Brochure

Bulletin 140M
Motor Protectors
3Circuit Breaker
3
3
Bulletin 140M
Cat. No. 140M-C2E
Cat. No. 140M-F8E
• Current Range 0.1…45 A
• With 140-CMN up to
90 A
• Type 2 Coordination with
Bulletin 100-C
Contactors
• UL Listed
• “Self-protected”
Type E Manual
Combination Starters
• Manual Starter
• Motor Disconnect
• Group Motor
Installation
• Visible Trip Indication
• Rotary Actuator
• High Current Limiting
• High Switching Capacity
TABLE OF CONTENTS
Description
Page
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-156
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-160
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-163
Description
Page
Specifications
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-169
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-179
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-183
Type 2 Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-185
Description
The Bulletin 140M Motor Protector provides short circuit and overload protection for
individual motor loads. A wide range of accessories makes installation and wiring
easy. Motor protectors may be applied as Manual Starters, Group Motor Starters,
Motor Disconnects, and Manual Combination Starters.
Conformity to Standards:
Approvals:
IEC 947-1/2/4
CE
IEC 204-1
CSA Certified
CSA, C22.2 No.14
UL Listed
UL 508
Construction Type E Self-Protected Manual Combination Starter.
Manual Motor Controller suitable for Group Installation.
Meets IEC Circuit Breaker requirements per IEC 947-2.
Does not meet UL489 requirements for molded case circuit breakers in North America.
Your order must include:
• Cat. No. of the motor protector selected.
• If required, Cat. No. of any accessories.
3-155
Bulletin 140M and 190S/190E
Motor Protectors/Compact Starters/Eco Starters
3
Product Overview
General Information
The new Bulletin 140M Motor Protectors provide Class 10
overload protection as well as current limiting short-circuit
protection for individual motor loads. They are approved for use
as circuit breakers per IEC 947-2 for applications outside of
North America, but in the United States and Canada, they are
UL/CSA listed as Manual Starters with the optional approvals
for Motor Disconnecting and Group Motor applications.
400V, 50 Hz, 3-Phase Power Supply
140M-C2E
-C10
Circuit Breaker Applications – IEC
Additionally, these new devices are UL/CSA listed as
Self-Protected (Type E) Manual Combination Starters —
eliminating the requirement for additional short-circuit protection
in many applications. This reduces both panel space and cost
in multi-motor installations and eliminates the restrictive
NEC/CEC rules that pertained to Manual Starters used in Group
Motor applications.
Motor Protector
as
IEC Circuit Breaker
Contactor
100-C09
14 AWG
7.6A
Fan #2
5 HP
Motor
480V, 60 Hz, 3-Phase Power Supply
The following information is provided to aid in proper system
design utilizing the capabilities of the new Bulletin 140M Motor
Protectors in North American applications. Please be sure to
follow all local and national codes for your particular installation.
Circuit Breaker Applications – IEC
The new Bulletin 140M Motor Protectors are current limiting IEC
circuit breakers (IEC 947-2) that also provide Class 10 motor
overload protection. Additionally, they meet the IEC
requirements for applications such as:
• Disconnector (IEC 947-2)
• Main Switch (IEC 204-1)
194R-NN030P3
30A
FUSE
Fusible
Disconnect
3 Fuses
Manual Starter Applications – UL/CSA
140M-C2E
-C10
Motor
Protector
as
Manual Starter
14 AWG
• Emergency Off (IEC 204-1)
The Bulletin 140M Motor Protectors cannot be applied in North
America as circuit breakers, however, since they do not meet
the UL specification for circuit breakers (UL 489).
7.6A
Fan #1
5 HP
Motor
480V, 60 Hz, 3-Phase Power Supply
Manual Starter Applications – UL/CSA
The new Bulletin 140M Motor Protectors are an excellent choice
for manual starting applications. As UL/CSA listed manual motor
controllers they provide motor overload protection, but a
separate short-circuit protective device must still be used. The
fuse or circuit breaker used for the short-circuit protection may
be sized to the maximum allowable per NEC Article 430 in the
U.S. and CEC Rule 28-200 in Canada.
194R-NJ030P3
30A
Fusible
Disconnect
FUSE
3 Fuses
Contactor
100-C09
Motor Disconnecting Applications – UL/CSA
The new Bulletin 140M Motor Protectors are also UL/CSA listed
as manual motor controllers with the optional approval “Suitable
for use as a motor disconnect” when a lockable twist knob is
used. This UL listing is new in 1999 and allows the 140M’s to
be applied as “at-motor” disconnects. All manual starters used
in such applications must be marked as “suitable for use as a
motor disconnect” per UL 508. At motor disconnects are
required by the NEC if the motor cannot be seen from the main
panel disconnect.
193-E
Overload
140M-C2E
-C10
Motor Disconnecting Applications – UL/CSA
14 AWG
7.6A
Fan #1
5 HP
3-156
Motor Protector
as
At-Motor
Disconnect
Motor
Bulletin 140M and 190S/190E
Motor Protectors/Compact Starters/Eco Starters
Product Overview, Continued
Group Motor Applications — UL/CSA
The new 140M Motor Protectors are also UL/CSA listed as manual starters for use in Group Motor installations. This listing allows
the 140M Motor Protectors to be used as manual starters providing individual overload protection with a single set of fuses or a
circuit breaker providing the short circuit protection for the “Group” of motors.
This is the most popular application for these products in North America and greatly reduces both panel space and cost versus the
traditional use of fuses or circuit breakers in each motor branch circuit. However, there are several NEC rules to follow for Group
Motor installations and one of these rules can dramatically affect panel size and layout. Per NEC Article 430-53(d), the conductors
of any tap supplying a single motor must have an ampacity less than one-third that of the branch-circuit conductors. This limits the
number of motors that can be “grouped” under one set of fuses or circuit breakers. See the following examples of two typical group
motor applications. For further assistance on how to properly apply Bulletin 140M Motor Protectors in Group Motor applications,
please see Publications 0140-2.3 and 6219-NP.
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100A
80HP
Fuse
45 A
Fusible
Disconnect
3 Fuses
8 AWG
Commoning Links
140M-C2E
140M-C2E
-C10
-C10
-C10
100-C09
100-C09
100-C16
14 AWG
7.6A
Fan #1
5 HP
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
14 AWG
7.5A
Heater #1
140M-C2E
140M-C2E
-C10
-C16
100-C16
14 AWG
100-C16
Motor Protectors
In this example, a single panel controls 5
motors. This Group Installation meets all of
the required NEC rules resulting in a very
compact, cost effective, and attractive panel
design.
Contactors
14 AWG
7.5A
Heater #2
14.0A
Pump #1
5 HP
Motors
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100A
80HP
FUSE
50A
Fusible
Disconnect
3 Fuses
6 AWG
8 AWG
FUSE
35A
14 AWG
3 Fuses
3 Fuses
8 AWG
FUSE
25A
14 AWG
Commoning Links
140M-C2E
140M-C2E
-C10
-C10
100-C09
100-C09
14 AWG
7.6A
Fan #1
5 HP
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #1
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #2
140M-C2E
-C16
100-C16
Motor Protectors
Contactors
14 AWG
14.0A
Pump #1
10 HP
In this example, we have the same group
of 5 motors, only now the pump motor is 10
HP rather than 5 HP. This Group Installation
no longer meets the NEC rules since the
wire feeding the group has increased from
#8 AWG to #6 AWG, and the ampacity of
the #14 AWG motor circuit conductors is
less than one third that of the #6 AWG
branch circuit conductors. This forces the
Group to be split, with 1 set of fuses
protecting the 4 small motors, and 1 set of
fuses protecting the 10 HP pump motor.
The third set of fuses just below the
disconnect is for protection of the #6 AWG
branch circuit conductors.
Motors
3-157
Bulletin 140M and 190S/190E
Motor Protectors/Compact Starters/Eco Starters
Product Overview, Continued
Self-Protected (Type E) Manual Combination Starter Applications — UL/CSA
The new 140M Motor Protectors, with improved current limiting and breaking capacity, are now UL/CSA listed as self-protected
(Type E) Manual Combination Starters. This new listing allows the 140M Motor Protectors to be used as short circuit protection for
individual motors, in addition to overload protection. This eliminates the need for fuses or a circuit breaker to provide short circuit
protection and also eliminates all of the NEC/CEC Group Motor rules for installations involving multi-motor panels.
The new Bulletin 140M Motor Protectors are standard components of the MCS Modular Control System. This provides for maximum
flexibility and minimum panel size without the restrictive and cumbersome rules involved with typical multi-motor (group) applications.
The 140M Motor Protectors, when used as self-protected (Type E) Manual Combination Starters, are only suitable for use on
Wye power systems if the system voltage exceeds 240V (i.e., 480Y/277V and 600Y/347V).
Self-Protected (Type E) Installations for Multi-Motor Panels
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100A
80HP
FUSE
50A
Fusible
Disconnect
3 Fuses
6 AWG
480Y/277V, 60 Hz, 3-Phase Power Supply
8 AWG
194R-NN100P3
100A
80HP
FUSE
35A
Non-Fusible
Disconnect
Commoning Links
140M-C2E
140M-C2E
-C10
-C10
-C10
100-C09
100-C09
100-C16
7.6A
Fan #1
5 HP
3 Fuses
8 AWG
6 AWG
14 AWG
14 AWG
3 Fuses
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
14 AWG
7.5A
Heater #1
140M-C2E
140M-C2E
-C10
-C16
100-C16
14 AWG
7.5A
Heater #2
Self-Protected (Type E) Installation
100-C16
Contactors
14.0A
Pump #1
10 HP
Motors
140M-C2E
-C10
-C10
100-C09
100-C09
14 AWG
14 AWG
14 AWG
Commoning Links
140M-C2E
Motor Protectors
FUSE
25A
7.6A
Fan #1
5 HP
14 AWG
140M-C2E
-C10
100-C16
14 AWG
7.6A
Fan #2
5 HP
7.5A
Heater #1
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #2
140M-C2E
-C16
100-C16
Motor Protectors
Contactors
14 AWG
14.0A
Pump #1
10 HP
Motors
Group Motor Installation
The new listing of the 140M as a self-protected (Type E) combination starter greatly simplifies multi-motor panel design. As a
self-protected combination starter the 140M provides both overload and short circuit protection for the motors and the NEC/CEC
group motor rules no longer apply.
In the diagrams above, the same 5 motors are shown in both a self-protected (Type E) installation as well as the previous example
of a Group Motor Installation. The rules in the NEC/CEC codes for the Group Motor Installation do not apply since each motor
already has short circuit protection provided by the 140M’s— i.e., the five motors are no longer “grouped” under a single short circuit
protective device (fuses or circuit-breaker). The three sets of fuses are no longer required and the 140M’s may simply be selected
for each individual motor load according to the motor full load current. A non-fusible disconnect switch for the main panel
disconnecting function completes the self-protected (Type E) Manual Combination Starter installation. Also, for remote operation a
contactor may be added to the installation Type 2 coordination may be achieved with the 100C in this case (see page 3-185).
3-158
Bulletin 140M and 190S/190E
Motor Protectors/Compact Starters/Eco Starters
Product Overview, Continued
Self-Protected (Type E) Installations for Single Motor Panels
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100 A
80 HP
Fusible
Disconnect
FUSE
25 A
3 Fuses
480Y/277V, 60 Hz, 3-Phase Power Supply
140M-C2E
-C16
Motor Protector
100-C16
Contactor
Contactor
100-C16
193-E
14 AWG
14 AWG
14.0A
Pump #1
10 HP
Overload
Relay
Motor
14.0 A
Pump #1
10 HP
Motor
The new listing of the 140M as a self-protected combination starter provides for extremely cost-effective and compact single motor
installations as well.
In the diagrams above, a panel consisting of a self-protected (Type E) Manual Combination Starter and a contactor is compared
with a traditional fusible combination starter panel. The Type E combination starter consists of a Bulletin 140M and a 100-C contactor.
The Bulletin 140M provides both the overload and short circuit protection as well as the disconnecting function for the motor while
the 100-C contactor allows for remote operation via push buttons. By contrast, the traditional fusible combination starter consists
of a 194R fusible disconnect switch for disconnecting function fuses for short circuit protection, a 100-C contactor for remote operation
and a 193-E overload relay for overload protection.
3-159
Bulletin 140M
Motor Protectors
33-160
Product Selection
Motor Protectors For Use as Manual Starters and Motor Disconnects
Cat. No. 140M-C
Cat. No. 140M-D
Cat. No. 140M-F
Motor Protectors — For Use as Manual Starters
Typical 1-phase [HP] ➊
Current Adjustment
Range [A]
115V
230V
0.10…0.16
—
—
0.16…0.25
—
—
0.25…0.40
—
0.40…0.63
Typical 3-phase [HP] ➊
200V
Cat. No. ➋
230V
460V
575V
—
—
—
—
140M-C2E-A16 ➌➍
—
—
—
—
140M-C2E-A25 ➌➍
—
—
—
—
—
—
—
—
—
0.63…1.0
—
—
—
—
1/2
3/4
140M-C2E-B10 ➌➍
1.0…1.6
—
1/10
—
—
3/4
1
140M-C2E-B16 ➌➍
1.6…2.5
1/10
1/6
1/2
1/2
1-1/2
2
140M-C2E-B25 ➌➍
2.5…4
1/8
1/3
1
1
3
3
140M-C2E-B40 ➌
4…6.3
1/4
3/4
1-1/2
2
3
5
140M-C2E-B63 ➌
6.3…10
1/2
1-1/2
3
3
7-1/2
10
140M-C2E-C10 ➌
140M-C, High Break
140M-C2E-A40 ➌➍
140M-C2E-A63 ➌➍
10…16
1
3
3
5
10
10
140M-C2E-C16 ➌
14.5…20
1-1/2
3
5
7-1/2
15
20
140M-C2E-C20
18…25
2
3
7-1/2
10
20
25
140M-C2E-C25
140M-D, High Break PLUS
1.6…2.5
1/10
1/6
1/2
1/2
1-1/2
2
140M-D8E-B25 ➍
2.5…4
1/8
1/3
1
1
3
3
140M-D8E-B40 ➍
4…6.3
1/4
3/4
1-1/2
2
3
5
140M-D8E-B63 ➍
6.3…10
1/2
1-1/2
3
3
7-1/2
10
140M-D8E-C10 ➍
10…16
1
3
3
5
10
10
140M-D8E-C16 ➌➍
14.5…20
1-1/2
3
5
7-1/2
15
20
140M-D8E-C20 ➌➍
18…25
2
3
7-1/2
10
20
25
140M-D8E-C25 ➍
140M-F, High Break PLUS
6.3…10
1/2
1-1/2
3
3
7-1/2
10
140M-F8E-C10
10…16
1
3
3
5
10
10
140M-F8E-C16
14.5…20
1-1/2
3
5
7-1/2
15
20
140M-F8E-C20
18…25
2
3
5
10
20
25
140M-F8E-C25 ➌➍
23…32
3
5
10
10
25
30
140M-F8E-C32 ➌➍
32…45
3
7-1/2
15
15
30
40
140M-F8E-C45 ➍
140-CMN
16…25
2
5
7-1/2
10
20
25
140-CMN-2500
25…40
3
7-1/2
10
15
30
40
140-CMN-4000
40…63
5
10
20
20
50
60
140-CMN-6300
63…90
7-1/2
20
30
30
60
75
140-CMN-9000
➊ Horsepower ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load
current and service factor.
• For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range.
Example: Motor F.L.C. = 4.2 A; S.F. = 1.0. (4.2 A x 0.9 = 3.78 A.) Select Cat. No. 140M-C2E-B40.
➋ Magnetic trip is fixed at 13x the maximum value of the current adjustment range.
➌ Devices with a fixed magnetic trip set at 16-20x the maximum value of the current adjustment range are available if nuisance tripping occurs (as
with some high-efficiency motors). To order these products, change the “E” in the cat. no. to a “T” (e.g., Cat. No. 140M-C2E-A16 changes to
140M-C2T-A16).
➍ Devices without a thermal trip (i.e., current adjustment range) are also available if separate motor overload protection is required. To order these
products, change the “E” in the cat. no. to an “N” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2N-A16).
3-160
Bulletin 140M
Motor Protectors
Product Selection, Continued
Motor Protectors For Use as Manual Starters in Group Installations
Cat. No. 140M-C
Cat. No. 140M-D
Cat. No. 140M-F
Motor Protectors for Group Installation
Current Adjustment
Range [A]
Max. Short-Circuit Current [kA]
For Use With
Cat. No. ➋
Max Fuse or
Circuit Breaker
[A]
Cat. No. ➊
480V
600V
0.10…0.16
65
47
100-C09, 100-M05
400
140M-C2E-A16 ➌➍
0.16…0.25
65
47
100-C09, 100-M05
400
140M-C2E-A25 ➌➍
0.25…0.40
65
47
100-C09, 100-M05
400
140M-C2E-A40 ➌➍
0.40…0.63
65
47
100-C09, 100-M05
400
140M-C2E-A63 ➌➍
0.63…1.0
65
47
100-C09, 100-M05
400
140M-C2E-B10 ➌➍
1.0…1.6
65
47
100-C09, 100-M05
400
140M-C2E-B16 ➌➍
1.6…2.5
65
5
100-C09, 100-M05
400
140M-C2E-B25 ➌➍
2.5…4
65
5
100-C09, 100-M05
400
140M-C2E-B40 ➌
4…6.3
65
5
100-C09, 100-M05
400
140M-C2E-B63 ➌
6.3…10
65
5
100-C09, 100-M05
400
140M-C2E-C10 ➌
140M-C, High Break
10…16
10
5
100-C12
400
140M-C2E-C16 ➌
14.5…20
10
5
100-C16
400
140M-C2E-C20
18…25
10
5
100-C23
400
140M-C2E-C25
140M-D, High Break PLUS
1.6…2.5
65
10
100-C09, 100-M05
400
140M-D8E-B25 ➍
2.5…4
65
10
100-C09, 100-M05
400
140M-D8E-B40 ➍
4…6.3
65
10
100-C09, 100-M05
400
140M-D8E-B63 ➍
6.3…10
65
10
100-C09, 100-M05
400
140M-D8E-C10 ➍
10…16
65
10
100-C12
400
140M-D8E-C16 ➌➍
14.5…20
65
5
100-C16
400
140M-D8E-C20 ➌➍
18…25
25
5
100-C23
400
140M-D8E-C25 ➍
140M-F, High Break PLUS
6.3…10
65
10
100-C09
500
140M-F8E-C10
10…16
65
10
100-C12
500
140M-F8E-C16
14.5…20
65
10
100-C16
500
140M-F8E-C20
18…25
65
10
100-C23
500
140M-F8E-C25 ➌➍
23…32
65
10
100-C30
500
140M-F8E-C32 ➌➍
32…45
50
10
100-C37
500
140M-F8E-C45 ➍
140-CMN
16…25
65
42
100-C16
1000
140-CMN-2500
25…40
65
42
100-C30
1000
140-CMN-4000
40…63
65
42
100-C43
1000
140-CMN-6300
63…90
65
30
100-C72
1000
140-CMN-9000
➊ Magnetic trip is fixed at 13x the maximum value of the current adjustment range.
➋ Ratings apply to specified or larger contactor.
➌ Devices with a fixed magnetic trip set at 16-20x the maximum value of the current adjustment range are available if nuisance tripping occurs (as
with some high-efficiency motors). To order these products, change the “E” in the cat. no. to a “T” (e.g., Cat. No. 140M-C2E-A16 changes to
140M-C2T-A16).
➍ Devices without a thermal trip (i.e., current adjustment range) are also available if separate motor overload protection is required. To order these
products, change the “E” in the cat. no. to an “N” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2N-A16).
➎ For Type 2 coordination see pages 3-185 and 3-186.
3-161
Bulletin 140M
Motor Protectors
3
Product Selection, Continued
Motor Protectors For Use as Self-Protected (Type E) Manual Combination Motor Controllers
Cat. No. 140M-C
Cat. No. 140M-F
Motor Protectors For Use As Self-Protected (Type E) Manual Combination Motor Controller
Typical
1-phase [HP] ➊
Current Adjustment
Range [A]
115V
230V
Max.
Short-Circuit
Current
[kA]
Typical
3-phase [HP] ➊
200V
230V
460V
575V
480Y/277V
Cat. No. ➋
140M-C, High Break
0.10...0.16
—
—
—
—
—
—
65
140M-C2E-A16
0.16...0.25
—
—
—
—
—
—
65
140M-C2E-A25
0.25...0.40
—
—
—
—
—
65
140M-C2E-A40
0.40...0.63
—
—
—
—
—
65
140M-C2E-A63
0.63...1.0
—
—
—
—
1/2
3/4
65
140M-C2E-B10
1.0...1.6
—
1/10
—
—
3/4
1
65
140M-C2E-B16
1.6...2.5
1/10
1/6
1/2
1/2
1-1/2
2
65
140M-C2E-B25
2.5...4
1/8
1/3
1
1
3
3
65
140M-C2E-B40
4...6.3
1/4
3/4
1-1/2
2
3
5
65
140M-C2E-B63
6.3...10
1/2
1-1/2
3
3
7-1/2
10
65
140M-C2E-C10
10...16
1
3
3
5
10
10
10
140M-C2E-C16
14.5...20
1-1/2
3
5
7-1/2
15
20
10
140M-C2E-C20
18...25
2
3
7-1/2
10
20
25
10
140M-C2E-C25
140M-D, High Break PLUS
1.6...2.5
1/10
1/6
1/2
1/2
1-1/2
2
65
140M-D8E-B25
2.5...4
1/8
1/3
1
1
3
3
65
140M-D8E-B40
4...6.3
1/4
3/4
1-1/2
2
3
5
65
140M-D8E-B63
6.3...10
1/2
1-1/2
3
3
7-1/2
10
65
140M-D8E-C10
10...16
1
3
3
5
10
10
65
140M-D8E-C16
14.5...20
1-1/2
3
5
7-1/2
15
20
65
140M-D8E-C20
18...25
2
3
7-1/2
10
20
25
25
140M-D8E-C25
140M-F, High Break PLUS
6.3...10
1/2
1-1/2
3
3
7-1/2
10
➌
140M-F8E-C10
10...16
1
3
3
5
10
10
➌
140M-F8E-C16
14.5...20
1-1/2
3
5
7-1/2
15
20
➌
140M-F8E-C20
18...25
2
3
5
10
20
25
➌
140M-F8E-C25
23...32
3
5
10
10
25
30
➌
140M-F8E-C32
32...45
3
7-1/2
15
15
30
40
➌
140M-F8E-C45
➊ Horsepower ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor
full load current and service factor.
• For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range.
Example: Motor F.L.C. = 4.2 A; S.F. = 1.0. (4.2 A x 0.9 = 3.78 A.) Select Cat. No. 140M-C2E-B40.
➋ Magnetic trip is fixed at 13x the maximum value of the current adjustment range.
➌ UL Pending. Contact your local Allen-Bradley Sales Office.
3-162
Bulletin 140M
Motor Protectors
Accessories
Description
Operator Position ➊
OFF
ON
Tripped Term.
No.
Desc.
Connection Diagram ➋
For Use
With
Cat. No.
140M
140M-C-AFA10
140M
140M-C-AFA01
140M
140M-C-AFA11
140M
140M-C-AFA20
140M
140M-C-AFA02
140M
140M-C-ASA20
140M
140M-C-ASA02
140M
140M-C-ASA11
13
O
X
O
13-14
N.O. Aux
14
I >>
11
X
O
X
11-12
N.C. Aux
12
I >>
Front-Mounted
Auxiliary Contact
• 1-pole or 2-pole
• No additional
space required
O
X
O
13-14
13
21
14
22
13
23
14
24
N.O. Aux
I >>
X
O
X
21-22
N.C. Aux
O
X
O
13-14
N.O. Aux
I >>
O
X
O
23-24
N.O. Aux
X
O
X
11-12
N.C. Aux
11
21
12
22
I >>
Right
Side-Mounted
Auxiliary Contact
• 2-pole
• Adds 9 mm to
the width of the
device
X
O
X
21-22
N.C. Aux
O
X
O
33-34
N.O. Aux
O
X
O
43-44
N.O. Aux
X
O
X
31-32
N.C. Aux
X
O
X
41-42
N.C. Aux
O
X
O
33-34
N.O. Aux
X
O
X
41-42
N.C. Aux
33
43
34
44
31
41
32
42
I >>
I >>
33
41
34
42
I >>
➊ X = Contact Closed
O = Contact Open
➋
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
3-163
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
Operator Position ➊
Front-Mounted
Trip Contact
• 2-pole
• Indicates tripping
of device
• No additional
space required
OFF
ON
Tripped
Term.
No.
Desc.
O
X
O
13-14
N.O. Aux
O
O
X
27-28
N.O. Trip
(Short-Circuit &
Overload)
X
O
X
11-12
N.C. Aux
O
O
X
27-28
N.O. Trip
(Short-Circuit &
Overload)
O
O
X
57-58
N.O. Trip
(Short-Circuit &
Overload)
O
O
Right
Side-Mounted Trip
Contact
• 2-pole
• Indicates tripping
of Motor
Protector
• Adds 9 mm to
the width of the
circuit breaker
X
X
O
X
X
O
X
➊ X = Contact Closed
O = Contact Open
➋
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
3-164
O
O
X
X
O
X
X
O
X
X
X
O
O
X
O
O
X
O
67-68
N.O. Trip
(Short-Circuit)
57-58
N.O. Trip
(Short-Circuit &
Overload)
65-66
N.C. Trip
(Short-Circuit)
55-56
N.C. Trip
(Short-Circuit &
Overload)
67-68
N.O. Trip
(Short-Circuit)
55-56
N.C. Trip
(Short-Circuit &
Overload)
65-66
N.C. Trip
(Short-Circuit)
77-78
N.O. Trip
(Short-Circuit)
65-66
N.C. Trip
(Short-Circuit)
Connection
Diagram ➋
13
27
14
28
For Use
With
Cat. No.
140M
140M-C-AFAR10A10
140M
140M-C-AFAR10A01
140M
140M-C-ASAR10M10
140M
140M-C-ASAR10M01
140M
140M-C-ASAR01M10
140M
140M-C-ASAR01M01
140M
140M-C-ASAM11
I >>
11
27
12
28
I >>
57
67
58
68
I >>
57
65
58
66
I >>
55
67
56
68
55
65
56
66
I >>
I >>
77
65
78
66
I >>
Bulletin 140M
Motor Protectors
3
Accessories, Continued
Description
Operator Position ➊
OFF
ON
O
X
Tripped Term.
No.
O
13-14
Desc.
N.O. Aux
Connection Diagram ➋
For Use
With
140-CMN
140-CA20
O
Front-Mounted
Auxiliary Contacts
• Internal
• 2-Pole
X
X
O
O
X
23-24
11-12
13
23
14
24
140-CMN
140-CMN
140-CA02
X
O
O
X
X
O
21-22
13-14
11
21
12
22
140-CMN
140-CA11
X
O
O
O
X
X
21-22
N.C. Aux
37-38
N.O. Trip
(Overload)
O
X
43-44
140-CA11
13
21
14
22
I >>
140-CMN
140-CT10-10
a
O
140-CA02
I >>
N.C. Aux
N.O. Aux
140-CA20
I >>
N.O. Aux
N.C. Aux
Cat. No.
37
43
38
44
140-CT10-10
I >>
N.O. Trip
(Short-Circuit)
b
a) Overload Trip
b) Short-Circuit Trip
X
X
O
35-36
N.C. Trip
(Overload)
140-CMN
140-CT01-01
35
a
Front-Mounted
Trip Indicating
Auxiliary Contacts
• Internal
• 2-Pole
X
X
O
41-42
41
140-CT01-01
I >>
N.C. Trip
(Short-Circuit)
b
36
42
a) Overload Trip
b) Short-Circuit Trip
X
X
O
35-36
N.C. Trip
(Overload)
140-CT01-10
a
O
O
X
43-44
140-CMN
140-CMN
35
43
36
44
140-CT01-10
I >>
N.O. Trip
(Short-Circuit)
b
a) Overload Trip
b) Short-Circuit Trip
O
O
X
37-38
N.O. Trip
(Overload)
140-CMN
140-CT10-01
a
X
X
O
41-42
N.C. Trip
(Short-Circuit)
37
41
38
42
140-CT10-01
I >>
b
a) Overload Trip
b) Short-Circuit Trip
➊
➋
X = Contact Closed
O = Contact Open
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
3-165
Bulletin 140M
Motor Protectors
3
Accessories, Continued
Description
Connection Diagram ➊
Undervoltage Trip
• Left-side mounted
• Adds 18 mm to the width
of the circuit breaker
• Trips motor protector
when voltage is removed
D1
U<
Shunt Trip
• Left-side mounted
• Adds 18 mm to the width
of the circuit breaker
• Trips motor protector
when voltage is applied
Undervoltage Trip Unit
• Internal, front mounted
• Integrated short circuit
trip indication
• Trips motor protector
when voltage is removed
D2
I >>
C1
C2
I >>
24V, 50 Hz/28V, 60 Hz
110V, 50 Hz/127V, 60 Hz
220…230V, 50 Hz
240…260V, 60 Hz
240V, 50 Hz/277V, 60 Hz
380…400V, 50 Hz/440…460V, 60 Hz
415V, 50 Hz/480V, 60 Hz
21V, 50 Hz/24V, 60 Hz
110V, 50Hz/27V, 60 Hz
24V, 50 Hz/28V, 60 Hz
110V, 50 Hz/127V, 60 Hz
220…230V, 50 Hz
240…260V, 60 Hz
240V, 50 Hz/277V, 60 Hz
380…400V, 50 Hz/440…460V, 60 Hz
415V, 50 Hz/480V, 60 Hz
21V, 50 Hz/24V, 60 Hz
110V, 50 Hz/127V, 60 Hz
For Use
With
Cat. No.
140M
140M-C-UXK
140M-C-UXD
140M-C-UXF
140M-C-UXA
140M-C-UXT
140M-C-UXN
140M-C-UXB
140M-C-UXJ
140M-C-UXC
140M
140M-C-SNK
140M-C-SND
140M-C-SNF
140M-C-SNA
140M-C-SNT
140M-C-SNN
140M-C-SNB
140M-C-SNJ
140M-C-SNC
140-CMN
140-CUV...
43
b
I >>
D1
U<
24V 50/60 Hz
110V 50 Hz/120V 60 Hz 140-CMN
220V 50 Hz/240V 60 Hz
140-CUV-KJ
140-CUV-D
140-CUV-A
24V 50/60 Hz
110V 50 Hz/120V 60 Hz 140-CMN
220V 50 Hz/240V 60 Hz
140-CRT-KJ
140-CRT-D
140-CRT-A
44
D2
b) Short-Circuit Trip
140-CMN
Shunt Trip Unit
• Internal, front mounted
• Integrated short circuit
trip indication
• Trips motor protector
when voltage is applied
140-CRT...
43
b
I >>
C1
44
C2
b) Short-Circuit Trip
➊
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
3-166
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
For Use With
Cat. No.
140M
140M-C-CA
black
140M
140M-C-KN
red/yellow
140M
140M-C-KRY
Anti Tamper Shield
• Provides protection against inadvertent adjustment of the current setting
Lockable Twist Knob
• For 1 padlock 4…8 mm (5/16") dia. shackle
• Can be locked in OFF position
140-KN
black
Padlockable Operating Knob
• Accepts 8mm (5/16") padlock — up to three padlocks.
• Permits padlocking in the off position.
140-CMN
140-KRY
red/yellow
Door Coupling Handle
• For 3 padlocks 4…8 mm (5/16") in diameter
• IP66 Protection/Type 1,3,3R,4,4x,13
• Interlock override capability
• Can be modified for locking in ON position
• Ships with coupling — order extension shaft and
legend plate separately
• Mounting depth (adapter-door):
140-C: 105.5 mm ± 5 mm (4.15" ± 3/16")
140-D: 114.5 mm ± 5 mm (4.5" ± 3/16")
140-F: 137.1 mm ± 5 mm (5.4" ± 3/16")
140M
140M-C-DN66
140-CMN
140-CDN66
140M
140M-C-DRY66
140-CMN
140-CDRY66
140M-C-DN66
140M-C-DRY66
140M-C-DS
140M-C-DN66
140M-C-DFCN
black
red/yellow
Extension Shaft
• Cut to required length for mounting depth (adapter-door):
140-C: 117…338 mm (4.6"…13.3")
140-D: 126…347 mm (5.0"…13.7")
140-F: 149…369 mm (5.4"…14.5")
Legend Plate
• Marking: "Haupschalter" and "Main Switch"
• Marking: "Not-Aus" and "Emergency Off"
140M-C-DRY66 140M-C-DFCRY
Locking Tag
• Padlock attachment to the lockable handles
• Up to three padlocks 4…8 mm (5/16") shackle
black handle
IP65 Non-Metallic Enclosure
• Knockouts for PG16 and PG21 fittings
• Suitable for flexible cable with internal ground wire or red/yellow
conduit when externally grounded around the outside handle
of the enclosure
140M-C-KN
140M-C-KRY
140M-F-KRY
140M-C-M3
140M-C
198E-AYTJ2
140M-C
198E-AYTG2
3-167
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
Connecting Modules — 25 A
• The Eco-connecting modules provide electrical and mechanical
inte-connection of 140M and 100M (with AC or DC coils) or 100C (with
AC coils) for use as combination starters
• Suitable for reversing and star/delta kits
• Eco-starters mount on single DIN Rail (140M on DIN Rail)
Connecting Modules — 45 A
• Electrical interconnection between 140M-F motor protector and 100-C
contactors (with AC coils)
• Contactor and motor protector must be mounted separately
Commoning Link Feeder Terminal
• For supply of commoning links — 600V, 65 A max.
• Top feed — overlaps commoning link
For Use With
Cat. No.
140M-C
to
100-M
140M-C-PEM12
140M-C
to
100-C09…C23
140M-C-PEC23
140M-D
to
100-C09…C23
140M-D-PEC23
140M-F
to
100-C30…C37
140M-F-PNC37
140M-F
to
100-C43
140M-F-PNC43
140M-C
140M-D
140M-C-WT
140M-F
140M-F-WT
Three-Phase Commoning Link for 25 A Motor Protectors — 63 A Max. Continuous Current
140M-C-W452
2 x 3 connections
•
•
•
•
•
•
140M-D
140M-C
45 mm spacing
For use with front-mounted auxiliary contact
54 mm spacing
For use with side-mounted auxiliary contact
3 x 3 connections
4 x 3 connections
140M-C
140M-D
140M-C-W453
140M-C-W454
5 x 3 connections
140M-C-W455
2 x 3 connections
140M-C-W542
3 x 3 connections
4 x 3 connections
140M-C
140M-D
140M-C-W543
140M-C-W544
5 x 3 connections
140M-C-W545
2 x 3 connections
140M-C-W632
63 mm spacing
3 x 3 connections
For use with side-mounted undervoltage trip and
4 x 3 connections
shunt trip
5 x 3 connections
Jumper for 140M-D to 140M-C
• Accommodates difference in depth from 140M-D
to 140M-C
2 x 3 connections
• Can be used with all other commoning links
• 54 mm spacing
140M-C
140M-D
140M-C-W633
140M-C-W634
140M-C-W635
140M-D
to
140M-C
140M-C-WD542
Three-Phase Commoning Link for 45 A Motor Protectors
•
•
•
•
54 mm spacing
For use with front-mounted auxiliary contact
63 mm spacing
For use with side-mounted auxiliary contact
2 x 3 connections
3 x 3 connections
4 x 3 connections
3 x 3 connections
3-168
140M-F-W632
140M-F
10 pcs per Pkg
140M-F-W633
140M-F-W634
4 x 3 connections
Screw Adapter
• For screw arrangement of a motor protector
140M-F-W543
140M-F-W544
2 x 3 connections
Terminal Cover
• For covering of unused connection terminals
• IP2X finger protection
DIN (#3) Symmetrical Rail
• 35 mm x 7.5 mm x 1 m long
• Zinc-plated, yellow chromated
• EN 50022
140M-F-W542
140M-F
140M-C
140M-D
140M-C-WS
140M-F
140M-F-WS
140M
140M-C-N45
—
199-DR1
Bulletin 140M
Motor Protectors
3
Specifications
UL/CSA Performance Data
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device)
Cat. No. 140M-C2EA16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
C20
Rated Operational Current,Ie[A]
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
10
16
20
25
[A]
2.1
3.3
5.2
8.2
13
21
33
52
82
130
208
260
325
480V
[kA]
65
65
65
65
65
65
65
65
65
65
10
10
10
600V
[kA]
47
47
47
47
47
47
5
5
5
5
5
5
5
115V
[HP]
—
—
—
—
—
—
1/10
1/8
1/4
1/2
1
1-1/2
2
230V
[HP]
—
—
—
—
—
1/10
1/6
2/3
3/4
1-1/2
3
3
3
230V
[HP]
—
—
—
—
—
—
1/2
1
2
3
5
7-1/2
10
460V
[HP]
—
—
—
—
1/2
3/4
1-1/2
3
3
7-1/2
10
15
20
575V
[HP]
—
—
—
—
3/4
1
2
3
5
10
10
20
25
C25
Magnetic Release Current
C25
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
Maximum Rated Current
of Protection Device
400
[A]
Self-Protected (Type E) Manual Combination Motor Controller
(UL 508)
Cat. No. 140M-C2EA16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
C20
Rated Operational Current,Ie[A]
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
10
16
20
25
[A]
2.1
3.3
5.2
8.2
13
21
33
52
82
130
208
260
325
480Y/277V
[kA]
65
65
65
65
65
65
65
65
65
65
10
10
10
600Y/347V
[kA]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
115V
[HP]
—
—
—
—
—
—
1/10
1/8
1/4
1/2
1
1-1/2
2
230V
[HP]
—
—
—
—
—
1/10
1/6
2/3
3/4
1-1/2
3
3
3
230V
[HP]
—
—
—
—
—
—
1/2
1
2
3
5
7-1/2
10
460V
[HP]
—
—
—
—
1/2
3/4
1-1/2
3
3
7-1/2
10
15
20
575V
[HP]
—
—
—
—
3/4
1
2
3
5
10
10
20
25
Magnetic Release Current
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
➊ Contact your local Allen-Bradley Sales Office.
3-169
Bulletin 140M
Motor Protectors
Specifications, Continued
UL/CSA Performance Data, Continued
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device)
Cat. No. 140M-D8E-
Cat. No. 140M-F8E-
B25
B40
B63
C10
C16
C20
C25
C10
C16
C20
C25
C32
Rated Operational Current,Ie[A]
2.5
4.0
6.3
10
16
20
25
10
16
20
25
32
45
[A]
33
52
82
130
208
260
325
130
208
260
325
416
585
480V
[kA]
65
65
65
65
65
65
25
65
65
65
65
65
50
600V
[kA]
10
10
10
10
10
5
5
10
10
10
10
10
10
115V
[HP]
1/10
1/8
1/4
1/2
1
1-1/2
2
1/2
1
1-1/2
2
3
3
230V
[HP]
1/6
1/3
3/4
1-1/2
3
3
3
1-1/2
3
3
3
5
7-1/2
Magnetic Release Current
C45
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
230V
[HP]
1/2
1
2
3
5
7-1/2
10
3
5
7-1/2
10
10
15
460V
[HP]
1-1/2
3
3
7-1/2
10
15
20
7-1/2
10
15
20
25
30
575V
[HP]
2
3
5
10
10
20
25
10
10
20
25
30
40
C45
Maximum Rated Current
of Protection Device
400
[A]
500
Type E Combination Motor Controller
(UL 508)
Cat. No. 140M-D8E-
Cat. No. 140M-F8E-
B25
B40
B63
C10
C16
C20
C25
C10
C16
C20
C25
C32
Rated Operational Current,Ie[A]
2.5
4.0
6.3
10
16
20
25
10
16
20
25
32
45
[A]
33
52
82
130
208
260
325
130
208
260
325
416
585
480Y/277V
[kA]
65
65
65
65
65
65
25
➊
➊
➊
➊
➊
➊
500Y/347V
[kA]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
115V
[HP]
1/10
1/8
1/4
1/2
1
1-1/2
2
1/2
1
1-1/2
2
3
3
230V
[HP]
1/6
1/3
3/4
1-1/2
3
3
3
1-1/2
3
3
3
5
7-1/2
Magnetic Release Current
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
230V
[HP]
1/2
1
2
3
5
7-1/2
10
3
5
7-1/2
10
10
15
460V
[HP]
1-1/2
3
3
7-1/2
10
15
20
7-1/2
10
15
20
25
30
575V
[HP]
2
3
5
10
10
20
25
10
10
20
25
30
40
➊ Contact your local Allen-Bradley Sales Office.
3-170
Bulletin 140M
Motor Protectors
Specifications, Continued
UL/CSA Performance Data, Continued
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device)
Cat. No. 140M-C2NA16
A25
A40
A63
B10
B16
B25
Rated Operational Current,Ie[A]
0.16
0.25
0.40
0.63
1.0
1.6
2.5
[A]
2.1
3.3
5.2
8.2
13
20
32
Magnetic Release Current
Max. Short Circuit Current
480V
[kA]
65
65
65
65
65
65
65
600V
[kA]
47
47
47
47
47
47
5
115V
[HP]
—
—
—
—
—
—
1/10
230V
[HP]
—
—
—
—
—
1/10
1/6
230V
[HP]
—
—
—
—
—
—
1/2
460V
[HP]
—
—
—
—
1/2
3/4
1-1/2
575V
[HP]
—
—
—
—
3/4
1
2
Motor Load, Single-Phase
Motor Load, Three-Phase
Maximum Rated Current
of Protection Device
400
[A]
Cat. No. 140M-D8N-
Cat. No. 140M-F8N-
B25
B40
B63
C10
C16
C25
C25
C32
Rated Operational Current,Ie[A]
2.5
4.0
6.3
10
16
25
25
32
45
[A]
32
52
82
130
208
325
325
416
585
480V
[kA]
65
65
65
65
65
25
65
65
50
600V
[kA]
10
10
10
10
10
5
10
10
10
115V
[HP]
1/10
1/8
1/4
1/2
1
2
2
3
3
230V
[HP]
1/6
1/3
3/4
1-1/2
3
3
3
5
7-1/2
15
Magnetic Release Current
C45
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
230V
[HP]
1/2
1
2
3
5
10
10
10
460V
[HP]
1-1/2
3
3
7-1/2
10
20
20
25
30
575V
[HP]
2
3
5
10
10
25
25
30
40
Maximum Rated Current
of Protection Device
[A]
400
500
3-171
Bulletin 140M
Motor Protectors
Specifications, Continued
UL/CSA Performance Data, Continued
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short Circuit Protection Device)
Cat. No. 140M-C2TA16
A25
A40
A63
B10
B16
B25
B40
B63
C10
Rated Operational Current,Ie[A]
0.16
0.25
0.40
0.63
1.0
1.6
2.5
4.0
6.3
10
16
[A]
3.2
5.2
8.2
13
21
32
52
82
130
208
260
480V
[kA]
65
65
65
65
65
65
65
65
65
65
10
600V
[kA]
47
47
47
47
47
47
5
5
5
5
5
115V
[HP]
—
—
—
—
—
—
1/10
1/8
1/4
1/2
1
230V
[HP]
—
—
—
—
—
1/10
1/6
2/3
3/4
1-1/2
3
230V
[HP]
—
—
—
—
—
—
1/2
1
2
3
5
460V
[HP]
—
—
—
—
1/2
3/4
1-1/2
3
3
7-1/2
10
575V
[HP]
—
—
—
—
3/4
1
2
3
5
10
10
Magnetic Release Current
C16
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
Maximum Rated Current
of Protection Device
400
[A]
Cat. No. 140M-D8T-
Cat. No. 140M-F8T-
C16
C20
C25
Rated Operational Current,Ie[A]
16
20
25
32
[A]
260
325
416
585
480V
[kA]
65
65
65
65
600V
[kA]
10
10
10
10
115V
[HP]
1
1-1/2
2
3
230V
[HP]
3
3
3
5
Magnetic Release Current
C32
Max. Short Circuit Current
Motor Load, Single-Phase
Motor Load, Three-Phase
230V
[HP]
5
7-1/2
10
10
460V
[HP]
10
15
20
25
575V
[HP]
10
20
25
30
Maximum Rated Current
of Protection Device
3-172
[A]
400
500
Bulletin 140M
Motor Protectors
Specifications, Continued
3
3
3
IEC Performance Data
Cat. No. 140M-C2EA16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
C20
Rated Operational Current,Ie[A]
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
10
16
20
25
[A]
2.1
3.3
5.2
8.2
13
21
33
52
82
130
208
260
325
230/240V
[kW]
—
—
—
0.06/
0.09
0.12
0.18/
0.25
0.37
0.55/
0.75
1.1/
1.5
2.2
3.0/
4.0
4.0/
5.5
—
400/415V
[kW]
0.02
0.06
0.09
0.12/
0.18
0.25
0.37/
0.55
0.75
1.1/1.5
2.2
3.0/
4.0
5.5/
7.5
7.5/10
11
500V
[kW]
—
—
—
0.18
0.25/
0.37
0.55/
0.75
1.1
1.5/2.2
2.5/
3.0
4.0/
6.3
7.5/10
11
15
690V
[kW]
—
—
—
0.25
0.37/
0.55
0.75/
1.1
1.8
2.2/3.0
4.0
5.5/
7.5
11/13 15/17
230/240V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
100
100
400/415V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
80
100
100
440/460V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
63
63
80
80
500V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
80
80
80
80
690V
[A]
➊
➊
➊
➊
➊
16
20
35
50
50
63
63
63
230/240V
[kA]
100
100
100
100
100
100
100
100
100
100
100
50
50
400/415V
[kA]
100
100
100
100
100
100
100
100
100
100
50
15
15
440/460V
[kA]
100
100
100
100
100
100
100
100
100
50
10
10
10
500V
[kA]
100
100
100
100
100
100
100
100
100
50
10
6
6
690V
[kA]
100
100
100
100
100
8
8
8
4
4
3
3
3
Magnetic Release Current
C25
Switching of Standard
Three-Phase Motors
AC-2, AC-3
18.5/
22
Back-Up Fuses
gG, gL, only if Icc > Icu
Ultimate Short Circuit
Breaking Capacity
Icu
Rated Service Short Circuit
Breaking Capacity
Ics
230/240V
[kA]
100
100
100
100
100
100
100
100
100
100
100
50
50
400/415V
[kA]
100
100
100
100
100
100
100
100
100
100
50
15
15
440/460V
[kA]
100
100
100
100
100
100
100
100
100
50
6
6
6
500V
[kA]
100
100
100
100
100
100
100
100
100
50
6
6
6
690V
[kA]
100
100
100
100
100
8
8
8
4
4
3
3
3
➊ No back-up fuse required.
3-173
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data, Continued
Cat. No. 140M-D8E-
Cat. No. 140M-F8E-
B25
B40
B63
C10
C16
C20
C25
C10
C16
C20
C25
C32
Rated Operational Current,Ie[A]
2.5
4.0
6.3
10
16
20
25
10
16
20
25
32
45
[A]
33
52
82
130
208
260
325
130
208
260
325
416
585
Magnetic Release Current
C45
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
0.37
0.55/
0.75
1.1/
1.5
2.2
3.0/
4.0
4.0/
5.5
—
2.2
3.0/
4.0
4.0/5.5 5.5/6.3
7.5
11/13
400/415V
[kW]
0.75
1.1/1.5
2.2
3.0/
4.0
5.5/
7.5
7.5/10
11
3.0/
4.0
5.5/
7.5
7.5/10
11
15
18.5/
22
500V
[kW]
1.1
1.5/2.2
2.5/
3.0
4.0/
6.3
7.5/10
11
15
4.0/
6.3
7.5/10
11
15
15/20
22/30
690V
[kW]
1.8
2.2/3.0
4.0
5.5/
7.5
11/13
15/17
18.5/
22
5.5/
7.5
11/13
15/17
18.5/
22
22/25
30/40
230/240V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
400/415V
[A]
➊
➊
➊
➊
➊
100
100
80
100
100
100
125
125
440/460V
[A]
➊
➊
➊
➊
80
100
100
➋
➋
➋
➋
➋
➋
500V
[A]
➊
➊
➊
➊
80
80
80
80
80
80
80
100
100
690V
[A]
20
35
50
50
63
63
63
50
63
63
63
80
80
230/240V
[kA]
100
100
100
100
100
100
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
50
50
50
50
50
50
50
50
440/460V
[kA]
100
100
100
100
50
50
50
➋
➋
➋
➋
➋
➋
500V
[kA]
100
100
100
40
25
25
25
10
10
10
10
10
10
690V
[kA]
10
10
10
10
6
6
6
6
6
6
6
6
6
Back-Up Fuses
gG, gL, only if Icc > Icu
Ultimate Short Circuit
Breaking Capacity
Icu
Rated Service Short Circuit
Breaking Capacity
Ics
230/240V
[kA]
100
100
100
100
100
100
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
50
25
25
50
50
25
25
25
25
440/460V
[kA]
100
100
100
100
50
25
25
➋
➋
➋
➋
➋
➋
500V
[kA]
100
100
100
100
50
25
25
10
10
10
10
10
10
690V
[kA]
10
10
10
6
4
4
4
6
6
6
6
6
4
➊ No back-up fuse required.
➋ Contact your local Allen-Bradley Sales Office.
3-174
Bulletin 140M
Motor Protectors
Specifications, Continued
3
3
3
IEC Performance Data, Continued
Cat. No. 140M-C2NRated Operational Current,Ie[A]
Magnetic Release Current
[A]
A16
A25
A40
A63
B10
B16
B25
0.16
0.25
0.4
0.63
1
1.6
2.5
2.1
3.3
5.2
8.2
13
21
32
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
—
—
—
0.06/0.09
0.12
0.18/0.25
0.37
400/415V
[kW]
0.02
0.06
0.09
0.12/0.18
0.25
0.37/0.55
0.75
500V
[kW]
—
—
—
0.18
0.25/0.37
0.55/0.75
1.1
690V
[kW]
—
—
—
0.25
0.37/0.55
0.75/1.1
1.8
230/240V
[A]
➊
➊
➊
➊
➊
➊
➊
400/415V
[A]
➊
➊
➊
➊
➊
➊
➊
440/460V
[A]
➊
➊
➊
➊
➊
➊
➊
500V
[A]
➊
➊
➊
➊
➊
➊
➊
690V
[A]
➊
➊
➊
➊
➊
16
20
Back-Up Fuses
gG, gL, only if Icc > Icu ➊
Ultimate Short Circuit
Breaking Capacity
Icu
230/240V
[kA]
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
100
100
440/460V
[kA]
100
100
100
100
100
100
100
500V
[kA]
100
100
100
100
100
100
100
690V
[kA]
100
100
100
100
100
8
8
Rated Service Short Circuit
Breaking Capacity
Ics
230/240V
[kA]
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
100
100
440/460V
[kA]
100
100
100
100
100
100
100
500V
[kA]
100
100
100
100
100
100
100
690V
[kA]
100
100
100
100
100
8
8
➊ No back-up fuse required.
3-175
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data, Continued
Cat. No. 140M-D8N-
Cat. No. 140M-F8N-
B25
B40
B63
C10
C16
C25
C25
C32
Rated Operational Current,Ie[A]
2.5
4.0
6.3
10
16
25
25
32
45
[A]
32
52
82
130
208
325
325
416
585
Magnetic Release Current
C45
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
0.37
0.55/0.75
1.1/1.5
2.2
3.0/4.0
—
5.5/6.3
7.5
11/13
400/415V
[kW]
0.75
1.1/1.5
2.2
3.0/4.0
5.5/7.5
11
11
15
18.5/22
500V
[kW]
1.1
1.5/2.2
2.5/3.0
4.0/6.3
7.5/10
15
15
15/20
22/30
690V
[kW]
1.8
2.2/3.0
4.0
5.5/7.5
11/13
18.5/22
18.5/22
22/25
30/40
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
400/415V
[A]
➊
➊
➊
➊
➊
100
100
125
125
440/460V
[A]
➊
➊
➊
➊
80
100
➋
➋
➋
500V
[A]
➊
➊
➊
➊
80
80
80
100
100
690V
[A]
20
35
50
50
63
63
63
80
80
230/240V
[kA]
100
100
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
50
50
50
50
440/460V
[kA]
100
100
100
100
50
50
➋
➋
➋
500V
[kA]
100
100
100
10
50
25
10
10
10
690V
[kA]
10
10
10
6
6
6
6
6
6
Ultimate Short Circuit
Breaking Capacity
Icu
Rated Service Short Circuit
Breaking Capacity
Ics
230/240V
[kA]
100
100
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
25
25
25
25
440/460V
[kA]
100
100
100
100
50
25
➋
➋
➋
500V
[kA]
100
100
100
100
50
25
10
10
10
690V
[kA]
10
10
10
6
4
4
6
6
4
➊ No back-up fuse required.
➋ Contact your local Allen-Bradley Sales Office.
3-176
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data, Continued
Cat. No. 140M-C2TA16
A25
A40
A63
B10
B16
B25
B40
B63
C10
0.16
0.25
0.40
0.63
1.0
1.6
2.5
4.0
6.3
10
16
[A]
3.2
5.2
8.2
13
21
32
52
82
130
208
260
230/240V
[kW]
—
—
—
0.06/
0.09
0.12
0.18/
0.25
0.37
0.55/
0.75
1.1/1.5
2.2
3.0/4.0
400/415V
[kW]
0.02
0.06
0.09
0.12/
0.18
0.25
0.37/
0.55
0.75
1.1/1.5
2.2
3.0/4.0
5.5/7.5
500V
[kW]
—
—
—
0.18
0.25/
0.37
0.55/
0.75
1.1
1.5/2.2
2.5/3.0
4.0/6.3
7.5/10
690V
[kW]
—
—
—
0.25
0.37/
0.55
0.75/1.1
1.8
2.2/3.0
4.0
5.5/7.5
11/13
230/240V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
400/415V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
80
440/460V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
63
63
500V
[A]
➊
➊
➊
➊
➊
➊
➊
➊
➊
80
80
690V
[A]
➊
➊
➊
➊
➊
16
20
35
50
50
63
230/240V
[kA]
100
100
100
100
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
100
100
100
100
100
15
440/460V
[kA]
100
100
100
100
100
100
100
100
100
50
10
500V
[kA]
100
100
100
100
100
100
100
100
100
50
6
690V
[kA]
100
100
100
100
100
8
8
8
4
4
3
Rated Operational Current,Ie[A]
Magnetic Release Current
C16
Switching of Standard
Three-Phase Motors
AC-2, AC-3
Back-Up Fuses
gG, gL, only if Icc > Icu
Ultimate Short Circuit
Breaking Capacity
Icu
Rated Service Short Circuit
Breaking Capacity
Ics
230/240V
[kA]
100
100
100
100
100
100
100
100
100
100
100
400/415V
[kA]
100
100
100
100
100
100
100
100
100
100
15
440/460V
[kA]
100
100
100
100
100
100
100
100
100
50
6
500V
[kA]
100
100
100
100
100
100
100
100
100
50
6
690V
[kA]
100
100
100
100
100
8
8
8
4
4
3
➊ No back-up fuse required.
3-177
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data, Continued
Cat. No. 140M-D8T-
Cat. No. 140M-F8T-
C16
C20
C25
Rated Operational Current,Ie[A]
16
20
25
32
[A]
260
325
416
585
7.5
Magnetic Release Current
C32
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
3.0/4.0
4.0/5.5
5.5/6.3
400/415V
[kW]
5.5/7.5
7.5/10
11
15
500V
[kW]
7.5/10
11
15
15/20
690V
[kW]
11/13
15/17
18.5/22
22/25
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
➊
➊
➊
➊
400/415V
[A]
80
100
100
125
440/460V
[A]
80
100
➋
➋
500V
[A]
80
80
80
100
690V
[A]
63
63
63
80
230/240V
[kA]
100
100
100
100
400/415V
[kA]
50
50
50
50
440/460V
[kA]
50
50
➋
➋
500V
[kA]
25
25
10
10
690V
[kA]
6
6
6
6
Ultimate Short Circuit
Breaking Capacity
Icu
Rated Service Short Circuit
Breaking Capacity
Ics
230/240V
[kA]
100
100
100
100
400/415V
[kA]
25
25
25
25
440/460V
[kA]
25
25
➋
➋
500V
[kA]
25
25
10
10
690V
[kA]
4
4
6
6
➊ No back-up fuse required.
➋ Contact your local Allen-Bradley Sales Office.
3-178
Bulletin 140M
Motor Protectors
Specifications, Continued
General Data
Cat. No.
140M-C…
140M-D…
Rated Insulation Voltage
IEC, SEV, VDE 0660
690 V
UL, CSA
600 V
Rated Impulse Withstand Voltage
Uimp/pollution degree
6 kV/3
50/60 Hz
Rated Frequency
Utilization Category:
• IEC 947-2 (Motor Protector)
• IEC 947-4-1 (Motor Starter)
Life Span
Mechanical
140M-F…
A
AC-3
[operations]
Electrical (Ie max.)
[operations]
Switching Frequency
[operations]
100,000
30,000
100,000
30,000
max. 25/h. (motor starts)
Ambient Temperature
Storage
–40…+80°C
Operation
–25…+60°C
IEC 68-2
Resistance to Climatic Change
to 2,000 m N.N.
Site Altitude
IP20 all round, when wired
Protection Class
30 G, 11 ms
Resistance to Shock
Rated Thermal Current Ith
IEC, SEV, VDE 0660
Up to 60 °C ambient temperature
—
IEC 68-2
Resistance to Vibration
0.1…25
1.6…25
6.3…45
[A]
Overload Protection
Characteristics
IEC 947-4-1 Motor protection (except 140M-C2N, 140M-D8N, 140M-F8N)
Ambient temperature compensation
–20…+60°C
Phase-failure protection
yes differential release
fixed setting
13 x Iemax. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N)
16…20 x Iemax. (for 140M-C2T, 140M-D8T, 140M-F8T)
Magnetic Release
Response current
Iemax. = maximum values of setting ranges
Total Power Loss Pv
Motor protector at rated load
operating temperature
6…8
6…8
9…16
[W]
3-179
Bulletin 140M
Motor Protectors
Specifications, Continued
General Data
Cat. No.
140M-C…
140M-D…
140M-F…
Conformity to Standards
IEC 947;
EN 60947;
UL 508; CSA 22.2
Approvals
CE, UL, CSA
Terminal Parts
Type of terminals
Screwdriver
Pozidriv No. 2/Blade No. 3
Pozidriv No. 2/Blade No. 3
1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
1…4/No. 16…12
1…4/No. 16…12
2.5…16/No.14…6
2.5…10/No. 14…8
1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
1…6/No. 16…8
1…6/No. 16…8
2.5…25/No. 14…4
2.5…16/No. 14…6
1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
1.5…6/No. 16…8
1.5…6/No. 16…8
2.5…25/No. 14…4
2.5…16/No. 14…6
1…2.5/8.9…22
1.5…3.5/13…31
Tightening torque
[Nm]/[lb-in]
Accessories for Bulletin 140M Motor Protectors
Rated Thermal Current Ith
at 40°C ambient temperature
at 60°C ambient temperature
Contact Class Coordination
According to NEMA
(UL/CSA-Standards)
Auxiliary Contact Blocks for
Right-Side Mounting
Cat. No. 140M-C-ASA…,
140M-C-ASAR…
5
4
10
6
B 300
Q 300
B 600
Q 600
[A]
[A]
AC
DC
Back-Up Fuses gG, gL
[A]
Rated Supply Current
AC-15:
[V]
DC-13:
Auxiliary Contact Blocks for
Front Mounting
Cat. No. 140M-C-AFA…,
140M-C-AFAR…
10
10
[A]
24
4
120
3
240
1.5
24
6
120
5
240
3
415
2
[V]
[A]
24
2
120
0.5
240
0.25
24
2
120
0.5
240
0.25
415
0.15
Terminal Parts
Type of terminals
Pozidriv No. 2/Blade No. 3
Screwdriver
1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.5…2.5/No. 18…14
0.5…2.5/No. 18…14
1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
Tightening torque
3-180
[Nm]/[lb-in]
1.5/13.3
690
0.7
Bulletin 140M
Motor Protectors
Specifications, Continued
Accessories for Bulletin 140M Motor Protectors
Actuating Voltage
Pull-in
Drop-out
Rated Control Voltage
On-Time
Coil Rating
min.
max.
Pull-in
Hold
Undervoltage Trip
for Left-Side Mounting
Cat. No. 140M-C-UX…
Undervoltage Trip
with 2 Auxiliary Contacts
for Left-Side Mounting
Cat. No. 140M-C-UC…
Shunt Trip
for Left-Side Mounting
Cat. No. 140M-C-SN…
0.85…1.1 x Us
0.7…0.35 x Us
0.85…1.1 x Us
0.7…0.35 x Us
0.7…1.1 x Us
21V 50 Hz, 24V 60 Hz
600V 50 Hz
100%
8.5 VA, 6 W
3 VA, 1.2 W
21V 50 Hz, 24V 60 Hz
600V 50 Hz
100%
8.5 VA, 6 W
3 VA, 1.2 W
21V 50 Hz, 24V 60 Hz
600V 50 Hz
100%
8.5 VA, 6 W
3 VA, 1.2 W
Terminal Parts
Type of terminals
Pozidriv No. 2/Blade No. 3
0.5…2.5/No. 18…14
0.5…2.5/No. 18…14
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
1.5/13.3
Screwdriver
1. conductor
2. conductor
1. conductor
2. conductor
1. conductor
2. conductor
Tightening torque
[mm2]/[AWG]
[mm2]/[AWG]
[mm2]/[AWG]
[mm2]/[AWG]
[mm2]/[AWG]
[mm2]/[AWG]
[Nm]/[lb-in]
Commoning Link Feeder Terminal
140M-C-WT
Commoning Link
140M-C-W
63
63
Rated Thermal Current Ith
at 60°C ambient temperature
[A]
1. conductor
[mm2]/[AWG]
2. conductor
[mm2]/[AWG]
1. conductor
[mm2]/[AWG]
2. conductor
[mm2]/[AWG]
1. conductor
[mm2]/[AWG]
2. conductor
[mm2]/[AWG]
Tightening torque
[Nm]/[lb-in]
4…16
4…10
6…25/No. 14…4
6…16/No. 14…6
6…25/No. 14…4
6…16/No. 14…6
3/27
—
—
—
—
Weights
Description
Motor Protectors
Auxiliary Contacts
Undervoltage Trip
Anti-tamper Cover
Cat. No.
140M-C2E-…
140M-D8E-…
140M-F8E-…
140M-C2N-…
140M-D8N-…
140M-F8N-…
140M-C2T-…
140M-D8T-…
140M-F8T-…
140M-C-AFA10
140M-C-AFA01
140M-C-AFA11
140M-C-AFA20
140M-C-ASA…
140M-C-AFAR10A…
140M-C-ASAR…M…
140M-C-ASAM11
140M-C-UX…
140M-C-SN…
140M-C-UC…
140M-C-CA
Weight
317 g
373 g
782 g
315 g
365 g
782 g
315 g
365 g
782 g
Description
Lockable Twist Knob
Locking Tag
Door Coupling Handle
Extension Shaft
Legend Plate
Feeder Terminal
10 g
15 g
108 g
110 g
116 g
2g
Commoning Links
Cat. No.
140M-C-KN
140M-C-KRY
140M-C-M3
140M-C-DN66
140M-C-NRY66
140M-C-DS
140M-C-DFC…
140M-C-WT
140M-F-WT
140M-C-W452
140M-C-W453
140M-C-W454
140M-C-W455
140M-C-W542
140M-C-W543
140M-C-W544
140M-C-W545
140M-C-W632
140M-C-W633
140M-C-W634
140M-C-W635
Weight
5g
30 g
123 g
46 g
4g
172 g
47 g
80 g
104 g
132 g
52 g
86 g
118 g
154 g
56 g
92 g
134 g
170 g
3-181
Bulletin 140M
Motor Protectors
3
Specifications, Continued
Time-Current Characteristic
140M Motor Protector
1) Thermal Release Trip Current:
The adjustable current-dependent delayed bimetal release
protects motors against overload. The curve shows the mean
operating current at an ambient temperature of 20°C starting
from the cold state. Careful testing and setting ensures
effective motor protection even in the case of single-phasing.
The overload characteristic is also valid for transformer
protection.
10 000
1h
1 000
100
1
2) Magnetic Release Trip Current:
The instantaneous magnetic trip has a fixed operating current
setting. This corresponds to 13 times the maximum value of
setting range. (Transformer protection up to 20 x Ie max.) At
a lower setting it is correspondingly higher.
10
1
2
Tripping time [s]
0.1
0.01
0.001
0.8 1
2
4
6
10
Multiple of set current IeF
3-182
20
40 60
100
Current Setting IeF:
The overload trip corresponds to a thermal overload relay in
a motor starter conforming to IEC 947-4-1. If a different value
is prescribed (e.g., reduced Ie for cooling medium having a
temperature higher than 40°C or a place of installation higher
than 2000 m above sea level), the setting current is equal to
the reduced rated current Ie of the motor.
Bulletin 140M
Motor Protectors
3
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
➋
24.8 (31/32)
18
(23/32)
9
(23/64)
45
(1-25/32)
4.5
(3/16)
62 (2-7/16)
4.5
(3/16)
29.4 (1-5/32)
➋
9
(23/64)
➍
54 (2-1/8)
72 (2-53/64)
7.5
(19/64)
140M-D…
45 (1-25/32)
➊
55 (2-11/64)
110 (4-21/64)
55 (2-11/64)
4.5
(3/16)
➌
54
(2-1/8)
7.5
(19/64)
➊
140M-C….
140M-C…, 140M-D…
18
(23/32)
➍
44 (1-47/64)
45 (1-25/32)
45 (1-25/32)
➊
45 (1-25/32)
➌
.
45 (1-25/32)
4.5
(3/16)
90 (3-35/64)
45 (1-25/32)
.
➊
➋
➌
➍
Mounting on 35 mm DIN Rail EN 50 022-35
Auxiliary contact (side-mounted)
Undervoltage trip or Shunt trip
Auxiliary contact (front-mounted)
➍
91 (3-37/64)
4.5
(3/16)
102 (4-1/64)
7.5
(19/64)
140M-F….
90
90
˚
90
˚
90
˚
˚
4.5
min. 100
3.5
1.5...5
35...45
Mounting position 140M-C…, 140M-D…, 140M-F…
b
53.5
a
53.5
a
4...8
b
±5
c1
c2
49.5
40.5
140M-C…
117…338
105.5
140M-D…
126…347
114.5 ±5
49.5
40.5
140M-F…
148.6…369.6
137.1 ±5
59.35
50.35
c2
4.5
c1
+ 5 mm
2.4
140M-C-D…66
3-183
Bulletin 140M
Motor Protectors
3
Approximate Dimensions, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 140-CMN
Mounting position of
Cat. No. 140-CMN
3-184
Bulletin 140M
Motor Protectors
Type 2 Coordination
Type 2 Coordination per UL508E
Voltage: 480V, 60 HZ
Motor Protector
Cat. No.
Thermal Overload
Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Contactor
Cat. No. ➊
Short Circuit Current, Iq
[kA]
140M-C2E-A16
0.10…0.16
2.1
100-C09, 100-M05
65
140M-C2E-A25
0.16…0.25
3.3
100-C09, 100-M05
65
140M-C2E-A40
0.25…0.40
5.2
100-C09, 100-M05
65
140M-C2E-A63
0.40…0.63
8.2
100-C09, 100-M05
65
140M-C2E-B10
0.63…1.0
13
100-C09, 100-M05
65
140M-C2E-B16
1.0…1.6
21
100-C09, 100-M05
65
140M-C2E-B25
1.6…2.5
33
100-C09
50
140M-C2E-B40
2.5…4.0
52
100-C30
50
140M-C2E-B63
4.0…6.3
82
100-C30
50
140M-C2E-C10
6.3…10.0
130
100-C30
50
140M-C2E-C16
10.0…16.0
208
100-C30
10
140M-C2E-C20
14.5…20.0
260
100-C30
10
140M-C2E-C25
18.0…25.0
325
100-C30
10
140M-D8E-B25
1.6…2.5
33
100-C09
65
140M-D8E-B40
2.5…4.0
52
100-C09
65
140M-D8E-B63
4.0…6.3
82
100-C09
65
140M-D8E-C10
6.3…10.0
130
100-C09
65
140M-D8E-C16
10.0…16.0
208
100-C12
65
140M-D8E-C20
14.5…20.0
260
100-C23
65
140M-D8E-C25
18.0…25.0
325
100-C23
50
140M-F8E-C10
6.3…10.0
130
100-C16
65
140M-F8E-C16
10.0…16.0
208
100-C16
65
140M-F8E-C20
14.5…20.0
260
100-C23
65
140M-F8E-C25
18.0…25.0
325
100-C23
65
140M-F8E-C32
23.0…32.0
416
100-C30
65
140M-F8E-C45
32.0…45.0
585
100-C37
50
140-CMN-2500
16.0…25.0
350
100-C30
65
140-CMN-4000
25.0…40.0
560
100-C30
65
140-CMN-6300
40.0…63.0
882
100-C43
65
140-CMN-9000
63.0…90.0
1260
100-C72
65
Definition of Type 2 Short Circuit Coordination per UL 508E:
•
•
The contactor or starter must not endanger persons or plant in the event of a short circuit.
No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if these can be
easily separated without appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully short
circuit coordinated starter combinations in accordance with UL508E, Type 2 coordination.
➊ Ratings apply to specified or larger contactor.
3-185
Bulletin 140M
Motor Protectors
Type 2 Coordination, Continued
Type 2 Coordination per UL 508E, Continued
Voltage: 600V, 60 HZ
Motor Protector
Cat. No.
Thermal Overload
Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Contactor
Cat. No. ➊
Short Circuit Current, Iq
[kA]
140M-C2E-A16
0.10…0.16
2.1
100-C09, 100-M05
47
140M-C2E-A25
0.16…0.25
3.3
100-C09, 100-M05
47
140M-C2E-A40
0.25…0.40
5.2
100-C09, 100-M05
47
140M-C2E-A63
0.40…0.63
8.2
100-C09, 100-M05
47
140M-C2E-B10
0.63…1.0
13
100-C09, 100-M05
47
140M-C2E-B16
1.0…1.6
21
100-C09, 100-M05
47
140M-C2E-B25
1.6…2.5
33
100-C09
10
140M-C2E-B40
2.5…4.0
52
100-C16
5
140M-C2E-B63
4.0…6.3
82
100-C23
5
140M-C2E-C10
6.3…10.0
130
100-C30
5
140M-C2E-C16
10.0…16.0
208
100-C30
5
140M-C2E-C20
14.5…20.0
260
100-C30
5
140M-C2E-C25
18.0…25.0
325
100-C30
5
140M-D8E-B25
1.6…2.5
33
100-C09
10
140M-D8E-B40
2.5…4.0
52
100-C16
10
140M-D8E-B63
4.0…6.3
82
100-C23
10
140M-D8E-C10
6.3…10.0
130
100-C30
10
140M-D8E-C16
10.0…16.0
208
100-C30
10
140M-D8E-C20
14.5…20.0
260
100-C30
5
140M-D8E-C25
18.0…25.0
325
100-C30
5
140M-F8E-C10
6.3…10.0
130
100-C30
10
140M-F8E-C16
10.0…16.0
208
100-C30
10
140M-F8E-C20
14.5…20.0
260
100-C30
10
140M-F8E-C25
18.0…25.0
325
100-C30
10
140M-F8E-C32
23.0…32.0
416
100-C30
10
140M-F8E-C45
32.0…45.0
585
100-C37
10
140-CMN-2500
16.0…25.0
350
100-C30
42
140-CMN-4000
25.0…40.0
560
100-C30
42
140-CMN-6300
40.0…63.0
882
100-C43
30
140-CMN-9000
63.0…90.0
1260
100-C72
15
Definition of Type 2 Short Circuit coordination per UL 508E:
•
•
The contactor or starter must not endanger persons or plant in the event of a short circuit.
No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily
separated without appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully short
circuit coordinated starter combinations in accordance with UL508, Type 2 coordination.
➊ Ratings apply to specified or larger contactor.