Installation Instructions

SL POWER ELECTRONICS CORP.
6050 King Drive, Bldg. A
Ventura, CA 93003 + 805-486-4565
Internet: www.slpower.com
GPFM115 SERIES
INSTALLATION INSTRUCTIONS
MODEL NUMBERS: GPFM115-X-YYY-C G, where X represents the output voltage, which may be
any number from 3.3 through 48, -YYY is a value added option not related to Safety. May be followed
by optional Suffixes: ā€“C, when used, indicates optional cover/fan is provided, ā€œGā€ indicates compliance
with RoHS.
RATINGS:
Input: 100-240 V ac, 2.3 A, 50/60 Hz
Output:
20 A or 115 W maximum, with a minimum of 150 LFM without cover, or with suffix -C.
12 A or 80 W maximum, with no airflow and no cover.
Fan output is 12 V dc, 0.1 A (provided for connection of fan only)
Notes: 1.
2.
3.
Maximum ambient temperature for rated output power is 50 °C.
Maximum Operating Relative Humidity 96%, no condensation.
Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before
application of power.
CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of
UL 2601-1, CSA 22.2 No. 601.1, EN 60601-1, and IEC 60601-1.
CLASSIFICATION: (5.1) Protection against electric shock = Class I
(In accordance with subclause 5 of IEC 60601-1)
(5.2) Degree of protection against electric shock = Not acceptable for applied part without
additional isolation (contact factory for details)
(5.3) Protection against harmful ingress of water = Ordinary (no protection)
(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic mixture with
air, oxygen, or nitrous oxide. This evaluation is to be made on the end equipment by the OEM.
(5.6) Mode of operation = Continuous
SAFETY DECLARATION: SL Power Electronics. declares under our sole responsibility
that all models listed above are in conformity with the applicable requirements of EN60950
following the provisions of the Low Voltage Directive 2006/95/EC.
GROUNDING: Protection Class I requires that the ground terminal be bonded to Protective Earth in the
end application. Using this terminal for the primary system earthing terminal is not recommended.
OUTPUTS: Output common or return should be connected to Protective Earth in the end application.
The output is intended for Protectively Earthed Signal Output and Intermediate Circuits only. The
output is not acceptable for patient connection without additional isolation. The DC output is SELV
under normal and single fault conditions.
OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some
applications where an overvoltage condition could result in a hazard as defined in applicable safety
standards, redundant or additional overvoltage protection may be required. Consult factory for details.
CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary
circuits. The components providing isolation from primary to secondary cannot be tested while installed
in the power supply without overstressing basic (primary to ground) insulation. All isolating
components are individually 100 % tested at 4800 V ac prior to installation.
41-34735-0001 Rev. E 1/11/08
Page 1 of 2
GPFM115 SERIES INSTALLATION INSTRUCTIONS
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse is located in the phase lead only. EN 60601-1
requires that both supply leads (phase and neutral) be protected against overcurrent. Complete
overcurrent protection must be provided in the host equipment. Fuse ratings must not exceed that
specified for the internal fuse, must meet the requirements of EN 60601-1, and be acceptable for the
country in which the host equipment is to be installed.
WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit
component(s). Refer to fuse marking on the supply for rating. Repair must be performed by Condor
authorized personnel.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed
wiring traces and heatsinks.
EXPLANATION OF SYMBOLS
Alternating Current
Direct Current
Attention, Consult
Accompanying Documents
Attention, Dangerous Voltages
Earth (Ground)
CONNECTIONS
J1 Pin
1
3
5
AC Input
Line
Neutral
Ground
J3 Pin
1
2
3
4
5
6
7
8
DC Output
+ Output
+ Output
+ Output
+ Output
- Output
- Output
- Output
- Output
J2 Pin
1
2
3
4
DC Output
Power Fail
- Sense
+ Sense
Common
J4
2
1
12 V Fan Output
Fan Return
+ Fan
MATING CONNECTORS
J1 Amp 640250-5 Contact 770476-1
J2 Amp MTA-100 Receptacle
J3 Amp 640250-8 Contact 770476-1
J4 Amp MTA-100 Receptacle
CAUTION: Do not exceed 5 A per contact on J3.
SL Power Electronics will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or
repairs are carried out by other than authorized agents of SL Power Electronics, or b) the installation of the supply is not in accordance
with these installation instructions and the applicable UL, CSA, and EN/IEC safety standards.
41-34735-0001 Rev. E 1/11/08