C-Series Circuit Breaker The C-Series hydraulic/magnetic circuit breakers are ideal for applications that require higher amperage and voltage handling capability in a smaller package. They are available in 1-6 poles, 0.02-100amps, UL Recognized up to 480VAC or 150VDC, UL489 Listed up to 240VAC or 125VDC, with choice of time delays, terminal options, actuator styles and colors. Product Highlights: The UL489 C-Series employs a unique arc chute design which allows for higher interrupting capacities of up to 10,000 amps. New thermoset glass filled polyester half shell construction provides for increased mechanical and electrical strength. The wiping contacts, mechanical linkage with two step actuation, clean contacts providing high, positive contact pressure and longer contact life Available with American Standard or Metric Threaded Stud terminals, or Saddle Clamp screw terminals. Optional mid-trip handle style actuator allows visual indication of electrical overload with or without alarm feature Available with new solid color rocker actuators and unique two-color Visi-rocker® actuators, which can be specified to indicate either the ON or TRIPPED/OFF mode Exclusive Rockerguard and Push-To-Reset bezel help prevent inadvertent actuation The metal toggle option was tested to MIL-PRF-55629C for ingress protection when mounted in a panel, and also meets IP68 requirement. HANDLE ACTUATOR METAL TOGGLE ACTUATOR PARALLEL POLE ACTUATOR Agency Certifications: UL Recognized UL Standard 1077 | UL Standard 508 UL Standard 1500 UL Listed UL Standard 489 | UL Standard 489A CSA Accepted | CSA Certified TUV Certified | VDE Certified * For full Agency Certifications, please see pg. 6 Carling Technologies, Inc. 60 Johnson Avenue • Plainville, CT 06062 Phone: (860) 793-9281 • Fax: (860) 793-9231 Email: [email protected] • www.carlingtech.com 2 | C-Series – General Specifications Electrical Tables Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary Protector C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS CIRCUIT CONFIGURATION SERIES VOLTAGE CURRENT RATING NOTES PHASE FULL LOAD AMPS 32 DC --- 0.02 - 100 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2 48 DC --- 110 - 150 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2 65 DC --- 0.02 - 70 --- --- 5000 TC1,2, OL1,U1 TC1,2, OL1,U1 --- 71 -100 --- 5000 TC1,2, OL0,U1 TC1,2, OL0,U1 0.02 - 70 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1 --- 71 -100 --- 7500 TC1,2, OL0,U1 TC1,2, OL0,U1 0.02 - 70 --- --- 10,000 TC1,2, OL1,U1 TC1,2, OL1,U1 Must Have Agency Code "L" --- 71 -100 --- 10,000 TC1,2, OL0,U1 TC1,2, OL0,U1 Must Have Agency Code "L" Must Have Agency Code "L" UL CSA 80 DC --- 80 DC --- 125 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 125 / 250 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L" 250 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L". 2 Pole Break Required for 250 Volts 125 50 / 60 1 150 DC --- 150 DC --- 250 50 / 60 1 50 / 60 3 277 50 / 60 1 480 / 277 50 / 60 3 0.02 - 100 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating 0.02 - 100 --- --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L" --- 80 - 100 --- 5000 TC1, OL0, U3 --- Must Have Agency Code "L" Must Have Agency Code "L" Parallel Pole --- 101 - 175 --- 5000 TC1, OL0, U3 --- 0.02 - 100 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 0.02 - 50 --- --- 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 51 - 100 --- --- 1000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase 0.02 - 100 --- --- 5000 TC1,2,OL1,U2 TC1,2,OL1,U2 2 or 3 poles breaking single phase, "L" Agency Code 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating 0.02 - 100 --- --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code "L" 51 - 70 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 --- 0.02 - 100 --- 3000 TC1, OL0, U2 TC1, OL0, U2 0.02 - 70 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase --- 0.02 - 90 --- 5000 TC1,2,OL0,U1 TC1,2,OL0,U1 Must Have Agency Code "L" 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 2 or 3 poles breaking single phase TC1,2,OL1,C1 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 --- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase 2 poles breaking 1 phase 480 50 / 60 1 --- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1 80 DC --- 0.02 - 50 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1 0.02 - 50 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 2 or 3 poles breaking single phase 0.02 - 50 --- --- 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 0.02 - 50 --- --- 3000 TC1, OL0, U2 TC1, OL0, U2 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 125 50 / 60 1 125 / 250 50 / 60 1 DUAL COIL 1 250 SWITCH ONLY APPLICATION CODES FREQUENCY 1 RELAY UL/CSA MAX. RATING 125 / 250 SHUNT SHORT CIRCUIT CAPACITY (AMPS) WITH BACKUP WITHOUT BACKUP GENERAL PURPOSE AMPS FUSE FUSE 1 50 / 60 3 277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 80 DC --- 0.02 - 50 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1 277 50 / 60 1 250 50 / 60 3 480 / 277 50 / 60 3 480 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase --- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1 0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 --- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1 TC1,2, OL1,U1 80 DC --- 0.02 - 50 --- --- 7500 TC1,2, OL1,U1 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 250 50 / 60 3 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 65 DC --- 0.02 - 70 --- --- --- --- --- 80 DC --- 125 50 / 60 125 / 250 50 / 60 250 50 / 60 277 50 / 60 50 / 60 --- 71 -100 --- --- --- --- 0.02 - 70 --- --- --- --- --- --- 71 -100 --- --- --- --- 1 0.02 - 100 --- --- --- --- --- 1 0.02 - 100 --- --- --- --- --- 1 0.02 - 100 --- --- --- --- --- 3 0.02 - 70 --- --- --- --- --- 1 0.02 - 50 --- --- --- --- --- 0.02 - 30 --- --- --- --- --- --- 31 - 50 --- --- --- --- 3 3 poles breaking 3 phase 0.02 - 30 277 480 / 277 Per Pole Rating 2 poles breaking 1 phase 3 poles breaking 3 phase 2 or 3 poles breaking single phase 3 poles breaking 3 phase Notes for Table A: 1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to exceed 175 for 51 through 100 Amp rating *Manufacturer reserves the right to change product specification without prior notice. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series – General Specifications | 3 Electrical Tables Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller. RELAY Notes for Table B: 1 UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with series fusing as stated above in note 1. *Series, Shunt and Relay Trip - Voltage Coil Construction not current coils Table C: Lists UL Recognized, CSA Accepted , VDE and TUV Certified configurations and performance capabilities as a Component Supplementary Protector. Notes for Table C: 1 General Purpose ratings for UL/CSA only. 2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to exceed 175 for 51 through 100 Amp rating. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 4 | C-Series – General Specifications Electrical Tables Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case Circuit Breaker. C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS CIRCUIT CONFIGURATION SERIES DUAL COIL INTERRUPTING CAPACITY (AMPS) WITHOUT FULL LOAD BACKUP FUSE AMPS CURRENT RATING VOLTAGE MAX. RATING FREQUENCY PHASE 80 DC --- 0.10 - 100 CONSTRUCTION NOTES 50,000 1 Limited to 2 Poles Max from 71 - 100 Amps. 10,000 Limited to 2 Poles Max from 71 - 100 Amps. 125 DC --- 0.10 - 100 5,000 1 - 3 Poles 125 / 250 DC --- 0.10 - 50 5,000 1 or 2 Poles (2 Poles Required for 250 Volts) 120 50 / 60 1 0.10 - 50 10,000 1 - 3 Poles 51 - 70 5,000 1 - 3 Poles 120 / 240 50 / 60 1 240 50 / 60 240 0.10 - 50 5,000 2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral 0.10 - 50 10000 1 2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral 1 0.10 - 30 5,000 1Pole 50 / 60 1 0.10 - 20 5,000 2 Pole 277 50 / 60 1 0.10 - 20 10,000 1Pole 120 50 / 60 1 0.10 - 30 10,000 --- Notes from Table D: 1 Special catalog number required. Consult factory. Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors. Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment (Guide DITT, File E189195), under UL489A. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series – General Specifications | 5 Mechanical Electrical Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz (see Table A.) UL489: AC,240 VAC. (See Table D), 50/60 Hz, 125 VDC Current Rating Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 25.0, 30.0, 35.0, 40.0, 50.0, 60.0, 70.0, 80.0, 90.0 and 100 amps. Other ratings available, see Ordering Scheme. Standard Voltage Coils DC - 6V, 12V; AC - 120V; other ratings available, see Ordering Scheme. Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux. Switch 1.0A, 65 VDC. 0.5A, 80VDC,1/4 HP, 125VAC,VDE & TUV 1.0 125 VAC. Insulation Resistance Minimum of 100 Megohms at 500 VDC. Dielectric Strength UL, CSA: 1960 V 50/60 Hz for one minute between all electrically isolated terminals. C-Series Circuit Breakers comply with the 8mm spacing and 3750V 50/60 Hz dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per Publications EN 60950 and VDE 0805. Resistance, Impedance Values from Line to Load Terminal based on Series Trip Circuit Breaker. RESISTANCE, IMPEDANCE VALUES from Line to Load Terminals (Values Based on Series Trip Circuit Breaker ) 1000 CURRENT (AMPS) TOLERANCE (%) 0.10 - 5.0 15% 20.1 - 100.0 35% 100 5.1 - 20.0 10 O H M S 1 0.1 60 Hz 1/2 Cycle Inrush Pulse Tolerance Time Delay Curves 42, 44 & 46 (50 Amps Max.) Multiple of Rated Current Ir 25x 0.01 Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) 12x 0.001 0.01 1 0.1 10 25% 100 t AMPERE RATING 4.165 8.33 16.67 Pulse Tolerance Curves TOLERANCE (%) 15% - 20.0 60 Hz 1/25.1 Cycle - 100 Inrush Pulse20.1 Tolerance 25% 35% 25x Ir 1 Multiple of Rated Current FIGURE Time Delay Curves 42, 44 & 46 (50 Amps Max.) Multiple of Rated Current Ir CURRENT (AMPS) 0.100 - 5.0 Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) 12x Time Delay Curves 42, 44 & 46 (50 Amps Max.) 22x Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) 10x t t 4.165 Ir Multiple of Rated Current 50 Hz 1/2 Cycle Inrush Pulse Tolerance 8.33 5.0 16.67 Time Delay Curves 42, 44 & 46 (50 Amps Max.) Time Delay Curves 22, 24 (100 Amps Max.) 26 (70 Amps Max.) 10x 20.0 Time in Milliseconds 50 Hz 1/2 Cycle Inrush Pulse Tolerance 22x 10.0 Endurance Trip Free Trip Indication Physical Number of Poles Internal Circuit Config. Weight Standard Colors 10,000 ON-OFF operations @ 6 per minute; with rated current & voltage. All C-Series circuit breakers will trip on overload, even when actuator is forcibly held in the ON position. The operating actuator moves positively to the OFF position when an overload causes the breaker to trip. With mid-trip, handle moves to the mid position on electrical trip of the circuit breaker. With mid trip handle with alarm switch, handle moves to the mid position and the alarm switch actuates when the circuit breaker is electrically tripped. 1-6 poles ≤ 50A; 1-4 poles @ 5170A; 1-2 poles 71-100A. UL489 Handle: 1 pole ≤ 100A, 2 pole ≤ 50A; Rocker: 1 pole ≤ 100A. Series (with or without auxiliary switch, mid trip & mid trip with alarm switch) Shunt & Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without aux. switch). UL489: Series (with or without auxiliary switch, mid-trip & midtrip with alarm switch). Approx.112 grams/pole ( 3.95 oz). Housing: Black Environmental Designed and tested in accordance with requirements of specification MIL-PRF-55629 & MIL-STD-202 as follows: Shock Withstands 100 Gs, 6ms sawtooth while carrying rated current per Method 213, Test Condition “I”. Instantaneous and ultrashort curves tested @ 90% of rated current. Vibration Withstands 0.060” excursion from 10-55 Hz & 10 Gs 55-500 Hz, @ rated current per Method 204C, Test Cond. A. Instantaneous & ultrashort curves tested @ 90% of rated current. Moisture Resistance Method 106D, i.e., ten 24-hour cycles @ +25°C to +65°C, 80-98% RH. Salt Spray Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs). Thermal Shock Method 107D, Condition A (five cycles @ -55°C to +25°C to +85°C to +25°C). Operating Temperature -40°C to +85°C t 5.0 10.0 20.0 Time in Milliseconds 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 6 | C-Series - Agency Certifications Agency Certifications: UL Recognized UL Standard 1077 Component Recognition Program as Protectors, Supplementary (Guide CCN/QVNU2, File E75596) UL Standard 508 Motor Controllers, Manual (Guide CCN/NLRV2, File E135367) UL Standard 1500 Protectors, Supplementary for Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition Protection UL Listed UL Standard 489 Circuit Breakers, Molded Case, (Guide DIVQ, File E129899) UL Standard 489A Communications Equipment (Guide CCN/DITT, File E189195) CSA Accepted Component Supplementary Protector under Class 3215 30, File 047848 0 000 CSA Standard C22.2 No. 235 CSA Certified Circuit Breaker Model Case (Class 1432 01, File 093910), CSA Standard C22.2 No. 5.1 - M TUV Certified EN60934, under License No. R72041016 VDE Certified EN60934, VDE 0642 under File No. 10537 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Handle UL Recognized – Ordering Scheme | 7 C A 3 1 Series 2 Actuator B 0 4 Circuit 3 Poles 10 5 Aux/Alarm Switch 6 Frequency & Delay Handle, one per pole Handle, one per multipole unit Mid-Trip Handle, one per pole Mid-Trip, one per pole & Alarm Switch 3 POLES2 3 4 One Two 4 CIRCUIT3 A3 B C D4 E4 Switch Only (no coil) Series Trip (current) Series Trip (voltage) Shunt Trip (current) Shunt Trip (voltage) 5 6 Three Four F4 G4 H4,5 K4,5 Five Six Relay Trip (current) Relay Trip (voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 033 107 11 12 14 16 207 21 22 24 26 9 Actuator Color 10 Mounting Bezel/Barrier C 11 Agency Approval DC 50/60Hz, Switch Only DC Instantaneous DC Ultra Short DC Short DC Medium DC Long 50/60Hz Instantaneous 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium 50/60Hz Long AMPERES 020 0.020 0250.025 0300.030 0350.035 0400.040 045 0.045 0500.050 055 0.055 060 0.060 0650.065 0700.070 075 0.075 0800.080 085 0.085 0900.090 0950.095 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 4303.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 650 50.000 6609 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 A3232DC A4848DC A6565DC J066AC J1212AC J1818AC J2424AC J4848AC J65 65AC K20120AC L40240AC VOLTAGE COIL (NOMINAL RATED VOLTAGE)7 5 AUXILIARY/ALARM SWITCH 0 2 3 4 8 Terminal 7 Current Rating CODE 2 ACTUATOR1 1 2 1 2 1 7 CURRENT RATING (AMPERES) 1 SERIES C A B S T 450 6 8 9 30 31 32 34 36 428 448 468 528 548 56 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. DC 50/60Hz Instantaneous DC 50/60Hz Ultra Short DC 50/60Hz Short DC 50/60Hz Medium DC 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units. B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles 5 pole - three handles at center poles 6 pole - four handles at center poles S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Standard multipole units have all poles identical except when specifying auxiliary switch and/or mixed poles. 4 pole max w/VDE. 5th pole available as Series Trip w/ Voltage Coil only. 3 Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D, F, H & K available up to 50 amps maximum Current Rating. 5 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 7 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 8 Available with Circuit Codes B & D only, and up to 50 amps maximum. 9 Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100 are available up to two poles maximum. 10 Terminal Code 1 available to 60 amps maximum. 11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum. 12 Terminal Codes 3, 6 & 9 available to 100 amps maximum. 13 Terminal Code 7 available to 25 amps maximum. 14 Terminal Code A available to 100 amps maximum. 15 Terminal Codes 7, 9 & C are not VDE approved. 16 No marking available. Consult factory. VDE/TUV Approval requires dual (I-O, ON-OFF) or I-O markings on all handles. 17 Single pole only. 18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor. CODE RATING A066DC A1212DC A1818DC A2424DC 8 TERMINAL15 110 211 312 411 511 612 713,15 915 A14 C11,15 Stud 10-32 Screw 10-32 Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 Stud M6 0.250 Double Click Connect 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 ACTUATOR COLOR & LEGEND16 Actuator Color White Black Red Green Blue Yellow Gray Orange Black (short handle)17 I-O ON-OFF Dual Legend Color AB 1Black CD 2White FG 3White HJ 4White KL 5White MN 6Black PQ 7Black RS 8Black TU 9 White 10 MOUNTING/BARRIERS MOUNTING STYLE BARRIERS Threaded Insert 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches yes C18 6-32 X 0.195 inches yes 2 ISO M3 x 5mm no B ISO M3 x 5mm yes D18 ISO M3 x 5mm yes Front panel Snap-In, 1.00” [25.4mm] wide bezel E17 with Handleguard no VOLTAGE < 300 < 300 ≥ 300 < 300 < 300 ≥ 300 < 300 11 AGENCY APPROVAL C D E H I L R UL Recognized, CSA Accepted VDE Certified, UL Recognized, CSA Accepted TUV Certified, UL Recognized, CSA Accepted UL489 Construction: VDE Certified, UL Recognized, CSA Accepted UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted UL489 Construction: UL Recognized, CSA Accepted UL489 Construction: TUV Certified, UL Recognized, CSA Accepted 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 8 | C-Series Handle UL489A Listed / Parallel Pole – Ordering Scheme C A 2 1 Series 2 Actuator P 0 4 Circuit 3 Poles D4 5 Aux/Alarm Switch 6 Frequency & Delay 3 6 A 2 ACTUATOR1 Handle, one per pole Mid-Trip Handle, one per pole Mid-Trip, one per pole & Alarm Switch 3 POLES4 1 2 One 3 P Series Trip Three Series Trip (parallel pole) 5 AUXILIARY/ALARM SWITCH 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY7 D1 D2 D4 D6 DC Ultra Short DC Short DC Medium DC Long 6 8 9 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 11 12 14 16 DC Ultra Short DC Short DC Medium DC Long 7 CURRENT RATING (AMPERES) CODE 810 811 812 912 AMPERES 100.00 110.00 120.00 125.00 9 Actuator Color 10 Mounting M T 11 12 Max. App. Agency Rating Approval 813 814 815 816 130.00 140.00 150.00 160.00 Stud 1/4-20 Stud M6 Plug-In Stud 9 ACTUATOR COLOR2 Two 4 CIRCUIT5 B 3 2 1 8 Terminal 8 TERMINAL6 1 SERIES C A S T 820 7 Current Rating 817 917 818 819 170.00 175.00 180.00 190.00 820 200.00 9224 225.00 8254 250.00 LEGEND ON-OFF White B Black D Red G Green J Blue L Yellow N Gray Q Orange S Dual Legend Color 1 Black 2 White 3 White 4 White 5 White 6 Black 7 Black 8 Black 10 MOUNTING 1 2 Threaded Insert 6-32 x 0.195 inches ISO M3 x 5mm 11 MAXIMUM APPLICATION RATING M 80 DC 12 AGENCY APPROVAL8 A J T K 7 Without Approval UL489A Listed, TUV Certified UL489A Listed UL489A Listed, VDE Certified (up to 200 amps) UL489A Listed, TUV Certified (up to 250 amps) Notes: 1 Handle moves to Mid-Position only upon electrical trip of C/B when Actuator S is specified. When Actuator Code T is specified, handle moves to Mid Position and Alarm Switch actuates only upon electrical trip of C/B. 2 Standard Handle colors are White, Black, Red & Yellow. 3 Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line and Load Terminals. For Terminal Code A, Line and Load Terminals must be connected to a copper bus bar having a minimum cross-section of 0.078 square inches. Terminal code A not available on the single pole unit. 4 Rating for 101 to 125 amps are available in 1 pole size. Ratings from 110 to 200 amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size. 5 Circuit code B only available with 1 pole. 6 1 pole only available with terminal codes 3 and 6. 7 Delays 11, 12, 14, and 16 are only available with 1 pole. 8 Agency code K and 7 not available with 1 pole. Agency code J only available with 1 pole. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Rocker UL489A Listed / Parallel Pole – Ordering Scheme | 9 C 1 2 1 Series 2 Actuator P 0 4 Circuit 3 Poles D4 5 Aux/Alarm Switch 6 Frequency & Delay 3 6 A 2 ACTUATOR Curved Rocker, Two Color Visi, Indicate On, Vertical Legend Curved Rocker, Two Color Visi, Indicate On, Horizontal Legend Curved Rocker, Two Color Visi, Indicate Off, Vertical Legend Curved Rocker, Two Color Visi, Indicate Off, Horizontal Legend Curved Rocker, Single Color, Vertical Legend Curved Rocker, Single Color, Horizontal Legend Flat Rocker, Two Color Visi, Vertical Legend Flat Rocker, Two Color Visi, Horizontal Legend Flat Rocker, Single Color, Vertical Legend Flat Rocker, Single Color, Horizontal Legend Flat Rocker, Push To Reset, Two Color Visi, Vertical Legend Flat Rocker, Push To Reset, Two Color Visi, Horizontal Legend Flat Rocker, Push To Reset, Single Color, Vertical Legend Flat Rocker, Push To Reset, Single Color, Horizontal Legend 3 POLES2 1 2 One P Series Trip 5 AUXILIARY/ALARM SWITCH 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY5 D1 D2 D4 D6 3 Two 4 CIRCUIT3 B 810 811 812 912 DC Ultra Short DC Short DC Medium DC Long AMPERES 100.00 110.00 120.00 125.00 9 Actuator Color 10 Mounting M T 11 12 Max. App. Agency Rating Approval 6 8 9 813 814 815 816 130.00 140.00 150.00 160.00 Stud 1/4-20 Stud M6 Plug-In Stud 9 ACTUATOR COLOR LEGEND ON-OFF White B Black D Red G Green J Blue L Yellow N Gray Q Orange S Dual Legend Color 1 Black 2 White 3 White 4 White 5 White 6 Black 7 Black 8 Black 10 MOUNTING Three Series Trip (parallel pole) S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. A B C D E F G H ROCKER / MOUNTING INSERT STYLE Standard Rocker Bezel - 6-32 Inserts Standard Rocker Bezel - M3 Inserts Rocker Guard Bezel - 6-32 Inserts Rocker Guard Bezel - M3 Inserts Standard Bezel with recessed Off Side Flat Rocker - 6-32 Inserts Standard Bezel with recessed Off Side Flat Rocker - M3 Inserts Push to Reset Bezel - 6-32 Inserts Push to Reset Bezel - M3 Inserts 11 MAXIMUM APPLICATION RATING M 80 DC 12 AGENCY APPROVAL6 11 12 14 16 DC Ultra Short DC Short DC Medium DC Long 7 CURRENT RATING (AMPERES) 2 CODE 3 1 A 8 Terminal 8 TERMINAL4 1 SERIES C C D F G J K 1 2 3 4 5 6 7 8 820 7 Current Rating 817 917 818 819 170.00 175.00 180.00 190.00 820 200.00 922 225.00 825 250.00 A J T 7 Without Approval UL489A Listed, TUV Certified UL489A Listed UL489A Listed, TUV Certified Notes: 1 Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line and Load Terminals. For Terminal Code A, Line and Load Terminals must be connected to a copper bus bar having a minimum cross-section of 0.078 square inches. Terminal code A not available on the single pole unit. 2 Ratings for 101 to 125 amps are availabe in 1-pole size. Ratings from 110 to 200 amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size. 3 Circuit code B only available with 1-pole. 4 1 pole only available with terminal codes 3 and 6. 5 Delays 11, 12, 14, and 16 are only available with 1 pole. 6 Agency code K and 7 not available with 1 pole. Agency code J only available with 1 pole. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 10 | C-Series Handle UL489 Listed – Ordering Scheme C A 3 1 Series 2 Actuator B 0 4 Circuit 3 Poles 14 5 Aux/Alarm Switch 6 Frequency & Delay CODE ACTUATOR1 A B S T Handle, one per pole Handle, one per multipole unit Mid-Trip Handle, one per pole Mid-Trip, one per pole & Alarm Switch 3 POLES2 1 2 One 3 Two Three 4 CIRCUIT B Series Trip (current) 5 AUXILIARY/ALARM SWITCH3 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 11 12 14 16 21 22 24 1 2 1 8 Terminal 9 Actuator Color 10 Mounting/ Barriers K G 11 Max. App. Rating 12 Agency Approval 7 CURRENT RATING (AMPERES) 5 1 SERIES C 2 450 7 Current Rating DC Ultra Short DC Short DC Medium DC Long 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium 6 8 9 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 26 424 444 464 524 544 564 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units. B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum. S: Handle moves to mid-position only upon electrical trip of the breaker. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. 2 Standard multipole units have all poles identical except when specifying auxiliary switch and/or mixed poles. 2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating code C) applications, have all poles identical except when specifying auxiliary / alarm switch which is normally supplied in extreme right pole per figure B. Terminal barriers are required on all multipole breakers. Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd pole has the same construction as poles 1 & 2. 3 On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme right pole. VDE approval on auxiliary switch codes 2, 3 & 4 only. Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit, only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC, and 120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit breaker, is supplied from factory with common terminal of auxiliary / alarm switch connected to line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated 120 VAC 50 amp maximum can be supplied with Auxiliary/Alarm switch common terminal connected to breaker line terminal. Consult factory for special catalog number. 4 Available up to 50 amps maximum. 5 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum. 6 Terminal Codes 9 & C are not VDE approved. 7 Terminal Code 1 available to 60 amps maximum. 8 Terminal Codes 2, 4, 5 & C available to 50 amps maximum. 9 Terminal Codes 3, 6 & 9 available to 100 amps maximum. 10 Terminal Code A available to 100 amps maximum. 11 VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles. 12 Barriers supplied on multi-pole units only. AMPERES 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 4303.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 8 TERMINAL6 1 7 2 8 3 9 4 8 5 8 6 9 9 9 A10 C 8 Stud 10-32 Screw 10-32 Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 Stud M6 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 ACTUATOR COLOR & LEGEND11 Actuator Color White Black Red Green Blue Yellow Gray Orange ON-OFF Dual Legend Color B1 Black D2 White G3 White J 4 White L 5 White N 6 Black Q 7 Black S 8 Black 10 MOUNTING/BARRIERS 1 2 MOUNTING STYLE Threaded Insert 6-32 x 0.195 inches ISO M3 x 5mm BARRIERS12 yes yes 11 MAXIMUM APPLICATION RATING A B C D K F M 65 DC 125 DC 120/240 AC2 240 AC 120 AC 277 AC 80 DC 12 AGENCY APPROVAL11 A F G J 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 660 60.000 670 70.000 680 80.000 685 85.000 690 90.000 695 95.000 810 100.000 w/o approvals UL489 Listed, CSA Certified & VDE Certified UL489 Listed & CSA Certified UL489 Listed, CSA Certified & TUV Certified 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Sealed Toggle UL Recognized – Ordering Scheme | 11 C M 3 1 Series 2 Actuator B 0 4 Circuit 3 Poles 10 5 Aux/Alarm Switch 6 Frequency & Delay CODE ACTUATOR1 M Sealed Toggle, one per pole 3 POLES 1 2 One 4 CIRCUIT A2 B C D3 E3 Switch Only (no coil) Series Trip (current) Series Trip (voltage) Shunt Trip (current) Shunt Trip (voltage) 3 Two F3 G3 H3,4 K3,4 Three Relay Trip (current) Relay Trip (voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil 5 AUXILIARY/ALARM SWITCH 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 032 106 11 12 14 16 206 21 22 24 26 7 Current Rating 1 0 1 8 Terminal 9 Legend Plate 10 Mounting Bezel/Barrier C 11 Agency Approval 7 CURRENT RATING (AMPERES) 9 1 SERIES C 2 450 DC 50/60Hz, Switch Only DC Instantaneous DC Ultra Short DC Short DC Medium DC Long 50/60Hz Instantaneous 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium 50/60Hz Long 6 8 9 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 30 31 32 34 36 427 447 467 527 547 56 DC 50/60Hz Instantaneous DC 50/60Hz Ultra Short DC 50/60Hz Short DC 50/60Hz Medium DC 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush Notes: 1 Actuator Code M: Handle location as viewed from front of breaker: 2 pole - right pole 3 pole - center pole 2 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 3 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. 4 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 5 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 6 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 7 Available with Circuit Codes B & D only, and up to 50 amps maximum. 8 Consult factory for current ratings 71-100, in three pole units, available as special catalog number only. 9 Terminal Code 1 available to 60 amps maximum. 10 Terminal Codes 2, 4, 5 and C available to 50 amps maximum. 11 Terminal Codes 3, 6 & 9 available to 100 amps maximum. 12 Terminal Code 7 available to 25 amps maximum. 13 Terminal Code A available to 100 amps maximum. AMPERES 020 0.020 0250.025 0300.030 0350.035 0400.040 045 0.045 0500.050 055 0.055 060 0.060 0650.065 0700.070 075 0.075 0800.080 085 0.085 0900.090 0950.095 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 4303.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 650 50.000 6609 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 A3232DC A4848DC A6565DC J066AC J1212AC J1818AC J2424AC J4848AC J65 65AC K20120AC L40240AC VOLTAGE COIL (NOMINAL RATED VOLTAGE)7 CODE RATING A066DC A1212DC A1818DC A2424DC 8 TERMINAL 1 9 210 311 410 510 Stud 10-32 Screw 10-32 Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 611 712 911 A13 C10 Stud M6 0.250 Double Click Connect 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 LEGEND PLATE 0 No Legend 10 MOUNTING/BARRIERS 1 A MOUNTING STYLE BARRIERS Standard Hex Nut no Standard Hex Nut (multi-pole units only) yes 11 AGENCY APPROVAL C L T UL Recognized & CSA Accepted UL Recognized & CSA Accepted with listed construction UL Recognized & CSA Accepted, UL1500 ignition protection 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 12 | C-Series Rocker UL Recognized – Ordering Scheme C C 3 1 Series 2 Actuator 14 B 0 4 Circuit 3 Poles 6 Frequency & Delay 5 Aux/Alarm Switch 1 SERIES C 450 7 Current Rating 1 2 1 8 Terminal 9 Actuator Color 10 Mounting/ Barriers D 11 Agency Approval 7 CURRENT RATING (AMPERES) CODE 2 ACTUATOR1 Single color J Vertical legend K Horizontal legend L No legend Push-To-Reset, Single color R Vertical legend U Horizontal legend V No legend Two Color Visi-Rocker C Indicate ON, vertical legend D Indicate ON, horizontal legend E Indicate ON, no legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend H Indicate OFF, no legend Push-To-Reset, Visi-Rocker N Indicate OFF, vertical legend O Indicate OFF, horizontal legend P Indicate OFF, no legend AMPERES 020 0.020 0250.025 0300.030 0350.035 0400.040 045 0.045 0500.050 055 0.055 060 0.060 0650.065 0700.070 075 0.075 0800.080 085 0.085 0900.090 0950.095 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 4303.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 650 50.000 6609 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 A3232DC A4848DC A6565DC J066AC J1212AC J1818AC J2424AC J4848AC J65 65AC K20120AC L40240AC VOLTAGE COIL (NOMINAL RATED VOLTAGE)7 CODE 3 POLES2 1 2 One 4 CIRCUIT A3 B C D 4 E4 3 Two Switch Only (No Coil) Series Trip (Current) Series Trip (Voltage) Shunt Trip (Current) Shunt Trip (Voltage) Three F4 G4 H4,5 K4,5 Relay Trip (Current) Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil 6 8 9 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 30 31 32 34 36 428 448 468 528 548 568 DC 50/60Hz Instantaneous DC 50/60Hz Ultra Short DC 50/60Hz Short DC 50/60Hz Medium DC 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush 5 AUXILIARY/ALARM SWITCH6 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 03 107 11 12 14 16 207 21 22 24 26 DC 50/60Hz, Switch Only DC Instantaneous DC Ultra Short DC Short DC Medium DC Long 50/60Hz Instantaneous 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium 50/60Hz Long Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all poles identical except when specifying Aux. switch and/ or mixed poles, and have one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole. 3 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up to 50 amps maximum Current Rating. 5 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxiliary switch codes 2, 3 & 4 are VDE approved. 7 Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 8 Available with Circuit Codes B & D only, and up to 50 amps maximum. 9 Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are available up to two poles maximum. 10 Terminal Code 1 available to 60 amps maximum. 11 Terminal Codes 2,4,5 & C available to 50 amps maximum. 12 Terminal Codes 3,6 & 9 available to 100 amps maximum. 13 Terminal Code 7 available to 25 amps maximum. 14 Terminal Code A available to 100 amps maximum. 15 Terminal Codes 7, 9 & C are not VDE approved. 16 Color shown is visi and legend with remainder of rocker black 17 Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered. Dual = ON-OFF/I-O legend with actuator codes C - G, and J, K, N, O, R, & U. None = no legend with actuator codes H, L, P, V. Rockerguard available with actuator codes C - L. Push-to-reset available with actuator codes N, O, P, R, U, V. 18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker. 19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor. RATING A066DC A1212DC A1818DC A2424DC 8 TERMINAL 110 211 312 411 511 Stud 10-32 Screw 10-32 Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 612 713 9 A14 C Stud M6 0.250 Double Quick Connect 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 ACTUATOR COLOR & LEGEND16,17,18 Actuator or Visi-Color Marking: Color: I-O ON-OFF Dual/None White A B 1 Black C D 2 Red F G 3 Green H J 4 Blue K L 5 Yellow M N 6 Gray P Q 7 Orange R S 8 10 MOUNTING/BARRIERS1 1 2 319 4 5 619 A C E19 G J L19 B D F19 H J M19 STANDARD ROCKER BEZEL 6-32 x 0.195 inches 6-32 x 0.195 inches 6-32 x 0.195 inches ISO M3 x 5mm ISO M3 x 5mm ISO M3 x 5mm ROCKERGUARD BEZEL 6-32 x 0.195 inches 6-32 x 0.195 inches 6-32 x 0.195 inches ISO M3 x 5mm ISO M3 x 5mm ISO M3 x 5mm PUSH-TO-RESET BEZEL 6-32 x 0.195 inches 6-32 x 0.195 inches 6-32 x 0.195 inches ISO M3 x 5mm ISO M3 x 5mm ISO M3 x 5mm Marking Color: Single Color Rocker/Handle Black White White White White Black Black Black BARRIERS no yes yes no yes yes no yes yes no yes yes no yes yes no yes yes 11 AGENCY APPROVAL C D E H I L R Visi-Rocker White n/a Red Green Blue Yellow Gray Orange UL Recognized & CSA Accepted VDE Certified, UL Recognized & CSA Accepted TUV Certified, UL Recognized & CSA Accepted UL489 Construction: VDE Certified, UL Recognized & CSA Accepted UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted UL489 Construction: UL Recognized & CSA Accepted UL489 Construction: TUV Certified, UL Recognized & CSA Accepted 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Rocker UL Listed – Ordering Scheme | 13 C C 3 1 Series 2 Actuator B 0 4 Circuit 3 Poles 5 Aux/Alarm Switch 14 6 Frequency & Delay CODE 2 ACTUATOR 1 Two Color Visi-Rocker C Indicate ON, vertical legend D Indicate ON, horizontal legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend Single color J Vertical legend K Horizontal legend ROCKER STYLE DESCRIPTIONS INDICATE "ON" INDICATE "OFF" SINGLE COLOR CODE "F" CODE "J" CODE "C" INDICATE COLOR LOCATION LINE CODE "D" HORIZONTAL STYLE VERTICAL STYLE LINE LINE 3 POLES1 2 One LINE CODE "G" LINE CODE "K" 3 Two Three Series Trip (current) without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 11 12 14 16 21 22 24 K G 10 Mounting/ Barriers 11 Max. App. Rating 12 Agency Approval DC Ultra Short DC Short DC Medium DC Long 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium AMPERES 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 430 3.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 15 26 37 46 56 Stud 10-32 Screw 10-32 w/saddle & washer clamps Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 w/saddle & washer clamps 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 67 97,8 A7,8 C6,8 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 650 50.000 660 60.000 670 70.000 680 80.000 685 85.000 690 90.000 695 95.000 810 100.000 Stud M6 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 ACTUATOR COLOR & LEGEND11 5 AUXILIARY/ALARM SWITCH2 0 2 3 4 9 Actuator Color 8 TERMINAL LINE 4 CIRCUIT B 1 2 A 8 Terminal 7 CURRENT RATING (AMPERES) 4 1 SERIES C 1 450 7 Current Rating 6 8 9 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 26 428 448 468 528 548 56 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush Notes: 1 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 2 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 3 Available up to 50 amps maximum. 4 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum. 5 Terminal Code 1 available to 60 amps maximum. 6 Terminal Codes 2, 4, 5 & C available to 50 amps maximum. 7 Terminal Codes 3, 6, 9 & A available to 100 amps maximum. 8 Terminal Codes 9 & C are not VDE approved. 9 Color shown is visi and legend with remainder of rocker black 10 Dual = ON-OFF/I-O legend on actuator. 11 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker. 12 Rockerguard available with all actuator codes. 13 Barriers supplied on multi-pole units only. 14 2 & 3 pole circuit breakers required for 120/240 AC rating. Actuator or Visi-Color Marking: Color: ON-OFF Dual10 White B 1 Black D 2 Red G 3 Green J 4 Blue L 5 Yellow N 6 Gray Q 7 Orange S 8 10 MOUNTING/BARRIERS12 Standard Rocker Bezel A C B D Marking Color: Single Color Rocker/Handle Black White White White White Black Black Black BARRIERS13 Threaded Insert, 2 per pole 6-32 X 0.195 inches ISO M3 x 5mm yes yes Threaded Insert, 2 per pole 6-32 x 0.195 inches ISO M3 x 5mm yes yes Rockerguard Bezel 11 MAXIMUM APPLICATION RATING A B C D F K M 65 DC 125 DC 120/240 AC14 240 AC 277 AC 120 AC 80 DC 12 AGENCY APPROVAL A F G J without approvals UL 489 Listed, CSA Certified, & VDE Certified UL 489 Listed & CSA Certified UL489 Listed, CSA Certified & TUV Certified 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com Visi-Rocker White n/a Red Green Blue Yellow Gray Orange 14 | C-Series Flat Rocker UL Recognized – Ordering Scheme C 1 2 1 Series 2 Actuator B 0 4 Circuit 3 Poles 10 5 Aux/Alarm Switch 6 Frequency & Delay 1 SERIES C 2 Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend 3 POLES2 2 One 3 Two 4 CIRCUIT A3 B C D4 E4 Switch Only (No Coil) Series Trip (Current) Series Trip (Voltage) Shunt Trip (Current) Shunt Trip (Voltage) F4 G4 H4,5 K4,5 Three Relay Trip (Current) Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil 5 AUXILIARY/ALARM SWITCH6 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 03 107 11 12 14 16 207 21 22 24 26 1 2 1 8 Terminal 9 Actuator Color 10 Mounting/ Barriers E 11 Agency Approval 7 CURRENT RATING (AMPERES) 9 CODE ACTUATOR1 1 450 7 Current Rating DC 50/60Hz, Switch Only DC Instantaneous DC Ultra Short DC Short DC Medium DC Long 50/60Hz Instantaneous 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium 50/60Hz Long 6 8 9 30 31 32 34 36 428 448 468 528 548 568 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. DC 50/60Hz Instantaneous DC 50/60Hz Ultra Short DC 50/60Hz Short DC 50/60Hz Medium DC 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush Notes: 1 Push-to-reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all poles identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole. 3 Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810. 4 Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up to 50 amps maximum Current Rating. 5 Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are rated for intermittent duty only. 6 Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxilary switch codes 2, 3 & 4 are VDE approved. 7 Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 8 Available with Circuit Codes B & D only, and up to 50 amps maximum. 9 Current ratings 60-70 are available up to four poles maximum. Current ratings 71 - 100 are available up to two poles maximum. 10 Terminal Code 1 available to 60 amps maximum. 11 Terminal Codes 2,4,5 & C available to 50 amps maximum. 12 Terminal Codes 3,6 & 9 available to 100 amps maximum. 13 Terminal Code 7 available to 25 amps maximum. 14 Terminal Code A available to 100 amps maximum. 15 Terminal Codes 7, 9 & C are not VDE approved. 16 Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O legend. 17 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-to-reset bezel/shroud matches visi-color of rocker with actuator codes 5 & 6. 18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker. 19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be used in applications with a motor. 20 Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are available in ink stamping only. AMPERES 020 0.020 0250.025 0300.030 0350.035 0400.040 045 0.045 0500.050 055 0.055 060 0.060 0650.065 0700.070 075 0.075 0800.080 085 0.085 0900.090 0950.095 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 4303.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 650 50.000 6609 60.000 6709 70.000 6809 80.000 6859 85.000 6909 90.000 6959 95.000 8109 100.000 A3232DC A4848DC A6565DC J066AC J1212AC J1818AC J2424AC J4848AC J65 65AC K20120AC L40240AC VOLTAGE COIL (NOMINAL RATED VOLTAGE)7 CODE RATING A066DC A1212DC A1818DC A2424DC 8 TERMINAL 110 211 312 411 511 Stud 10-32 Screw 10-32 Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 612 713 915 A14 C15 Stud M6 0.250 Double Quick Connect 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 ACTUATOR COLOR & LEGEND16,17,18 Actuator or Visi-Color Marking: Color: I-O ON-OFF Dual/None White A B 1 Black C D 2 Red F G 3 Green H J 4 Blue K L 5 Yellow M N 6 Gray P Q 7 Orange R S 8 10 MOUNTING/BARRIERS1 STANDARD ROCKER BEZEL 1 6-32 x 0.195 inches 2 6-32 x 0.195 inches 319 6-32 x 0.195 inches 4 ISO M3 x 5mm 5 ISO M3 x 5mm 619 ISO M3 x 5mm RECESSED OFF ROCKER 7 6-32 x 0.195 inches 8 6-32 x 0.195 inches 9 6-32 x 0.195 inches A ISO M3 x 5mm C ISO M3 x 5mm E ISO M3 x 5mm PUSH-TO-RESET BEZEL B 6-32 x 0.195 inches D 6-32 x 0.195 inches F19 6-32 x 0.195 inches H ISO M3 x 5mm J ISO M3 x 5mm M19 ISO M3 x 5mm Marking Color: Single Color Rocker/Handle Black White White White White Black Black Black BARRIERS no yes yes no yes yes VOLTAGE <300 <300 ≥300 <300 <300 ≥300 no yes yes no yes yes <300 <300 ≥300 <300 <300 ≥300 no yes yes no yes yes <300 <300 ≥300 <300 <300 ≥300 11 AGENCY APPROVAL C E I L R Visi-Rocker White n/a Red Green Blue Yellow Gray Orange UL Recognized & CSA Accepted TUV Certified, UL Recognized & CSA Accepted UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted UL489 Construction: UL Recognized & CSA Accepted UL489 Construction: TUV Certified, UL Recognized & CSA Accepted 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Flat Rocker UL Listed – Ordering Scheme | 15 C 1 2 1 Series 2 Actuator B 0 4 Circuit 3 Poles 5 Aux/Alarm Switch 14 6 Frequency & Delay CODE Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend 3 POLES2 2 One 3 Two Three Series Trip (current) 5 AUXILIARY/ALARM SWITCH2 0 2 3 4 without Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 6 FREQUENCY & DELAY 11 12 14 16 21 22 24 9 Actuator Color 10 Mounting/ Barriers DC Ultra Short DC Short DC Medium DC Long 50/60Hz Ultra Short 50/60Hz Short 50/60Hz Medium 6 8 9 26 424 444 464 524 544 564 S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC Short, Hi-Inrush DC Medium, Hi-Inrush DC Long, Hi-Inrush 1 Notes: 2 Push-to-reset actuators have OFF portion of rocker shrouded. 3 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 4 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 5 Available up to 50 amps maximum. 6 Current ratings 71 - 100 with VDE approvals are available up to two poles maximum. 7 Terminal Code 1 available to 60 amps maximum. 8 Terminal Codes 2, 4, 5 & C available to 50 amps maximum. 9 Terminal Codes 3, 6, 9 & A available to 100 amps maximum. 10 Terminal Codes 9 & C are not VDE approved. 11 Color shown is visi and legend with remainder of rocker black 12 Dual = ON-OFF/I-O legend on actuator. 13 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker. 14 Legend on push-to-reset bezel/shroud is white when single color rocker is ordered. Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator codes 15 5 & 6. 16 Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker are available in ink stamping only. 17 Barriers supplied on multi-pole units only. 18 2 & 3 pole circuit breakers required for 120/240 AC rating. 295 0.950 410 1.000 512 1.250 415 1.500 5171.750 420 2.000 522 2.250 4252.500 5272.750 4303.000 4353.500 440 4.000 445 4.500 4505.000 4555.500 4606.000 4656.500 8 TERMINAL 17 28 39 48 58 4 CIRCUIT B AMPERES 210 0.100 2150.150 220 0.200 2250.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 2550.550 2600.600 265 0.650 2700.700 2750.750 2800.800 2850.850 290 0.900 ACTUATOR1 1 1 2 A 8 Terminal K G 11 Max. App. Rating 12 Agency Approval 7 CURRENT RATING (AMPERES) 5 1 SERIES C 2 450 7 Current Rating Stud 10-32 Screw 10-32 Stud 1/4-20 Stud M5 x 0.8 Screw M5 x 0.8 4707.000 475 7.500 4808.000 4858.500 4909.000 4959.500 61010.000 71010.500 61111.000 71111.500 61212.000 71212.500 61313.000 61414.000 615 15.000 61616.000 61717.000 69 99,10 A 9 C8,10 618 18.000 62020.000 62222.000 624 24.000 62525.000 63030.000 63535.000 64040.000 650 50.000 660 60.000 670 70.000 680 80.000 685 85.000 690 90.000 695 95.000 810 100.000 Stud M6 7/16” Clip Terminal Plug-In Stud 5/16” Clip Terminal 9 ACTUATOR COLOR & LEGEND12 Actuator or Visi-Color Marking: Color: ON-OFF Dual11 White B 1 Black D 2 Red G 3 Green J 4 Blue L 5 Yellow N 6 Gray Q 7 Orange S 8 10 MOUNTING/BARRIERS12 A C E F B D STANDARD ROCKER BEZEL Threaded Insert, 2 per pole 6-32 X 0.195 inches ISO M3 x 5mm RECESSED OFF ROCKER14 Threaded Insert, 2 per pole 6-32 x 0.195 inches ISO M3 x 5mm PUSH-TO-RESET BEZEL13 Threaded Insert, 2 per pole 6-32 x 0.195 inches ISO M3 x 5mm Marking Color: Single Color Rocker/Handle Black White White White White Black Black Black BARRIERS15 yes yes yes yes yes yes 11 MAXIMUM APPLICATION RATING A B C D F K M 65 DC 125 DC 120/240 AC16 240 AC 277 AC 120 AC 80 DC 12 AGENCY APPROVAL A G J without approvals UL 489 Listed & CSA Certified UL489 Listed, CSA Certified & TUV Certified 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com Visi-Rocker White n/a Red Green Blue Yellow Gray Orange 16 | C-Series Handle – Circuit & Terminal Diagrams .960 [24.38] .311 DIA [Ø7.90] .558 [14.17] Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Available on Series Trip and Switch Only Circuits when called for on multi-pole units. Only one aux. switch is normally supplied, as viewed in mulit-pole identification scheme. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Handle – Circuit & Terminal Diagrams | 17 Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Schematic shown represents current trip circuits. 4 Available only as special catalog number. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 18 | C-Series Handle – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Handleguard – Form & Fit Drawings | 19 Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 20 | C-Series Arc Chute Barrier UL Recognized/Listed – Form & Fit Drawings Notes: 1 Only 1-pole and 3-pole configurations shown. Arc chute (w/o barrier) and arc chute barrier also available for 2-pole construction. 2 Dimensions apply to all variations shown. 3 Notice that line and load terminal orientation for indicate on and indicate off rocker circuit breakers are opposite. 4 Screw type terminals shown for Rocker style (CF1, C11, etc) circuit breakers. For other terminal configurations see circuit and terminal diagrams. 5 All dimensions are in inches [millimeters]. 6 Tolerance ± .020 unless otherwise specified. 7 Must be ordered under a special catalog number. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Parallel Pole – Form & Fit Drawings | 21 Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 22 | C-Series Sealed Toggle – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Rocker – Circuit & Terminal Diagrams | 23 Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Schematic shown represents current trip circuit. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com 24 | C-Series Rocker – Form & Fit Drawings Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON. 2 For pole orientation with horizontal legend, rotate front view clockwise 90°. 3 All dimensions are in inches [millimeters]. 4 Tolerance ±.020 [.51] unless otherwise specified. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com C-Series Flat Rocker – Form & Fit Drawings | 25 Notes: 1 For pole orientation with horizontal legend, rotate front view clockwise 90°. 2 All dimensions are in inches [millimeters]. 3 Tolerance ±.020 [.51] unless otherwise specified. 60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231 Email: [email protected] • www.carlingtech.com Worldwide Headquarters Carling Technologies, Inc. 60 Johnson Avenue • Plainville, CT 06062 Phone: (860) 793-9281 • Fax: (860) 793-9231 Email: [email protected] • www.carlingtech.com East Region Sales Office, CT • [email protected] Midwest Region Sales Office, IL • [email protected] West Region Sales Office, CA • [email protected] Asia-Pacific Headquarters Carling Technologies, Asia-Pacific Ltd., Kowloon, Hong Kong Int + 852-2737-2277 • Fax: Int + 852-2736-9332 Email: [email protected] Shenzhen, China • [email protected] Shanghai, China • [email protected] Pune, India • [email protected] Kaohsiung, Taiwan • [email protected] Yokohama, Japan • [email protected] Europe/Middle East/Africa Headquarters Carling Technologies LTD 4 Airport Business Park, Exeter Airport, Clyst Honiton, Exeter, Devon, EX5 2UL, UK Int + 44 1392-364422 • Fax: Int + 44 1392-364477 Email: [email protected] GmbH, Germany • [email protected] SAS, France • [email protected] CB_C_09_2014