RM4830 - power, Murata

!-0
-/$5,!237)4#(%$-/$%2%#4)&)%2
2-
&%!452%3
s 37)4#(%$-/$%
s 0&#
s %&&)#)%.#9
s (/437!0#!0!",%
s !54/-!4)#,/!$3(!2).'
s #/-0!#43):%
s 3(%,&-/5.4%$
s "%,,#/2%"!3%$$%3)'.
s 2%-/4%2%34!24&5.#4)/.
s &2/.40!.%,#522%.4-%4%2
s "!44%29/2"!44%29,%33/0%2!4)/.
s ).4%,,)'%.4()'(6/,4!'%3(54$/7.
s '5!2!.4%%$./3).',%0!24&!),52%7),,
2%35,4)./54054()'(6/,4!'%
$%3#2)04)/.
s 4($
4HE2--ODULAR3WITCHED-ODE2ECTIFIERISONE
OFDFAMILYOFRECTIFIERSTHATMAYBEUSEDIN
MODULAR POWER PLANTS 4HIS UNIT WILL FUNCTION IN PARALLEL
WITH ANY RECTIFIER WITH SIMILAR
R CURRENT
CURRENT SHARING
SHARING CAPACITIES
4HISCOMPACTVERSATILEANDEFFICIENTUNITISIDEALFORUSEIN
DE
EFFICIENT UNIT IS IDEAL FOR USE
E IN
SMALLTOMEDIUMCELLULARAND0#3SITES
AN
ND 0#3 SITES
!'%.#9!002/6!,3
Contact Factory for Replacement Model
www.murata-ps.com
Technical enquiries - email: [email protected], tel: +1 508 339 3000
Input Specifications
Parameter
Conditions
Operating Range
Current (when supplying 30ADC at 48VDC)
Min
45 - 65 Hz, single phase, no taps required
105 VAC
Max
Units
264
VAC
AAC
20
208 VAC
240 VAC
Efficiency
Power Factor Correction (PFC)
Typ
106
10
8.5
>85
input range between 105VAC-264VAC
AAC
AAC
%
>.99
MEASUREMENTS OF RM4830
Module
Shelf*
Weight
Height
Depth
Width
Weight
Height
Depth
Width
14 lbs.
5 U (8.75”)
15.55”
3.35”
21 lbs.
5 U (8.75”)
15.55”
23” rack mount
* These measurements are specifically for the 180A Power Shelf for up to 6 quantity RM 4830.
Please contact factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules
These shelf-mounted modules are easy and safe to install
or remove while system is operational without affecting
the overall system’s performance.
Current Limit
When rectifier current reaches 30ADC - 32ADC, the unit
will automatically limit the current down to short circuit conditions with no fold back.
Parallel Operation and Automatic Load Sharing
A series of RM4830 rectifiers will automatically share equal
amounts of the load current when operating in parallel
within ±5% of the average current for the load applied.
LED Indicators
The front panel includes a 10 segment yellow LED output
current bar graph, a green normal operation LED, and a
red rectifier failed LED.
N+1 Operation
The rectifier can operate in true N + 1 redundacy mode.
Safety
UL/CUL Recognized: UL 1950/CSA 950.
File No.: E131694
EMI filtering to FCC and VDE-0875 limits.
Remote Equalize
The rectifier output may be changed from float to equalize
via remote signal.
www.murata-ps.com
Technical enquiries - email: [email protected], tel: +1 508 339 3000
Output Specifications
Parameter
Conditions
Min
Typ
Max
Units
Voltage Adjustment Range
Regulation
Load Current
Filtering
Voice band
Wide band noise
float voltage
40
60
VDC
equalize voltage
0-100% load within
specified input voltage and frequency range
within a 10 - 100% rating
40
60
VDC
dBrnC
mV p-p
mVrms
0
+32
-50
-58
0.01
0
0
0
Storage
Heat Dissipation
Audible Noise
%
%
<32
<250
<40
20 MHz bandwidth
ENVIRONMENTAL
Temperature
Operating
Temperature Coefficient
Humidity
Altitude
±0.5
± 10
after half hour warm-up
non-condensing
@54V
2 ft. from any vertical surface
+50
122
85
185
95
7000
2133
980
<65
°C
°F
°C
°F
V/°C
%
ft.
m
Btu/hr
dBa
PROTECTION, ALARM AND CONTROL SYSTEMS
Rectifier Failure Alarm (RFA)
Problems occurring because of an unacceptable relationship between the output power and load conditions will
cause a Rectifier Failure Alarm (RFA). This alarm consists
of a red LED. Conditions which may lead to an RFA are:
Low Current - Output current has decreased to below
2% of its rated value.
Unit Shutdown - Any shutdown occurrence due to
overvoltage, external shutdown command, unacceptable
ambient temperature conditions or low AC input voltage.
Fan Malfunction - The fan has stopped operating or is
not providing the airflow needed to cool the unit.
Over Temperature - The ambient temperature has
exceeded 50°C.
www.murata-ps.com
High Voltage Shutdown (HVSD)
The unit’s built-in high voltage limit is permanently set at
60.5VDC. When internal shutdown occurs, the unit may
be restarted by a local switch or by a remote signal.
Surge Protection
The unit will withstand lightning and input surges of
6000V/3000A.
Under Voltage Protection
When input voltage is below 106 VAC (with tolerance),
the rectifier’s operation is automatically inhibited.
Output Circuit Protection Device (Fuse)
The unit has one internal output protection fuse which is
in series with the -48VDC output.
Technical enquiries - email: [email protected], tel: +1 508 339 3000
Mechanical
SIDE
14.30
1.25
FRONT
4.95
+ .25
FAN
3.35
4.70
+ .25
4830
2.35
+ .25
4.35
+ .25
8.63
1st TEST BURN-IN
HI-POT
2nd TEST
QA
30
27
24
21
18
15
12
9
6
3
VOLTAGE PWR/RESET
FLT EQL
Standard Options are shown, consult factory for other available options.
www.murata-ps.com
Technical enquiries - email: [email protected], tel: +1 508 339 3000