakers required for 120/240 AC rating.
Actuator or
Visi-Color
Marking:
Color: ON-OFF Dual10
White B
1
Black D
2
Red G
3
Green J
4
Blue L
5
Yellow N
6
Gray Q
7
Orange S
8
10 MOUNTING/BARRIERS12
Standard Rocker Bezel A
C
B
D
Marking Color:
Single Color
Rocker/Handle Black White White White White Black Black Black BARRIERS13
Threaded Insert, 2 per pole
6-32 X 0.195 inches ISO M3 x 5mm yes
yes
Threaded Insert, 2 per pole
6-32 x 0.195 inches ISO M3 x 5mm yes
yes
Rockerguard Bezel
11 MAXIMUM APPLICATION RATING
A
B
C
D
F
K
M
65 DC
125 DC
120/240 AC14
240 AC
277 AC
120 AC
80 DC
12 AGENCY APPROVAL
A
F
G
J
without approvals
UL 489 Listed, CSA Certified, & VDE Certified
UL 489 Listed & CSA Certified
UL489 Listed, CSA Certified & TUV Certified
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
Visi-Rocker
White
n/a
Red
Green
Blue
Yellow
Gray
Orange
14 | C-Series Flat Rocker UL Recognized – Ordering Scheme
C 1 2
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
10
5
Aux/Alarm
Switch
6
Frequency
& Delay
1 SERIES
C
2
Two Color Visi-Rocker
1
Indicate OFF, vertical legend
2
Indicate OFF, horizontal legend
Single color
3
Vertical legend
4
Horizontal legend
Push-To-Reset, Visi-Rocker
5
Indicate OFF, vertical legend
6
Indicate OFF, horizontal legend
Push-To-Reset , Single color
7
Vertical legend
8
Horizontal legend
3 POLES2
2
One
3
Two
4 CIRCUIT
A3
B
C
D4
E4
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
F4
G4
H4,5
K4,5
Three
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
Dual Coil with Relay Trip Voltage Coil
5 AUXILIARY/ALARM SWITCH6
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03
107
11
12
14
16
207
21
22
24
26
1 2 1
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
E
11
Agency
Approval
7 CURRENT RATING (AMPERES) 9
CODE
ACTUATOR1
1
450
7
Current Rating
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
6
8
9
30
31
32
34
36
428
448
468
528
548
568
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Notes:
1 Push-to-reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all poles identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole.
3 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up to 50 amps maximum Current Rating.
5 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only.
6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxilary switch codes 2, 3 & 4 are VDE approved.
7 Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
8 Available with Circuit Codes B & D only, and up to 50 amps maximum.
9 Current ratings 60-70 are available up to four poles maximum. Current ratings 71 - 100 are available up to two poles maximum.
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
17 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-to-reset bezel/shroud matches visi-color of rocker with actuator codes 5 & 6.
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
20 Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are available in ink stamping only.
AMPERES
020 0.020
0250.025
0300.030
0350.035
0400.040
045 0.045
0500.050
055 0.055
060 0.060
0650.065
0700.070
075 0.075
0800.080
085 0.085
0900.090
0950.095
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
4303.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
A3232DC
A4848DC
A6565DC
J066AC
J1212AC
J1818AC
J2424AC
J4848AC
J65 65AC
K20120AC
L40240AC
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
CODE
RATING
A066DC
A1212DC
A1818DC
A2424DC
8 TERMINAL
110
211
312
411
511
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
612
713
915
A14
C15
Stud M6
0.250 Double Quick Connect
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND16,17,18
Actuator or
Visi-Color
Marking:
Color: I-O ON-OFF Dual/None White A
B
1
Black C
D
2
Red F
G
3
Green H
J
4
Blue K
L
5
Yellow M
N
6
Gray P
Q
7
Orange R
S
8
10 MOUNTING/BARRIERS1
STANDARD ROCKER BEZEL 1
6-32 x 0.195 inches 2
6-32 x 0.195 inches 319 6-32 x 0.195 inches 4
ISO M3 x 5mm 5
ISO M3 x 5mm 619 ISO M3 x 5mm RECESSED OFF ROCKER
7
6-32 x 0.195 inches 8
6-32 x 0.195 inches 9
6-32 x 0.195 inches A
ISO M3 x 5mm C
ISO M3 x 5mm E
ISO M3 x 5mm PUSH-TO-RESET BEZEL
B
6-32 x 0.195 inches D
6-32 x 0.195 inches F19 6-32 x 0.195 inches H
ISO M3 x 5mm J
ISO M3 x 5mm M19 ISO M3 x 5mm Marking Color:
Single Color
Rocker/Handle Black White White White White Black Black Black BARRIERS no yes yes no yes yes VOLTAGE
<300
<300
≥300
<300
<300
≥300
no yes yes no yes yes <300
<300
≥300
<300
<300
≥300
no yes yes no yes yes <300
<300
≥300
<300
<300
≥300
11 AGENCY APPROVAL
C
E
I
L
R
Visi-Rocker
White
n/a
Red
Green
Blue
Yellow
Gray
Orange
UL Recognized & CSA Accepted
TUV Certified, UL Recognized & CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
UL489 Construction: UL Recognized & CSA Accepted
UL489 Construction: TUV Certified, UL Recognized & CSA Accepted
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Flat Rocker UL Listed – Ordering Scheme | 15
C 1 2
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
5
Aux/Alarm
Switch
14
6
Frequency
& Delay
CODE
Two Color Visi-Rocker
1
Indicate OFF, vertical legend
2
Indicate OFF, horizontal legend
Single color
3
Vertical legend
4
Horizontal legend
Push-To-Reset, Visi-Rocker
5
Indicate OFF, vertical legend
6
Indicate OFF, horizontal legend
Push-To-Reset , Single color
7
Vertical legend
8
Horizontal legend
3 POLES2
2
One
3
Two
Three
Series Trip (current)
5 AUXILIARY/ALARM SWITCH2
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
11
12
14
16
21
22
24
9
Actuator
Color
10
Mounting/
Barriers
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
6
8
9
26
424
444
464
524
544
564
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
1 Notes:
2 Push-to-reset actuators have OFF portion of rocker shrouded.
3 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker.
4 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
5 Available up to 50 amps maximum.
6 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
7 Terminal Code 1 available to 60 amps maximum.
8 Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
9 Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
10 Terminal Codes 9 & C are not VDE approved.
11 Color shown is visi and legend with remainder of rocker black
12 Dual = ON-OFF/I-O legend on actuator.
13 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
14 Legend on push-to-reset bezel/shroud is white when single color rocker is ordered. Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator codes
15 5 & 6.
16 Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker are available in ink stamping only.
17 Barriers supplied on multi-pole units only.
18 2 & 3 pole circuit breakers required for 120/240 AC rating.
295 0.950
410 1.000
512 1.250
415 1.500
5171.750
420 2.000
522 2.250
4252.500
5272.750
4303.000
4353.500
440 4.000
445 4.500
4505.000
4555.500
4606.000
4656.500
8 TERMINAL
17
28
39
48
58
4 CIRCUIT
B
AMPERES
210 0.100
2150.150
220 0.200
2250.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
2550.550
2600.600
265 0.650
2700.700
2750.750
2800.800
2850.850
290 0.900
ACTUATOR1
1
1 2 A
8
Terminal
K G
11
Max. App.
Rating
12
Agency
Approval
7 CURRENT RATING (AMPERES) 5
1 SERIES
C
2
450
7
Current Rating
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
4707.000
475 7.500
4808.000
4858.500
4909.000
4959.500
61010.000
71010.500
61111.000
71111.500
61212.000
71212.500
61313.000
61414.000
615 15.000
61616.000
61717.000
69
99,10
A 9
C8,10
618 18.000
62020.000
62222.000
624 24.000
62525.000
63030.000
63535.000
64040.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
Stud M6
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND12
Actuator or
Visi-Color
Marking:
Color: ON-OFF Dual11 White B
1
Black D
2
Red G
3
Green J
4
Blue L
5
Yellow N
6
Gray Q
7
Orange S
8
10 MOUNTING/BARRIERS12
A
C
E
F
B
D
STANDARD ROCKER BEZEL Threaded Insert, 2 per pole
6-32 X 0.195 inches ISO M3 x 5mm RECESSED OFF ROCKER14
Threaded Insert, 2 per pole
6-32 x 0.195 inches ISO M3 x 5mm PUSH-TO-RESET BEZEL13
Threaded Insert, 2 per pole
6-32 x 0.195 inches ISO M3 x 5mm Marking Color:
Single Color
Rocker/Handle Black White White White White Black Black Black BARRIERS15
yes
yes
yes
yes
yes
yes
11 MAXIMUM APPLICATION RATING
A
B
C
D
F
K
M
65 DC
125 DC
120/240 AC16
240 AC
277 AC
120 AC
80 DC
12 AGENCY APPROVAL
A
G
J
without approvals
UL 489 Listed & CSA Certified
UL489 Listed, CSA Certified & TUV Certified
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
Visi-Rocker
White
n/a
Red
Green
Blue
Yellow
Gray
Orange
16 | C-Series Handle – Circuit & Terminal Diagrams
.960 [24.38]
.311 DIA [Ø7.90]
.558 [14.17]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Available on Series Trip and Switch Only Circuits when called for on multi-pole units. Only one aux. switch is normally supplied, as viewed in mulit-pole identification scheme.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Handle – Circuit & Terminal Diagrams | 17
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Schematic shown represents current trip circuits.
4 Available only as special catalog number.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
18 | C-Series Handle – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Handleguard – Form & Fit Drawings | 19
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
20 | C-Series Arc Chute Barrier UL Recognized/Listed – Form & Fit Drawings
Notes:
1 Only 1-pole and 3-pole configurations shown. Arc chute (w/o barrier) and arc chute barrier also available for 2-pole construction.
2 Dimensions apply to all variations shown.
3 Notice that line and load terminal orientation for indicate on and indicate off rocker circuit breakers are opposite.
4 Screw type terminals shown for Rocker style (CF1, C11, etc) circuit breakers. For other terminal configurations see circuit and terminal diagrams.
5 All dimensions are in inches [millimeters].
6 Tolerance ± .020 unless otherwise specified.
7 Must be ordered under a special catalog number.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Parallel Pole – Form & Fit Drawings | 21
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
22 | C-Series Sealed Toggle – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Rocker – Circuit & Terminal Diagrams | 23
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Schematic shown represents current trip circuit.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
24 | C-Series Rocker – Form & Fit Drawings
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON.
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 All dimensions are in inches [millimeters].
4 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
C-Series Flat Rocker – Form & Fit Drawings | 25
Notes:
1 For pole orientation with horizontal legend, rotate front view clockwise 90°.
2 All dimensions are in inches [millimeters].
3 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: [email protected] • www.carlingtech.com
East Region Sales Office, CT • [email protected]
Midwest Region Sales Office, IL • [email protected]
West Region Sales Office, CA • [email protected]
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Int + 852-2737-2277 • Fax: Int + 852-2736-9332
Email: [email protected]
Shenzhen, China • [email protected]
Shanghai, China • [email protected]
Pune, India • [email protected]
Kaohsiung, Taiwan • [email protected]
Yokohama, Japan • [email protected]
Europe/Middle East/Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Int + 44 1392-364422 • Fax: Int + 44 1392-364477
Email: [email protected]
GmbH, Germany • [email protected]
SAS, France • [email protected]
CB_C_09_2014