Bulletin 140M Motor Protectors 3Circuit Breaker 3 3 Bulletin 140M Cat. No. 140M-C2E Cat. No. 140M-F8E • Current Range 0.1…45 A • With 140-CMN up to 90 A • Type 2 Coordination with Bulletin 100-C Contactors • UL Listed • “Self-protected” Type E Manual Combination Starters • Manual Starter • Motor Disconnect • Group Motor Installation • Visible Trip Indication • Rotary Actuator • High Current Limiting • High Switching Capacity TABLE OF CONTENTS Description Page Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-156 Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-160 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-163 Description Page Specifications Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-169 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-179 Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-183 Type 2 Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-185 Description The Bulletin 140M Motor Protector provides short circuit and overload protection for individual motor loads. A wide range of accessories makes installation and wiring easy. Motor protectors may be applied as Manual Starters, Group Motor Starters, Motor Disconnects, and Manual Combination Starters. Conformity to Standards: Approvals: IEC 947-1/2/4 CE IEC 204-1 CSA Certified CSA, C22.2 No.14 UL Listed UL 508 Construction Type E Self-Protected Manual Combination Starter. Manual Motor Controller suitable for Group Installation. Meets IEC Circuit Breaker requirements per IEC 947-2. Does not meet UL489 requirements for molded case circuit breakers in North America. Your order must include: • Cat. No. of the motor protector selected. • If required, Cat. No. of any accessories. 3-155 Bulletin 140M and 190S/190E Motor Protectors/Compact Starters/Eco Starters 3 Product Overview General Information The new Bulletin 140M Motor Protectors provide Class 10 overload protection as well as current limiting short-circuit protection for individual motor loads. They are approved for use as circuit breakers per IEC 947-2 for applications outside of North America, but in the United States and Canada, they are UL/CSA listed as Manual Starters with the optional approvals for Motor Disconnecting and Group Motor applications. 400V, 50 Hz, 3-Phase Power Supply 140M-C2E -C10 Circuit Breaker Applications – IEC Additionally, these new devices are UL/CSA listed as Self-Protected (Type E) Manual Combination Starters — eliminating the requirement for additional short-circuit protection in many applications. This reduces both panel space and cost in multi-motor installations and eliminates the restrictive NEC/CEC rules that pertained to Manual Starters used in Group Motor applications. Motor Protector as IEC Circuit Breaker Contactor 100-C09 14 AWG 7.6A Fan #2 5 HP Motor 480V, 60 Hz, 3-Phase Power Supply The following information is provided to aid in proper system design utilizing the capabilities of the new Bulletin 140M Motor Protectors in North American applications. Please be sure to follow all local and national codes for your particular installation. Circuit Breaker Applications – IEC The new Bulletin 140M Motor Protectors are current limiting IEC circuit breakers (IEC 947-2) that also provide Class 10 motor overload protection. Additionally, they meet the IEC requirements for applications such as: • Disconnector (IEC 947-2) • Main Switch (IEC 204-1) 194R-NN030P3 30A FUSE Fusible Disconnect 3 Fuses Manual Starter Applications – UL/CSA 140M-C2E -C10 Motor Protector as Manual Starter 14 AWG • Emergency Off (IEC 204-1) The Bulletin 140M Motor Protectors cannot be applied in North America as circuit breakers, however, since they do not meet the UL specification for circuit breakers (UL 489). 7.6A Fan #1 5 HP Motor 480V, 60 Hz, 3-Phase Power Supply Manual Starter Applications – UL/CSA The new Bulletin 140M Motor Protectors are an excellent choice for manual starting applications. As UL/CSA listed manual motor controllers they provide motor overload protection, but a separate short-circuit protective device must still be used. The fuse or circuit breaker used for the short-circuit protection may be sized to the maximum allowable per NEC Article 430 in the U.S. and CEC Rule 28-200 in Canada. 194R-NJ030P3 30A Fusible Disconnect FUSE 3 Fuses Contactor 100-C09 Motor Disconnecting Applications – UL/CSA The new Bulletin 140M Motor Protectors are also UL/CSA listed as manual motor controllers with the optional approval “Suitable for use as a motor disconnect” when a lockable twist knob is used. This UL listing is new in 1999 and allows the 140M’s to be applied as “at-motor” disconnects. All manual starters used in such applications must be marked as “suitable for use as a motor disconnect” per UL 508. At motor disconnects are required by the NEC if the motor cannot be seen from the main panel disconnect. 193-E Overload 140M-C2E -C10 Motor Disconnecting Applications – UL/CSA 14 AWG 7.6A Fan #1 5 HP 3-156 Motor Protector as At-Motor Disconnect Motor Bulletin 140M and 190S/190E Motor Protectors/Compact Starters/Eco Starters Product Overview, Continued Group Motor Applications — UL/CSA The new 140M Motor Protectors are also UL/CSA listed as manual starters for use in Group Motor installations. This listing allows the 140M Motor Protectors to be used as manual starters providing individual overload protection with a single set of fuses or a circuit breaker providing the short circuit protection for the “Group” of motors. This is the most popular application for these products in North America and greatly reduces both panel space and cost versus the traditional use of fuses or circuit breakers in each motor branch circuit. However, there are several NEC rules to follow for Group Motor installations and one of these rules can dramatically affect panel size and layout. Per NEC Article 430-53(d), the conductors of any tap supplying a single motor must have an ampacity less than one-third that of the branch-circuit conductors. This limits the number of motors that can be “grouped” under one set of fuses or circuit breakers. See the following examples of two typical group motor applications. For further assistance on how to properly apply Bulletin 140M Motor Protectors in Group Motor applications, please see Publications 0140-2.3 and 6219-NP. 480V, 60 Hz, 3-Phase Power Supply 194R-NJ100P3 100A 80HP Fuse 45 A Fusible Disconnect 3 Fuses 8 AWG Commoning Links 140M-C2E 140M-C2E -C10 -C10 -C10 100-C09 100-C09 100-C16 14 AWG 7.6A Fan #1 5 HP 14 AWG 7.6A Fan #2 5 HP 140M-C2E 14 AWG 7.5A Heater #1 140M-C2E 140M-C2E -C10 -C16 100-C16 14 AWG 100-C16 Motor Protectors In this example, a single panel controls 5 motors. This Group Installation meets all of the required NEC rules resulting in a very compact, cost effective, and attractive panel design. Contactors 14 AWG 7.5A Heater #2 14.0A Pump #1 5 HP Motors 480V, 60 Hz, 3-Phase Power Supply 194R-NJ100P3 100A 80HP FUSE 50A Fusible Disconnect 3 Fuses 6 AWG 8 AWG FUSE 35A 14 AWG 3 Fuses 3 Fuses 8 AWG FUSE 25A 14 AWG Commoning Links 140M-C2E 140M-C2E -C10 -C10 100-C09 100-C09 14 AWG 7.6A Fan #1 5 HP 14 AWG 7.6A Fan #2 5 HP 140M-C2E -C10 100-C16 14 AWG 7.5A Heater #1 140M-C2E -C10 100-C16 14 AWG 7.5A Heater #2 140M-C2E -C16 100-C16 Motor Protectors Contactors 14 AWG 14.0A Pump #1 10 HP In this example, we have the same group of 5 motors, only now the pump motor is 10 HP rather than 5 HP. This Group Installation no longer meets the NEC rules since the wire feeding the group has increased from #8 AWG to #6 AWG, and the ampacity of the #14 AWG motor circuit conductors is less than one third that of the #6 AWG branch circuit conductors. This forces the Group to be split, with 1 set of fuses protecting the 4 small motors, and 1 set of fuses protecting the 10 HP pump motor. The third set of fuses just below the disconnect is for protection of the #6 AWG branch circuit conductors. Motors 3-157 Bulletin 140M and 190S/190E Motor Protectors/Compact Starters/Eco Starters Product Overview, Continued Self-Protected (Type E) Manual Combination Starter Applications — UL/CSA The new 140M Motor Protectors, with improved current limiting and breaking capacity, are now UL/CSA listed as self-protected (Type E) Manual Combination Starters. This new listing allows the 140M Motor Protectors to be used as short circuit protection for individual motors, in addition to overload protection. This eliminates the need for fuses or a circuit breaker to provide short circuit protection and also eliminates all of the NEC/CEC Group Motor rules for installations involving multi-motor panels. The new Bulletin 140M Motor Protectors are standard components of the MCS Modular Control System. This provides for maximum flexibility and minimum panel size without the restrictive and cumbersome rules involved with typical multi-motor (group) applications. The 140M Motor Protectors, when used as self-protected (Type E) Manual Combination Starters, are only suitable for use on Wye power systems if the system voltage exceeds 240V (i.e., 480Y/277V and 600Y/347V). Self-Protected (Type E) Installations for Multi-Motor Panels 480V, 60 Hz, 3-Phase Power Supply 194R-NJ100P3 100A 80HP FUSE 50A Fusible Disconnect 3 Fuses 6 AWG 480Y/277V, 60 Hz, 3-Phase Power Supply 8 AWG 194R-NN100P3 100A 80HP FUSE 35A Non-Fusible Disconnect Commoning Links 140M-C2E 140M-C2E -C10 -C10 -C10 100-C09 100-C09 100-C16 7.6A Fan #1 5 HP 3 Fuses 8 AWG 6 AWG 14 AWG 14 AWG 3 Fuses 14 AWG 7.6A Fan #2 5 HP 140M-C2E 14 AWG 7.5A Heater #1 140M-C2E 140M-C2E -C10 -C16 100-C16 14 AWG 7.5A Heater #2 Self-Protected (Type E) Installation 100-C16 Contactors 14.0A Pump #1 10 HP Motors 140M-C2E -C10 -C10 100-C09 100-C09 14 AWG 14 AWG 14 AWG Commoning Links 140M-C2E Motor Protectors FUSE 25A 7.6A Fan #1 5 HP 14 AWG 140M-C2E -C10 100-C16 14 AWG 7.6A Fan #2 5 HP 7.5A Heater #1 140M-C2E -C10 100-C16 14 AWG 7.5A Heater #2 140M-C2E -C16 100-C16 Motor Protectors Contactors 14 AWG 14.0A Pump #1 10 HP Motors Group Motor Installation The new listing of the 140M as a self-protected (Type E) combination starter greatly simplifies multi-motor panel design. As a self-protected combination starter the 140M provides both overload and short circuit protection for the motors and the NEC/CEC group motor rules no longer apply. In the diagrams above, the same 5 motors are shown in both a self-protected (Type E) installation as well as the previous example of a Group Motor Installation. The rules in the NEC/CEC codes for the Group Motor Installation do not apply since each motor already has short circuit protection provided by the 140M’s— i.e., the five motors are no longer “grouped” under a single short circuit protective device (fuses or circuit-breaker). The three sets of fuses are no longer required and the 140M’s may simply be selected for each individual motor load according to the motor full load current. A non-fusible disconnect switch for the main panel disconnecting function completes the self-protected (Type E) Manual Combination Starter installation. Also, for remote operation a contactor may be added to the installation Type 2 coordination may be achieved with the 100C in this case (see page 3-185). 3-158 Bulletin 140M and 190S/190E Motor Protectors/Compact Starters/Eco Starters Product Overview, Continued Self-Protected (Type E) Installations for Single Motor Panels 480V, 60 Hz, 3-Phase Power Supply 194R-NJ100P3 100 A 80 HP Fusible Disconnect FUSE 25 A 3 Fuses 480Y/277V, 60 Hz, 3-Phase Power Supply 140M-C2E -C16 Motor Protector 100-C16 Contactor Contactor 100-C16 193-E 14 AWG 14 AWG 14.0A Pump #1 10 HP Overload Relay Motor 14.0 A Pump #1 10 HP Motor The new listing of the 140M as a self-protected combination starter provides for extremely cost-effective and compact single motor installations as well. In the diagrams above, a panel consisting of a self-protected (Type E) Manual Combination Starter and a contactor is compared with a traditional fusible combination starter panel. The Type E combination starter consists of a Bulletin 140M and a 100-C contactor. The Bulletin 140M provides both the overload and short circuit protection as well as the disconnecting function for the motor while the 100-C contactor allows for remote operation via push buttons. By contrast, the traditional fusible combination starter consists of a 194R fusible disconnect switch for disconnecting function fuses for short circuit protection, a 100-C contactor for remote operation and a 193-E overload relay for overload protection. 3-159 Bulletin 140M Motor Protectors 33-160 Product Selection Motor Protectors For Use as Manual Starters and Motor Disconnects Cat. No. 140M-C Cat. No. 140M-D Cat. No. 140M-F Motor Protectors — For Use as Manual Starters Typical 1-phase [HP] ➊ Current Adjustment Range [A] 115V 230V 0.10…0.16 — — 0.16…0.25 — — 0.25…0.40 — 0.40…0.63 Typical 3-phase [HP] ➊ 200V Cat. No. ➋ 230V 460V 575V — — — — 140M-C2E-A16 ➌➍ — — — — 140M-C2E-A25 ➌➍ — — — — — — — — — 0.63…1.0 — — — — 1/2 3/4 140M-C2E-B10 ➌➍ 1.0…1.6 — 1/10 — — 3/4 1 140M-C2E-B16 ➌➍ 1.6…2.5 1/10 1/6 1/2 1/2 1-1/2 2 140M-C2E-B25 ➌➍ 2.5…4 1/8 1/3 1 1 3 3 140M-C2E-B40 ➌ 4…6.3 1/4 3/4 1-1/2 2 3 5 140M-C2E-B63 ➌ 6.3…10 1/2 1-1/2 3 3 7-1/2 10 140M-C2E-C10 ➌ 140M-C, High Break 140M-C2E-A40 ➌➍ 140M-C2E-A63 ➌➍ 10…16 1 3 3 5 10 10 140M-C2E-C16 ➌ 14.5…20 1-1/2 3 5 7-1/2 15 20 140M-C2E-C20 18…25 2 3 7-1/2 10 20 25 140M-C2E-C25 140M-D, High Break PLUS 1.6…2.5 1/10 1/6 1/2 1/2 1-1/2 2 140M-D8E-B25 ➍ 2.5…4 1/8 1/3 1 1 3 3 140M-D8E-B40 ➍ 4…6.3 1/4 3/4 1-1/2 2 3 5 140M-D8E-B63 ➍ 6.3…10 1/2 1-1/2 3 3 7-1/2 10 140M-D8E-C10 ➍ 10…16 1 3 3 5 10 10 140M-D8E-C16 ➌➍ 14.5…20 1-1/2 3 5 7-1/2 15 20 140M-D8E-C20 ➌➍ 18…25 2 3 7-1/2 10 20 25 140M-D8E-C25 ➍ 140M-F, High Break PLUS 6.3…10 1/2 1-1/2 3 3 7-1/2 10 140M-F8E-C10 10…16 1 3 3 5 10 10 140M-F8E-C16 14.5…20 1-1/2 3 5 7-1/2 15 20 140M-F8E-C20 18…25 2 3 5 10 20 25 140M-F8E-C25 ➌➍ 23…32 3 5 10 10 25 30 140M-F8E-C32 ➌➍ 32…45 3 7-1/2 15 15 30 40 140M-F8E-C45 ➍ 140-CMN 16…25 2 5 7-1/2 10 20 25 140-CMN-2500 25…40 3 7-1/2 10 15 30 40 140-CMN-4000 40…63 5 10 20 20 50 60 140-CMN-6300 63…90 7-1/2 20 30 30 60 75 140-CMN-9000 ➊ Horsepower ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load current and service factor. • For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range. Example: Motor F.L.C. = 4.2 A; S.F. = 1.0. (4.2 A x 0.9 = 3.78 A.) Select Cat. No. 140M-C2E-B40. ➋ Magnetic trip is fixed at 13x the maximum value of the current adjustment range. ➌ Devices with a fixed magnetic trip set at 16-20x the maximum value of the current adjustment range are available if nuisance tripping occurs (as with some high-efficiency motors). To order these products, change the “E” in the cat. no. to a “T” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2T-A16). ➍ Devices without a thermal trip (i.e., current adjustment range) are also available if separate motor overload protection is required. To order these products, change the “E” in the cat. no. to an “N” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2N-A16). 3-160 Bulletin 140M Motor Protectors Product Selection, Continued Motor Protectors For Use as Manual Starters in Group Installations Cat. No. 140M-C Cat. No. 140M-D Cat. No. 140M-F Motor Protectors for Group Installation Current Adjustment Range [A] Max. Short-Circuit Current [kA] For Use With Cat. No. ➋ Max Fuse or Circuit Breaker [A] Cat. No. ➊ 480V 600V 0.10…0.16 65 47 100-C09, 100-M05 400 140M-C2E-A16 ➌➍ 0.16…0.25 65 47 100-C09, 100-M05 400 140M-C2E-A25 ➌➍ 0.25…0.40 65 47 100-C09, 100-M05 400 140M-C2E-A40 ➌➍ 0.40…0.63 65 47 100-C09, 100-M05 400 140M-C2E-A63 ➌➍ 0.63…1.0 65 47 100-C09, 100-M05 400 140M-C2E-B10 ➌➍ 1.0…1.6 65 47 100-C09, 100-M05 400 140M-C2E-B16 ➌➍ 1.6…2.5 65 5 100-C09, 100-M05 400 140M-C2E-B25 ➌➍ 2.5…4 65 5 100-C09, 100-M05 400 140M-C2E-B40 ➌ 4…6.3 65 5 100-C09, 100-M05 400 140M-C2E-B63 ➌ 6.3…10 65 5 100-C09, 100-M05 400 140M-C2E-C10 ➌ 140M-C, High Break 10…16 10 5 100-C12 400 140M-C2E-C16 ➌ 14.5…20 10 5 100-C16 400 140M-C2E-C20 18…25 10 5 100-C23 400 140M-C2E-C25 140M-D, High Break PLUS 1.6…2.5 65 10 100-C09, 100-M05 400 140M-D8E-B25 ➍ 2.5…4 65 10 100-C09, 100-M05 400 140M-D8E-B40 ➍ 4…6.3 65 10 100-C09, 100-M05 400 140M-D8E-B63 ➍ 6.3…10 65 10 100-C09, 100-M05 400 140M-D8E-C10 ➍ 10…16 65 10 100-C12 400 140M-D8E-C16 ➌➍ 14.5…20 65 5 100-C16 400 140M-D8E-C20 ➌➍ 18…25 25 5 100-C23 400 140M-D8E-C25 ➍ 140M-F, High Break PLUS 6.3…10 65 10 100-C09 500 140M-F8E-C10 10…16 65 10 100-C12 500 140M-F8E-C16 14.5…20 65 10 100-C16 500 140M-F8E-C20 18…25 65 10 100-C23 500 140M-F8E-C25 ➌➍ 23…32 65 10 100-C30 500 140M-F8E-C32 ➌➍ 32…45 50 10 100-C37 500 140M-F8E-C45 ➍ 140-CMN 16…25 65 42 100-C16 1000 140-CMN-2500 25…40 65 42 100-C30 1000 140-CMN-4000 40…63 65 42 100-C43 1000 140-CMN-6300 63…90 65 30 100-C72 1000 140-CMN-9000 ➊ Magnetic trip is fixed at 13x the maximum value of the current adjustment range. ➋ Ratings apply to specified or larger contactor. ➌ Devices with a fixed magnetic trip set at 16-20x the maximum value of the current adjustment range are available if nuisance tripping occurs (as with some high-efficiency motors). To order these products, change the “E” in the cat. no. to a “T” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2T-A16). ➍ Devices without a thermal trip (i.e., current adjustment range) are also available if separate motor overload protection is required. To order these products, change the “E” in the cat. no. to an “N” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2N-A16). ➎ For Type 2 coordination see pages 3-185 and 3-186. 3-161 Bulletin 140M Motor Protectors 3 Product Selection, Continued Motor Protectors For Use as Self-Protected (Type E) Manual Combination Motor Controllers Cat. No. 140M-C Cat. No. 140M-F Motor Protectors For Use As Self-Protected (Type E) Manual Combination Motor Controller Typical 1-phase [HP] ➊ Current Adjustment Range [A] 115V 230V Max. Short-Circuit Current [kA] Typical 3-phase [HP] ➊ 200V 230V 460V 575V 480Y/277V Cat. No. ➋ 140M-C, High Break 0.10...0.16 — — — — — — 65 140M-C2E-A16 0.16...0.25 — — — — — — 65 140M-C2E-A25 0.25...0.40 — — — — — 65 140M-C2E-A40 0.40...0.63 — — — — — 65 140M-C2E-A63 0.63...1.0 — — — — 1/2 3/4 65 140M-C2E-B10 1.0...1.6 — 1/10 — — 3/4 1 65 140M-C2E-B16 1.6...2.5 1/10 1/6 1/2 1/2 1-1/2 2 65 140M-C2E-B25 2.5...4 1/8 1/3 1 1 3 3 65 140M-C2E-B40 4...6.3 1/4 3/4 1-1/2 2 3 5 65 140M-C2E-B63 6.3...10 1/2 1-1/2 3 3 7-1/2 10 65 140M-C2E-C10 10...16 1 3 3 5 10 10 10 140M-C2E-C16 14.5...20 1-1/2 3 5 7-1/2 15 20 10 140M-C2E-C20 18...25 2 3 7-1/2 10 20 25 10 140M-C2E-C25 140M-D, High Break PLUS 1.6...2.5 1/10 1/6 1/2 1/2 1-1/2 2 65 140M-D8E-B25 2.5...4 1/8 1/3 1 1 3 3 65 140M-D8E-B40 4...6.3 1/4 3/4 1-1/2 2 3 5 65 140M-D8E-B63 6.3...10 1/2 1-1/2 3 3 7-1/2 10 65 140M-D8E-C10 10...16 1 3 3 5 10 10 65 140M-D8E-C16 14.5...20 1-1/2 3 5 7-1/2 15 20 65 140M-D8E-C20 18...25 2 3 7-1/2 10 20 25 25 140M-D8E-C25 140M-F, High Break PLUS 6.3...10 1/2 1-1/2 3 3 7-1/2 10 ➌ 140M-F8E-C10 10...16 1 3 3 5 10 10 ➌ 140M-F8E-C16 14.5...20 1-1/2 3 5 7-1/2 15 20 ➌ 140M-F8E-C20 18...25 2 3 5 10 20 25 ➌ 140M-F8E-C25 23...32 3 5 10 10 25 30 ➌ 140M-F8E-C32 32...45 3 7-1/2 15 15 30 40 ➌ 140M-F8E-C45 ➊ Horsepower ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load current and service factor. • For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range. Example: Motor F.L.C. = 4.2 A; S.F. = 1.0. (4.2 A x 0.9 = 3.78 A.) Select Cat. No. 140M-C2E-B40. ➋ Magnetic trip is fixed at 13x the maximum value of the current adjustment range. ➌ UL Pending. Contact your local Allen-Bradley Sales Office. 3-162 Bulletin 140M Motor Protectors Accessories Description Operator Position ➊ OFF ON Tripped Term. No. Desc. Connection Diagram ➋ For Use With Cat. No. 140M 140M-C-AFA10 140M 140M-C-AFA01 140M 140M-C-AFA11 140M 140M-C-AFA20 140M 140M-C-AFA02 140M 140M-C-ASA20 140M 140M-C-ASA02 140M 140M-C-ASA11 13 O X O 13-14 N.O. Aux 14 I >> 11 X O X 11-12 N.C. Aux 12 I >> Front-Mounted Auxiliary Contact • 1-pole or 2-pole • No additional space required O X O 13-14 13 21 14 22 13 23 14 24 N.O. Aux I >> X O X 21-22 N.C. Aux O X O 13-14 N.O. Aux I >> O X O 23-24 N.O. Aux X O X 11-12 N.C. Aux 11 21 12 22 I >> Right Side-Mounted Auxiliary Contact • 2-pole • Adds 9 mm to the width of the device X O X 21-22 N.C. Aux O X O 33-34 N.O. Aux O X O 43-44 N.O. Aux X O X 31-32 N.C. Aux X O X 41-42 N.C. Aux O X O 33-34 N.O. Aux X O X 41-42 N.C. Aux 33 43 34 44 31 41 32 42 I >> I >> 33 41 34 42 I >> ➊ X = Contact Closed O = Contact Open ➋ 140 M Operator Overload (thermal) Trip I >> Short-Circuit (magnetic) Trip 3-163 Bulletin 140M Motor Protectors Accessories, Continued Description Operator Position ➊ Front-Mounted Trip Contact • 2-pole • Indicates tripping of device • No additional space required OFF ON Tripped Term. No. Desc. O X O 13-14 N.O. Aux O O X 27-28 N.O. Trip (Short-Circuit & Overload) X O X 11-12 N.C. Aux O O X 27-28 N.O. Trip (Short-Circuit & Overload) O O X 57-58 N.O. Trip (Short-Circuit & Overload) O O Right Side-Mounted Trip Contact • 2-pole • Indicates tripping of Motor Protector • Adds 9 mm to the width of the circuit breaker X X O X X O X ➊ X = Contact Closed O = Contact Open ➋ 140 M Operator Overload (thermal) Trip I >> Short-Circuit (magnetic) Trip 3-164 O O X X O X X O X X X O O X O O X O 67-68 N.O. Trip (Short-Circuit) 57-58 N.O. Trip (Short-Circuit & Overload) 65-66 N.C. Trip (Short-Circuit) 55-56 N.C. Trip (Short-Circuit & Overload) 67-68 N.O. Trip (Short-Circuit) 55-56 N.C. Trip (Short-Circuit & Overload) 65-66 N.C. Trip (Short-Circuit) 77-78 N.O. Trip (Short-Circuit) 65-66 N.C. Trip (Short-Circuit) Connection Diagram ➋ 13 27 14 28 For Use With Cat. No. 140M 140M-C-AFAR10A10 140M 140M-C-AFAR10A01 140M 140M-C-ASAR10M10 140M 140M-C-ASAR10M01 140M 140M-C-ASAR01M10 140M 140M-C-ASAR01M01 140M 140M-C-ASAM11 I >> 11 27 12 28 I >> 57 67 58 68 I >> 57 65 58 66 I >> 55 67 56 68 55 65 56 66 I >> I >> 77 65 78 66 I >> Bulletin 140M Motor Protectors 3 Accessories, Continued Description Operator Position ➊ OFF ON O X Tripped Term. No. O 13-14 Desc. N.O. Aux Connection Diagram ➋ For Use With 140-CMN 140-CA20 O Front-Mounted Auxiliary Contacts • Internal • 2-Pole X X O O X 23-24 11-12 13 23 14 24 140-CMN 140-CMN 140-CA02 X O O X X O 21-22 13-14 11 21 12 22 140-CMN 140-CA11 X O O O X X 21-22 N.C. Aux 37-38 N.O. Trip (Overload) O X 43-44 140-CA11 13 21 14 22 I >> 140-CMN 140-CT10-10 a O 140-CA02 I >> N.C. Aux N.O. Aux 140-CA20 I >> N.O. Aux N.C. Aux Cat. No. 37 43 38 44 140-CT10-10 I >> N.O. Trip (Short-Circuit) b a) Overload Trip b) Short-Circuit Trip X X O 35-36 N.C. Trip (Overload) 140-CMN 140-CT01-01 35 a Front-Mounted Trip Indicating Auxiliary Contacts • Internal • 2-Pole X X O 41-42 41 140-CT01-01 I >> N.C. Trip (Short-Circuit) b 36 42 a) Overload Trip b) Short-Circuit Trip X X O 35-36 N.C. Trip (Overload) 140-CT01-10 a O O X 43-44 140-CMN 140-CMN 35 43 36 44 140-CT01-10 I >> N.O. Trip (Short-Circuit) b a) Overload Trip b) Short-Circuit Trip O O X 37-38 N.O. Trip (Overload) 140-CMN 140-CT10-01 a X X O 41-42 N.C. Trip (Short-Circuit) 37 41 38 42 140-CT10-01 I >> b a) Overload Trip b) Short-Circuit Trip ➊ ➋ X = Contact Closed O = Contact Open 140 M Operator Overload (thermal) Trip I >> Short-Circuit (magnetic) Trip 3-165 Bulletin 140M Motor Protectors 3 Accessories, Continued Description Connection Diagram ➊ Undervoltage Trip • Left-side mounted • Adds 18 mm to the width of the circuit breaker • Trips motor protector when voltage is removed D1 U< Shunt Trip • Left-side mounted • Adds 18 mm to the width of the circuit breaker • Trips motor protector when voltage is applied Undervoltage Trip Unit • Internal, front mounted • Integrated short circuit trip indication • Trips motor protector when voltage is removed D2 I >> C1 C2 I >> 24V, 50 Hz/28V, 60 Hz 110V, 50 Hz/127V, 60 Hz 220…230V, 50 Hz 240…260V, 60 Hz 240V, 50 Hz/277V, 60 Hz 380…400V, 50 Hz/440…460V, 60 Hz 415V, 50 Hz/480V, 60 Hz 21V, 50 Hz/24V, 60 Hz 110V, 50Hz/27V, 60 Hz 24V, 50 Hz/28V, 60 Hz 110V, 50 Hz/127V, 60 Hz 220…230V, 50 Hz 240…260V, 60 Hz 240V, 50 Hz/277V, 60 Hz 380…400V, 50 Hz/440…460V, 60 Hz 415V, 50 Hz/480V, 60 Hz 21V, 50 Hz/24V, 60 Hz 110V, 50 Hz/127V, 60 Hz For Use With Cat. No. 140M 140M-C-UXK 140M-C-UXD 140M-C-UXF 140M-C-UXA 140M-C-UXT 140M-C-UXN 140M-C-UXB 140M-C-UXJ 140M-C-UXC 140M 140M-C-SNK 140M-C-SND 140M-C-SNF 140M-C-SNA 140M-C-SNT 140M-C-SNN 140M-C-SNB 140M-C-SNJ 140M-C-SNC 140-CMN 140-CUV... 43 b I >> D1 U< 24V 50/60 Hz 110V 50 Hz/120V 60 Hz 140-CMN 220V 50 Hz/240V 60 Hz 140-CUV-KJ 140-CUV-D 140-CUV-A 24V 50/60 Hz 110V 50 Hz/120V 60 Hz 140-CMN 220V 50 Hz/240V 60 Hz 140-CRT-KJ 140-CRT-D 140-CRT-A 44 D2 b) Short-Circuit Trip 140-CMN Shunt Trip Unit • Internal, front mounted • Integrated short circuit trip indication • Trips motor protector when voltage is applied 140-CRT... 43 b I >> C1 44 C2 b) Short-Circuit Trip ➊ 140 M Operator Overload (thermal) Trip I >> Short-Circuit (magnetic) Trip 3-166 Bulletin 140M Motor Protectors Accessories, Continued Description For Use With Cat. No. 140M 140M-C-CA black 140M 140M-C-KN red/yellow 140M 140M-C-KRY Anti Tamper Shield • Provides protection against inadvertent adjustment of the current setting Lockable Twist Knob • For 1 padlock 4…8 mm (5/16") dia. shackle • Can be locked in OFF position 140-KN black Padlockable Operating Knob • Accepts 8mm (5/16") padlock — up to three padlocks. • Permits padlocking in the off position. 140-CMN 140-KRY red/yellow Door Coupling Handle • For 3 padlocks 4…8 mm (5/16") in diameter • IP66 Protection/Type 1,3,3R,4,4x,13 • Interlock override capability • Can be modified for locking in ON position • Ships with coupling — order extension shaft and legend plate separately • Mounting depth (adapter-door): 140-C: 105.5 mm ± 5 mm (4.15" ± 3/16") 140-D: 114.5 mm ± 5 mm (4.5" ± 3/16") 140-F: 137.1 mm ± 5 mm (5.4" ± 3/16") 140M 140M-C-DN66 140-CMN 140-CDN66 140M 140M-C-DRY66 140-CMN 140-CDRY66 140M-C-DN66 140M-C-DRY66 140M-C-DS 140M-C-DN66 140M-C-DFCN black red/yellow Extension Shaft • Cut to required length for mounting depth (adapter-door): 140-C: 117…338 mm (4.6"…13.3") 140-D: 126…347 mm (5.0"…13.7") 140-F: 149…369 mm (5.4"…14.5") Legend Plate • Marking: "Haupschalter" and "Main Switch" • Marking: "Not-Aus" and "Emergency Off" 140M-C-DRY66 140M-C-DFCRY Locking Tag • Padlock attachment to the lockable handles • Up to three padlocks 4…8 mm (5/16") shackle black handle IP65 Non-Metallic Enclosure • Knockouts for PG16 and PG21 fittings • Suitable for flexible cable with internal ground wire or red/yellow conduit when externally grounded around the outside handle of the enclosure 140M-C-KN 140M-C-KRY 140M-F-KRY 140M-C-M3 140M-C 198E-AYTJ2 140M-C 198E-AYTG2 3-167 Bulletin 140M Motor Protectors Accessories, Continued Description Connecting Modules — 25 A • The Eco-connecting modules provide electrical and mechanical inte-connection of 140M and 100M (with AC or DC coils) or 100C (with AC coils) for use as combination starters • Suitable for reversing and star/delta kits • Eco-starters mount on single DIN Rail (140M on DIN Rail) Connecting Modules — 45 A • Electrical interconnection between 140M-F motor protector and 100-C contactors (with AC coils) • Contactor and motor protector must be mounted separately Commoning Link Feeder Terminal • For supply of commoning links — 600V, 65 A max. • Top feed — overlaps commoning link For Use With Cat. No. 140M-C to 100-M 140M-C-PEM12 140M-C to 100-C09…C23 140M-C-PEC23 140M-D to 100-C09…C23 140M-D-PEC23 140M-F to 100-C30…C37 140M-F-PNC37 140M-F to 100-C43 140M-F-PNC43 140M-C 140M-D 140M-C-WT 140M-F 140M-F-WT Three-Phase Commoning Link for 25 A Motor Protectors — 63 A Max. Continuous Current 140M-C-W452 2 x 3 connections • • • • • • 140M-D 140M-C 45 mm spacing For use with front-mounted auxiliary contact 54 mm spacing For use with side-mounted auxiliary contact 3 x 3 connections 4 x 3 connections 140M-C 140M-D 140M-C-W453 140M-C-W454 5 x 3 connections 140M-C-W455 2 x 3 connections 140M-C-W542 3 x 3 connections 4 x 3 connections 140M-C 140M-D 140M-C-W543 140M-C-W544 5 x 3 connections 140M-C-W545 2 x 3 connections 140M-C-W632 63 mm spacing 3 x 3 connections For use with side-mounted undervoltage trip and 4 x 3 connections shunt trip 5 x 3 connections Jumper for 140M-D to 140M-C • Accommodates difference in depth from 140M-D to 140M-C 2 x 3 connections • Can be used with all other commoning links • 54 mm spacing 140M-C 140M-D 140M-C-W633 140M-C-W634 140M-C-W635 140M-D to 140M-C 140M-C-WD542 Three-Phase Commoning Link for 45 A Motor Protectors • • • • 54 mm spacing For use with front-mounted auxiliary contact 63 mm spacing For use with side-mounted auxiliary contact 2 x 3 connections 3 x 3 connections 4 x 3 connections 3 x 3 connections 3-168 140M-F-W632 140M-F 10 pcs per Pkg 140M-F-W633 140M-F-W634 4 x 3 connections Screw Adapter • For screw arrangement of a motor protector 140M-F-W543 140M-F-W544 2 x 3 connections Terminal Cover • For covering of unused connection terminals • IP2X finger protection DIN (#3) Symmetrical Rail • 35 mm x 7.5 mm x 1 m long • Zinc-plated, yellow chromated • EN 50022 140M-F-W542 140M-F 140M-C 140M-D 140M-C-WS 140M-F 140M-F-WS 140M 140M-C-N45 — 199-DR1 Bulletin 140M Motor Protectors 3 Specifications UL/CSA Performance Data Manual Motor Controller (UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device) Cat. No. 140M-C2EA16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 Rated Operational Current,Ie[A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25 [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325 480V [kA] 65 65 65 65 65 65 65 65 65 65 10 10 10 600V [kA] 47 47 47 47 47 47 5 5 5 5 5 5 5 115V [HP] — — — — — — 1/10 1/8 1/4 1/2 1 1-1/2 2 230V [HP] — — — — — 1/10 1/6 2/3 3/4 1-1/2 3 3 3 230V [HP] — — — — — — 1/2 1 2 3 5 7-1/2 10 460V [HP] — — — — 1/2 3/4 1-1/2 3 3 7-1/2 10 15 20 575V [HP] — — — — 3/4 1 2 3 5 10 10 20 25 C25 Magnetic Release Current C25 Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase Maximum Rated Current of Protection Device 400 [A] Self-Protected (Type E) Manual Combination Motor Controller (UL 508) Cat. No. 140M-C2EA16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 Rated Operational Current,Ie[A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25 [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325 480Y/277V [kA] 65 65 65 65 65 65 65 65 65 65 10 10 10 600Y/347V [kA] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 115V [HP] — — — — — — 1/10 1/8 1/4 1/2 1 1-1/2 2 230V [HP] — — — — — 1/10 1/6 2/3 3/4 1-1/2 3 3 3 230V [HP] — — — — — — 1/2 1 2 3 5 7-1/2 10 460V [HP] — — — — 1/2 3/4 1-1/2 3 3 7-1/2 10 15 20 575V [HP] — — — — 3/4 1 2 3 5 10 10 20 25 Magnetic Release Current Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase ➊ Contact your local Allen-Bradley Sales Office. 3-169 Bulletin 140M Motor Protectors Specifications, Continued UL/CSA Performance Data, Continued Manual Motor Controller (UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device) Cat. No. 140M-D8E- Cat. No. 140M-F8E- B25 B40 B63 C10 C16 C20 C25 C10 C16 C20 C25 C32 Rated Operational Current,Ie[A] 2.5 4.0 6.3 10 16 20 25 10 16 20 25 32 45 [A] 33 52 82 130 208 260 325 130 208 260 325 416 585 480V [kA] 65 65 65 65 65 65 25 65 65 65 65 65 50 600V [kA] 10 10 10 10 10 5 5 10 10 10 10 10 10 115V [HP] 1/10 1/8 1/4 1/2 1 1-1/2 2 1/2 1 1-1/2 2 3 3 230V [HP] 1/6 1/3 3/4 1-1/2 3 3 3 1-1/2 3 3 3 5 7-1/2 Magnetic Release Current C45 Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase 230V [HP] 1/2 1 2 3 5 7-1/2 10 3 5 7-1/2 10 10 15 460V [HP] 1-1/2 3 3 7-1/2 10 15 20 7-1/2 10 15 20 25 30 575V [HP] 2 3 5 10 10 20 25 10 10 20 25 30 40 C45 Maximum Rated Current of Protection Device 400 [A] 500 Type E Combination Motor Controller (UL 508) Cat. No. 140M-D8E- Cat. No. 140M-F8E- B25 B40 B63 C10 C16 C20 C25 C10 C16 C20 C25 C32 Rated Operational Current,Ie[A] 2.5 4.0 6.3 10 16 20 25 10 16 20 25 32 45 [A] 33 52 82 130 208 260 325 130 208 260 325 416 585 480Y/277V [kA] 65 65 65 65 65 65 25 ➊ ➊ ➊ ➊ ➊ ➊ 500Y/347V [kA] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 115V [HP] 1/10 1/8 1/4 1/2 1 1-1/2 2 1/2 1 1-1/2 2 3 3 230V [HP] 1/6 1/3 3/4 1-1/2 3 3 3 1-1/2 3 3 3 5 7-1/2 Magnetic Release Current Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase 230V [HP] 1/2 1 2 3 5 7-1/2 10 3 5 7-1/2 10 10 15 460V [HP] 1-1/2 3 3 7-1/2 10 15 20 7-1/2 10 15 20 25 30 575V [HP] 2 3 5 10 10 20 25 10 10 20 25 30 40 ➊ Contact your local Allen-Bradley Sales Office. 3-170 Bulletin 140M Motor Protectors Specifications, Continued UL/CSA Performance Data, Continued Manual Motor Controller (UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device) Cat. No. 140M-C2NA16 A25 A40 A63 B10 B16 B25 Rated Operational Current,Ie[A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 [A] 2.1 3.3 5.2 8.2 13 20 32 Magnetic Release Current Max. Short Circuit Current 480V [kA] 65 65 65 65 65 65 65 600V [kA] 47 47 47 47 47 47 5 115V [HP] — — — — — — 1/10 230V [HP] — — — — — 1/10 1/6 230V [HP] — — — — — — 1/2 460V [HP] — — — — 1/2 3/4 1-1/2 575V [HP] — — — — 3/4 1 2 Motor Load, Single-Phase Motor Load, Three-Phase Maximum Rated Current of Protection Device 400 [A] Cat. No. 140M-D8N- Cat. No. 140M-F8N- B25 B40 B63 C10 C16 C25 C25 C32 Rated Operational Current,Ie[A] 2.5 4.0 6.3 10 16 25 25 32 45 [A] 32 52 82 130 208 325 325 416 585 480V [kA] 65 65 65 65 65 25 65 65 50 600V [kA] 10 10 10 10 10 5 10 10 10 115V [HP] 1/10 1/8 1/4 1/2 1 2 2 3 3 230V [HP] 1/6 1/3 3/4 1-1/2 3 3 3 5 7-1/2 15 Magnetic Release Current C45 Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase 230V [HP] 1/2 1 2 3 5 10 10 10 460V [HP] 1-1/2 3 3 7-1/2 10 20 20 25 30 575V [HP] 2 3 5 10 10 25 25 30 40 Maximum Rated Current of Protection Device [A] 400 500 3-171 Bulletin 140M Motor Protectors Specifications, Continued UL/CSA Performance Data, Continued Manual Motor Controller (UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device) Cat. No. 140M-C2TA16 A25 A40 A63 B10 B16 B25 B40 B63 C10 Rated Operational Current,Ie[A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16 [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260 480V [kA] 65 65 65 65 65 65 65 65 65 65 10 600V [kA] 47 47 47 47 47 47 5 5 5 5 5 115V [HP] — — — — — — 1/10 1/8 1/4 1/2 1 230V [HP] — — — — — 1/10 1/6 2/3 3/4 1-1/2 3 230V [HP] — — — — — — 1/2 1 2 3 5 460V [HP] — — — — 1/2 3/4 1-1/2 3 3 7-1/2 10 575V [HP] — — — — 3/4 1 2 3 5 10 10 Magnetic Release Current C16 Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase Maximum Rated Current of Protection Device 400 [A] Cat. No. 140M-D8T- Cat. No. 140M-F8T- C16 C20 C25 Rated Operational Current,Ie[A] 16 20 25 32 [A] 260 325 416 585 480V [kA] 65 65 65 65 600V [kA] 10 10 10 10 115V [HP] 1 1-1/2 2 3 230V [HP] 3 3 3 5 Magnetic Release Current C32 Max. Short Circuit Current Motor Load, Single-Phase Motor Load, Three-Phase 230V [HP] 5 7-1/2 10 10 460V [HP] 10 15 20 25 575V [HP] 10 20 25 30 Maximum Rated Current of Protection Device 3-172 [A] 400 500 Bulletin 140M Motor Protectors Specifications, Continued 3 3 3 IEC Performance Data Cat. No. 140M-C2EA16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 Rated Operational Current,Ie[A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25 [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325 230/240V [kW] — — — 0.06/ 0.09 0.12 0.18/ 0.25 0.37 0.55/ 0.75 1.1/ 1.5 2.2 3.0/ 4.0 4.0/ 5.5 — 400/415V [kW] 0.02 0.06 0.09 0.12/ 0.18 0.25 0.37/ 0.55 0.75 1.1/1.5 2.2 3.0/ 4.0 5.5/ 7.5 7.5/10 11 500V [kW] — — — 0.18 0.25/ 0.37 0.55/ 0.75 1.1 1.5/2.2 2.5/ 3.0 4.0/ 6.3 7.5/10 11 15 690V [kW] — — — 0.25 0.37/ 0.55 0.75/ 1.1 1.8 2.2/3.0 4.0 5.5/ 7.5 11/13 15/17 230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 100 100 400/415V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 100 100 440/460V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 63 63 80 80 500V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 80 80 80 690V [A] ➊ ➊ ➊ ➊ ➊ 16 20 35 50 50 63 63 63 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 10 10 500V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3 Magnetic Release Current C25 Switching of Standard Three-Phase Motors AC-2, AC-3 18.5/ 22 Back-Up Fuses gG, gL, only if Icc > Icu Ultimate Short Circuit Breaking Capacity Icu Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 500V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3 ➊ No back-up fuse required. 3-173 Bulletin 140M Motor Protectors Specifications, Continued IEC Performance Data, Continued Cat. No. 140M-D8E- Cat. No. 140M-F8E- B25 B40 B63 C10 C16 C20 C25 C10 C16 C20 C25 C32 Rated Operational Current,Ie[A] 2.5 4.0 6.3 10 16 20 25 10 16 20 25 32 45 [A] 33 52 82 130 208 260 325 130 208 260 325 416 585 Magnetic Release Current C45 Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V [kW] 0.37 0.55/ 0.75 1.1/ 1.5 2.2 3.0/ 4.0 4.0/ 5.5 — 2.2 3.0/ 4.0 4.0/5.5 5.5/6.3 7.5 11/13 400/415V [kW] 0.75 1.1/1.5 2.2 3.0/ 4.0 5.5/ 7.5 7.5/10 11 3.0/ 4.0 5.5/ 7.5 7.5/10 11 15 18.5/ 22 500V [kW] 1.1 1.5/2.2 2.5/ 3.0 4.0/ 6.3 7.5/10 11 15 4.0/ 6.3 7.5/10 11 15 15/20 22/30 690V [kW] 1.8 2.2/3.0 4.0 5.5/ 7.5 11/13 15/17 18.5/ 22 5.5/ 7.5 11/13 15/17 18.5/ 22 22/25 30/40 230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 400/415V [A] ➊ ➊ ➊ ➊ ➊ 100 100 80 100 100 100 125 125 440/460V [A] ➊ ➊ ➊ ➊ 80 100 100 ➋ ➋ ➋ ➋ ➋ ➋ 500V [A] ➊ ➊ ➊ ➊ 80 80 80 80 80 80 80 100 100 690V [A] 20 35 50 50 63 63 63 50 63 63 63 80 80 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 50 50 50 50 50 50 50 50 440/460V [kA] 100 100 100 100 50 50 50 ➋ ➋ ➋ ➋ ➋ ➋ 500V [kA] 100 100 100 40 25 25 25 10 10 10 10 10 10 690V [kA] 10 10 10 10 6 6 6 6 6 6 6 6 6 Back-Up Fuses gG, gL, only if Icc > Icu Ultimate Short Circuit Breaking Capacity Icu Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 50 25 25 50 50 25 25 25 25 440/460V [kA] 100 100 100 100 50 25 25 ➋ ➋ ➋ ➋ ➋ ➋ 500V [kA] 100 100 100 100 50 25 25 10 10 10 10 10 10 690V [kA] 10 10 10 6 4 4 4 6 6 6 6 6 4 ➊ No back-up fuse required. ➋ Contact your local Allen-Bradley Sales Office. 3-174 Bulletin 140M Motor Protectors Specifications, Continued 3 3 3 IEC Performance Data, Continued Cat. No. 140M-C2NRated Operational Current,Ie[A] Magnetic Release Current [A] A16 A25 A40 A63 B10 B16 B25 0.16 0.25 0.4 0.63 1 1.6 2.5 2.1 3.3 5.2 8.2 13 21 32 Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V [kW] — — — 0.06/0.09 0.12 0.18/0.25 0.37 400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 500V [kW] — — — 0.18 0.25/0.37 0.55/0.75 1.1 690V [kW] — — — 0.25 0.37/0.55 0.75/1.1 1.8 230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ 400/415V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ 440/460V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ 500V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ 690V [A] ➊ ➊ ➊ ➊ ➊ 16 20 Back-Up Fuses gG, gL, only if Icc > Icu ➊ Ultimate Short Circuit Breaking Capacity Icu 230/240V [kA] 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 100 100 500V [kA] 100 100 100 100 100 100 100 690V [kA] 100 100 100 100 100 8 8 Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 100 100 500V [kA] 100 100 100 100 100 100 100 690V [kA] 100 100 100 100 100 8 8 ➊ No back-up fuse required. 3-175 Bulletin 140M Motor Protectors Specifications, Continued IEC Performance Data, Continued Cat. No. 140M-D8N- Cat. No. 140M-F8N- B25 B40 B63 C10 C16 C25 C25 C32 Rated Operational Current,Ie[A] 2.5 4.0 6.3 10 16 25 25 32 45 [A] 32 52 82 130 208 325 325 416 585 Magnetic Release Current C45 Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V [kW] 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 — 5.5/6.3 7.5 11/13 400/415V [kW] 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 11 11 15 18.5/22 500V [kW] 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 15 15 15/20 22/30 690V [kW] 1.8 2.2/3.0 4.0 5.5/7.5 11/13 18.5/22 18.5/22 22/25 30/40 Back-Up Fuses gG, gL, only if Icc > Icu 230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 400/415V [A] ➊ ➊ ➊ ➊ ➊ 100 100 125 125 440/460V [A] ➊ ➊ ➊ ➊ 80 100 ➋ ➋ ➋ 500V [A] ➊ ➊ ➊ ➊ 80 80 80 100 100 690V [A] 20 35 50 50 63 63 63 80 80 230/240V [kA] 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 50 50 50 50 440/460V [kA] 100 100 100 100 50 50 ➋ ➋ ➋ 500V [kA] 100 100 100 10 50 25 10 10 10 690V [kA] 10 10 10 6 6 6 6 6 6 Ultimate Short Circuit Breaking Capacity Icu Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 25 25 25 25 440/460V [kA] 100 100 100 100 50 25 ➋ ➋ ➋ 500V [kA] 100 100 100 100 50 25 10 10 10 690V [kA] 10 10 10 6 4 4 6 6 4 ➊ No back-up fuse required. ➋ Contact your local Allen-Bradley Sales Office. 3-176 Bulletin 140M Motor Protectors Specifications, Continued IEC Performance Data, Continued Cat. No. 140M-C2TA16 A25 A40 A63 B10 B16 B25 B40 B63 C10 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16 [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260 230/240V [kW] — — — 0.06/ 0.09 0.12 0.18/ 0.25 0.37 0.55/ 0.75 1.1/1.5 2.2 3.0/4.0 400/415V [kW] 0.02 0.06 0.09 0.12/ 0.18 0.25 0.37/ 0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 500V [kW] — — — 0.18 0.25/ 0.37 0.55/ 0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 690V [kW] — — — 0.25 0.37/ 0.55 0.75/1.1 1.8 2.2/3.0 4.0 5.5/7.5 11/13 230/240V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 400/415V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 440/460V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 63 63 500V [A] ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ ➊ 80 80 690V [A] ➊ ➊ ➊ ➊ ➊ 16 20 35 50 50 63 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 500V [kA] 100 100 100 100 100 100 100 100 100 50 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 Rated Operational Current,Ie[A] Magnetic Release Current C16 Switching of Standard Three-Phase Motors AC-2, AC-3 Back-Up Fuses gG, gL, only if Icc > Icu Ultimate Short Circuit Breaking Capacity Icu Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 500V [kA] 100 100 100 100 100 100 100 100 100 50 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 ➊ No back-up fuse required. 3-177 Bulletin 140M Motor Protectors Specifications, Continued IEC Performance Data, Continued Cat. No. 140M-D8T- Cat. No. 140M-F8T- C16 C20 C25 Rated Operational Current,Ie[A] 16 20 25 32 [A] 260 325 416 585 7.5 Magnetic Release Current C32 Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V [kW] 3.0/4.0 4.0/5.5 5.5/6.3 400/415V [kW] 5.5/7.5 7.5/10 11 15 500V [kW] 7.5/10 11 15 15/20 690V [kW] 11/13 15/17 18.5/22 22/25 Back-Up Fuses gG, gL, only if Icc > Icu 230/240V [A] ➊ ➊ ➊ ➊ 400/415V [A] 80 100 100 125 440/460V [A] 80 100 ➋ ➋ 500V [A] 80 80 80 100 690V [A] 63 63 63 80 230/240V [kA] 100 100 100 100 400/415V [kA] 50 50 50 50 440/460V [kA] 50 50 ➋ ➋ 500V [kA] 25 25 10 10 690V [kA] 6 6 6 6 Ultimate Short Circuit Breaking Capacity Icu Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 400/415V [kA] 25 25 25 25 440/460V [kA] 25 25 ➋ ➋ 500V [kA] 25 25 10 10 690V [kA] 4 4 6 6 ➊ No back-up fuse required. ➋ Contact your local Allen-Bradley Sales Office. 3-178 Bulletin 140M Motor Protectors Specifications, Continued General Data Cat. No. 140M-C… 140M-D… Rated Insulation Voltage IEC, SEV, VDE 0660 690 V UL, CSA 600 V Rated Impulse Withstand Voltage Uimp/pollution degree 6 kV/3 50/60 Hz Rated Frequency Utilization Category: • IEC 947-2 (Motor Protector) • IEC 947-4-1 (Motor Starter) Life Span Mechanical 140M-F… A AC-3 [operations] Electrical (Ie max.) [operations] Switching Frequency [operations] 100,000 30,000 100,000 30,000 max. 25/h. (motor starts) Ambient Temperature Storage –40…+80°C Operation –25…+60°C IEC 68-2 Resistance to Climatic Change to 2,000 m N.N. Site Altitude IP20 all round, when wired Protection Class 30 G, 11 ms Resistance to Shock Rated Thermal Current Ith IEC, SEV, VDE 0660 Up to 60 °C ambient temperature — IEC 68-2 Resistance to Vibration 0.1…25 1.6…25 6.3…45 [A] Overload Protection Characteristics IEC 947-4-1 Motor protection (except 140M-C2N, 140M-D8N, 140M-F8N) Ambient temperature compensation –20…+60°C Phase-failure protection yes differential release fixed setting 13 x Iemax. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N) 16…20 x Iemax. (for 140M-C2T, 140M-D8T, 140M-F8T) Magnetic Release Response current Iemax. = maximum values of setting ranges Total Power Loss Pv Motor protector at rated load operating temperature 6…8 6…8 9…16 [W] 3-179 Bulletin 140M Motor Protectors Specifications, Continued General Data Cat. No. 140M-C… 140M-D… 140M-F… Conformity to Standards IEC 947; EN 60947; UL 508; CSA 22.2 Approvals CE, UL, CSA Terminal Parts Type of terminals Screwdriver Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 1…4/No. 16…12 1…4/No. 16…12 2.5…16/No.14…6 2.5…10/No. 14…8 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 1…6/No. 16…8 1…6/No. 16…8 2.5…25/No. 14…4 2.5…16/No. 14…6 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 1.5…6/No. 16…8 1.5…6/No. 16…8 2.5…25/No. 14…4 2.5…16/No. 14…6 1…2.5/8.9…22 1.5…3.5/13…31 Tightening torque [Nm]/[lb-in] Accessories for Bulletin 140M Motor Protectors Rated Thermal Current Ith at 40°C ambient temperature at 60°C ambient temperature Contact Class Coordination According to NEMA (UL/CSA-Standards) Auxiliary Contact Blocks for Right-Side Mounting Cat. No. 140M-C-ASA…, 140M-C-ASAR… 5 4 10 6 B 300 Q 300 B 600 Q 600 [A] [A] AC DC Back-Up Fuses gG, gL [A] Rated Supply Current AC-15: [V] DC-13: Auxiliary Contact Blocks for Front Mounting Cat. No. 140M-C-AFA…, 140M-C-AFAR… 10 10 [A] 24 4 120 3 240 1.5 24 6 120 5 240 3 415 2 [V] [A] 24 2 120 0.5 240 0.25 24 2 120 0.5 240 0.25 415 0.15 Terminal Parts Type of terminals Pozidriv No. 2/Blade No. 3 Screwdriver 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.5…2.5/No. 18…14 0.5…2.5/No. 18…14 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 Tightening torque 3-180 [Nm]/[lb-in] 1.5/13.3 690 0.7 Bulletin 140M Motor Protectors Specifications, Continued Accessories for Bulletin 140M Motor Protectors Actuating Voltage Pull-in Drop-out Rated Control Voltage On-Time Coil Rating min. max. Pull-in Hold Undervoltage Trip for Left-Side Mounting Cat. No. 140M-C-UX… Undervoltage Trip with 2 Auxiliary Contacts for Left-Side Mounting Cat. No. 140M-C-UC… Shunt Trip for Left-Side Mounting Cat. No. 140M-C-SN… 0.85…1.1 x Us 0.7…0.35 x Us 0.85…1.1 x Us 0.7…0.35 x Us 0.7…1.1 x Us 21V 50 Hz, 24V 60 Hz 600V 50 Hz 100% 8.5 VA, 6 W 3 VA, 1.2 W 21V 50 Hz, 24V 60 Hz 600V 50 Hz 100% 8.5 VA, 6 W 3 VA, 1.2 W 21V 50 Hz, 24V 60 Hz 600V 50 Hz 100% 8.5 VA, 6 W 3 VA, 1.2 W Terminal Parts Type of terminals Pozidriv No. 2/Blade No. 3 0.5…2.5/No. 18…14 0.5…2.5/No. 18…14 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 1.5/13.3 Screwdriver 1. conductor 2. conductor 1. conductor 2. conductor 1. conductor 2. conductor Tightening torque [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [Nm]/[lb-in] Commoning Link Feeder Terminal 140M-C-WT Commoning Link 140M-C-W 63 63 Rated Thermal Current Ith at 60°C ambient temperature [A] 1. conductor [mm2]/[AWG] 2. conductor [mm2]/[AWG] 1. conductor [mm2]/[AWG] 2. conductor [mm2]/[AWG] 1. conductor [mm2]/[AWG] 2. conductor [mm2]/[AWG] Tightening torque [Nm]/[lb-in] 4…16 4…10 6…25/No. 14…4 6…16/No. 14…6 6…25/No. 14…4 6…16/No. 14…6 3/27 — — — — Weights Description Motor Protectors Auxiliary Contacts Undervoltage Trip Anti-tamper Cover Cat. No. 140M-C2E-… 140M-D8E-… 140M-F8E-… 140M-C2N-… 140M-D8N-… 140M-F8N-… 140M-C2T-… 140M-D8T-… 140M-F8T-… 140M-C-AFA10 140M-C-AFA01 140M-C-AFA11 140M-C-AFA20 140M-C-ASA… 140M-C-AFAR10A… 140M-C-ASAR…M… 140M-C-ASAM11 140M-C-UX… 140M-C-SN… 140M-C-UC… 140M-C-CA Weight 317 g 373 g 782 g 315 g 365 g 782 g 315 g 365 g 782 g Description Lockable Twist Knob Locking Tag Door Coupling Handle Extension Shaft Legend Plate Feeder Terminal 10 g 15 g 108 g 110 g 116 g 2g Commoning Links Cat. No. 140M-C-KN 140M-C-KRY 140M-C-M3 140M-C-DN66 140M-C-NRY66 140M-C-DS 140M-C-DFC… 140M-C-WT 140M-F-WT 140M-C-W452 140M-C-W453 140M-C-W454 140M-C-W455 140M-C-W542 140M-C-W543 140M-C-W544 140M-C-W545 140M-C-W632 140M-C-W633 140M-C-W634 140M-C-W635 Weight 5g 30 g 123 g 46 g 4g 172 g 47 g 80 g 104 g 132 g 52 g 86 g 118 g 154 g 56 g 92 g 134 g 170 g 3-181 Bulletin 140M Motor Protectors 3 Specifications, Continued Time-Current Characteristic 140M Motor Protector 1) Thermal Release Trip Current: The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20°C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single-phasing. The overload characteristic is also valid for transformer protection. 10 000 1h 1 000 100 1 2) Magnetic Release Trip Current: The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher. 10 1 2 Tripping time [s] 0.1 0.01 0.001 0.8 1 2 4 6 10 Multiple of set current IeF 3-182 20 40 60 100 Current Setting IeF: The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC 947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40°C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor. Bulletin 140M Motor Protectors 3 Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. ➋ 24.8 (31/32) 18 (23/32) 9 (23/64) 45 (1-25/32) 4.5 (3/16) 62 (2-7/16) 4.5 (3/16) 29.4 (1-5/32) ➋ 9 (23/64) ➍ 54 (2-1/8) 72 (2-53/64) 7.5 (19/64) 140M-D… 45 (1-25/32) ➊ 55 (2-11/64) 110 (4-21/64) 55 (2-11/64) 4.5 (3/16) ➌ 54 (2-1/8) 7.5 (19/64) ➊ 140M-C…. 140M-C…, 140M-D… 18 (23/32) ➍ 44 (1-47/64) 45 (1-25/32) 45 (1-25/32) ➊ 45 (1-25/32) ➌ . 45 (1-25/32) 4.5 (3/16) 90 (3-35/64) 45 (1-25/32) . ➊ ➋ ➌ ➍ Mounting on 35 mm DIN Rail EN 50 022-35 Auxiliary contact (side-mounted) Undervoltage trip or Shunt trip Auxiliary contact (front-mounted) ➍ 91 (3-37/64) 4.5 (3/16) 102 (4-1/64) 7.5 (19/64) 140M-F…. 90 90 ˚ 90 ˚ 90 ˚ ˚ 4.5 min. 100 3.5 1.5...5 35...45 Mounting position 140M-C…, 140M-D…, 140M-F… b 53.5 a 53.5 a 4...8 b ±5 c1 c2 49.5 40.5 140M-C… 117…338 105.5 140M-D… 126…347 114.5 ±5 49.5 40.5 140M-F… 148.6…369.6 137.1 ±5 59.35 50.35 c2 4.5 c1 + 5 mm 2.4 140M-C-D…66 3-183 Bulletin 140M Motor Protectors 3 Approximate Dimensions, Continued Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Cat. No. 140-CMN Mounting position of Cat. No. 140-CMN 3-184 Bulletin 140M Motor Protectors Type 2 Coordination Type 2 Coordination per UL508E Voltage: 480V, 60 HZ Motor Protector Cat. No. Thermal Overload Release Setting Range [A] Magnetic Release Response Current [A] Contactor Cat. No. ➊ Short Circuit Current, Iq [kA] 140M-C2E-A16 0.10…0.16 2.1 100-C09, 100-M05 65 140M-C2E-A25 0.16…0.25 3.3 100-C09, 100-M05 65 140M-C2E-A40 0.25…0.40 5.2 100-C09, 100-M05 65 140M-C2E-A63 0.40…0.63 8.2 100-C09, 100-M05 65 140M-C2E-B10 0.63…1.0 13 100-C09, 100-M05 65 140M-C2E-B16 1.0…1.6 21 100-C09, 100-M05 65 140M-C2E-B25 1.6…2.5 33 100-C09 50 140M-C2E-B40 2.5…4.0 52 100-C30 50 140M-C2E-B63 4.0…6.3 82 100-C30 50 140M-C2E-C10 6.3…10.0 130 100-C30 50 140M-C2E-C16 10.0…16.0 208 100-C30 10 140M-C2E-C20 14.5…20.0 260 100-C30 10 140M-C2E-C25 18.0…25.0 325 100-C30 10 140M-D8E-B25 1.6…2.5 33 100-C09 65 140M-D8E-B40 2.5…4.0 52 100-C09 65 140M-D8E-B63 4.0…6.3 82 100-C09 65 140M-D8E-C10 6.3…10.0 130 100-C09 65 140M-D8E-C16 10.0…16.0 208 100-C12 65 140M-D8E-C20 14.5…20.0 260 100-C23 65 140M-D8E-C25 18.0…25.0 325 100-C23 50 140M-F8E-C10 6.3…10.0 130 100-C16 65 140M-F8E-C16 10.0…16.0 208 100-C16 65 140M-F8E-C20 14.5…20.0 260 100-C23 65 140M-F8E-C25 18.0…25.0 325 100-C23 65 140M-F8E-C32 23.0…32.0 416 100-C30 65 140M-F8E-C45 32.0…45.0 585 100-C37 50 140-CMN-2500 16.0…25.0 350 100-C30 65 140-CMN-4000 25.0…40.0 560 100-C30 65 140-CMN-6300 40.0…63.0 882 100-C43 65 140-CMN-9000 63.0…90.0 1260 100-C72 65 Definition of Type 2 Short Circuit Coordination per UL 508E: • • The contactor or starter must not endanger persons or plant in the event of a short circuit. No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver). In the event of short circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully short circuit coordinated starter combinations in accordance with UL508E, Type 2 coordination. ➊ Ratings apply to specified or larger contactor. 3-185 Bulletin 140M Motor Protectors Type 2 Coordination, Continued Type 2 Coordination per UL 508E, Continued Voltage: 600V, 60 HZ Motor Protector Cat. No. Thermal Overload Release Setting Range [A] Magnetic Release Response Current [A] Contactor Cat. No. ➊ Short Circuit Current, Iq [kA] 140M-C2E-A16 0.10…0.16 2.1 100-C09, 100-M05 47 140M-C2E-A25 0.16…0.25 3.3 100-C09, 100-M05 47 140M-C2E-A40 0.25…0.40 5.2 100-C09, 100-M05 47 140M-C2E-A63 0.40…0.63 8.2 100-C09, 100-M05 47 140M-C2E-B10 0.63…1.0 13 100-C09, 100-M05 47 140M-C2E-B16 1.0…1.6 21 100-C09, 100-M05 47 140M-C2E-B25 1.6…2.5 33 100-C09 10 140M-C2E-B40 2.5…4.0 52 100-C16 5 140M-C2E-B63 4.0…6.3 82 100-C23 5 140M-C2E-C10 6.3…10.0 130 100-C30 5 140M-C2E-C16 10.0…16.0 208 100-C30 5 140M-C2E-C20 14.5…20.0 260 100-C30 5 140M-C2E-C25 18.0…25.0 325 100-C30 5 140M-D8E-B25 1.6…2.5 33 100-C09 10 140M-D8E-B40 2.5…4.0 52 100-C16 10 140M-D8E-B63 4.0…6.3 82 100-C23 10 140M-D8E-C10 6.3…10.0 130 100-C30 10 140M-D8E-C16 10.0…16.0 208 100-C30 10 140M-D8E-C20 14.5…20.0 260 100-C30 5 140M-D8E-C25 18.0…25.0 325 100-C30 5 140M-F8E-C10 6.3…10.0 130 100-C30 10 140M-F8E-C16 10.0…16.0 208 100-C30 10 140M-F8E-C20 14.5…20.0 260 100-C30 10 140M-F8E-C25 18.0…25.0 325 100-C30 10 140M-F8E-C32 23.0…32.0 416 100-C30 10 140M-F8E-C45 32.0…45.0 585 100-C37 10 140-CMN-2500 16.0…25.0 350 100-C30 42 140-CMN-4000 25.0…40.0 560 100-C30 42 140-CMN-6300 40.0…63.0 882 100-C43 30 140-CMN-9000 63.0…90.0 1260 100-C72 15 Definition of Type 2 Short Circuit coordination per UL 508E: • • The contactor or starter must not endanger persons or plant in the event of a short circuit. No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver). In the event of short circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully short circuit coordinated starter combinations in accordance with UL508, Type 2 coordination. ➊ Ratings apply to specified or larger contactor. 3-186