Medical Linears Instructions

CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
MEDICAL LINEAR SERIES
INSTALLATION INSTRUCTIONS
RATINGS:
Input:
100/120/215/230-240 V ac, 50/60 Hz
Derate output current 10 % for operation at 50 Hz.
Refer to chassis marking for input current ratings.
Output:
See table on Page 2.
Notes:
1. Maximum ambient temperature for continuous output specified in the table is 50 °C.
2. Maximum Relative Humidity 96 %, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing
conditions before application of power.
SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole responsibility,
that all models listed above are in conformity with the applicable requirements of EN 60950 following
the provisions of the Low Voltage Directive 73/23/EEC. All models are Certified to be in compliance
with the applicable requirements of UL 60601-1, CSA 22.2 No. 601.1, and EN 60601-1 for Pollution
Degree 2 environment and Class I TN-S power systems.
CLASSIFICATION: (5.1)
(In accordance with sub- (5.2)
clause 5 of EN 60601-1) (5.3)
(5.5)
Protection against electric shock = Class I
Degree of protection against electric shock = Signal output or intermediate
Protection against harmful ingress of water = Ordinary (no protection)
Have not been evaluated for use in the presence of a flammable anaesthetic mixture with
air, oxygen, or nitrous oxide. This evaluation is to be made on the end equipment.
(5.6) Mode of operation = Continuous
GROUNDING: Protection Class I requires that the chassis be bonded to Protective Earth in the end application.
OUTPUTS: The output(s) are intended for Signal Input/Signal Output and Intermediate Circuits only. The output(s)
are not acceptable for patient connection without additional isolation. All DC outputs are SELV.
ISOLATION: The isolation voltage from primary to secondary is 4000 V ac. The creepage distance between primary
and secondary circuits is 12 mm minimum. The required creepage and clearance distances from primary circuits to
ground and secondary circuits must be maintained after installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in the applicable
safety standards, must not be exceeded after installation to preserve the intended safety. The output power, ambient air
temperature and the availability, amount, direction and/or restriction of airflow influence the temperatures of these
components.
OVERCURRENT PROTECTION: All models require external fusing to maintain the intended safety. Refer to
marking on chassis for maximum fuse ratings. EN 60601-1 requires that both supply leads (phase and neutral) be
protected against overcurrent.
WARNING! RISK OF FIRE! A blown secondary fuse may be an indication of catastrophic failure of circuit
component(s). Repair must be performed by Condor authorized personnel. Replace secondary fuses with Littelfuse 2AG
slo-blow type. Fuse values are marked on unit and are listed on page 2.
Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes,
modifications or repairs are carried out by other than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the
supply is not in accordance with these installation instructions and the applicable UL, CSA, EN/IEC safety standards.
41-31933-0001 Rev. H 09/20/05
Page 1
MEDICAL LINEAR SERIES
AC INPUT HOOKUP INSTRUCTIONS
1
1
1
EXPLANATION OF SYMBOLS
1
Alternating Current
Direct Current
2
100 VAC
3
2
120 VAC
3
2
215 VAC
3
230-240
VAC
2
Attention, Consult
Accompanying Documents
3
Attention, Dangerous Voltages
5
4
MODEL
5
4
5
4
5
4
Earth (Ground)
Maximum Output Ratings 50 °C Ambient
Secondary Fuse Rating
CSA
Level
SINGLE OUTPUT MODELS
MB12-1.7-A
MB15-1.5-A
MB24-1.2-A
MB28-1-A
MB5-3/OVP-A
MC12-3.4-A
MC15-3-A
MC24-2.4-A
MC28-2-A
MC5-6/OVP-A
MD12-6.8-A
MD15-6-A
MD24-4.8-A
MD28-4-A
MD5-12/OVP-A
MODEL
MAA15-0.8-A
MAA512-A
MAA524-A
MBB15-1.5-A
MBB512-A
MBB524-A
MCC15-3-A
MCC512-A
MCC524-A
12 V 1.7 A
15 V 1.5 A
24 V 1.2 A
28 V 1 A
5V3A
12 V 3.4 A
15 V 3 A
24 V 2.4 A
28 V 2 A
5V6A
12 V 6.8 A
15 V 6 A
24 V 4.8 A
28 V 4 A
5 V 12 A
F1=3.5 A/250 V
F1=3 A/250 V
F1=2.25 A/250 V
F1=2 A/250 V
F1,F3=4 A/125 V
F1,F3=4 A/125 V
F1,F3=3.5 A/250 V
F1,F2=2.25 A/250 V
F1=4 A/125 V
F1,F3=7 A/125 V
F1,F2,F5,F6=5 A/125 V
F1,F2,F5,F6=4 A/125 V
F1,F2=5 A/125 V
F1,F2=4 A/125 V
F1,F2,F5,F6=7 A/125 V
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
DUAL OUTPUT MODELS
Maximum Output Ratings 50 °C Ambient
CSA
Level
F4,F6=2.5 A/250 V
F1,F3=3 A/250 V; F4=1.5 A/250 V
F1,F3=3 A/250 V; F4=1 A/250 V
F4,F6=3.5 A/250 V
F1,F3=4 A/125 V; F4,F6=2 A/250 V
F1,F3=4A/125 V; F4,F6=1.5 A/250 V
F4,F6=7 A/125 V
F1,F3=7 A/125 V; F4,F6=3.5 A/250 V
F1,F3=4 A/125 V; F4,F6=3 A/250 V
±12 V 1 A or ±15 V 0.8 A; or -5 V 0.4 A
5 V 2 A; 9-15 V 0.5 A
5 V 2 A; 18-24 V 0.3 A
±12 V 1.7 A or ±15 V 1.5 A; or -5 V 0.7 A
5 V 3 A; 9-15 V 1.25 A
5 V 3 A; 18-24 V 0.8 A
±12 V 3.4 A or ±15 V 3 A; or -5 V 1.4 A
5 V 4 A; 9-15 V 2.5 A
5 V 4 A (6 A with 14 cfm airflow); 18-24 V 2 A
3
3
3
3
3
3
3
3
3
TRIPLE OUTPUT MODELS
MTAA-16W-A
MBAA40W-A
MCAA60W-A
MCBB75W-A
41-31933-0001 Rev. H 09/20/05
5 V 2 A; ±9 to 15 V 0.4 A; or -5 V 0.4 A
5 V 3 A; ±12 V 1 A or ±15 V 0.8 A; or -5 V 0.4 A
5 V 6 A; ±12 V 1 A or ±15 V 0.8 A; or -5 V 0.4 A
5 V 6 A; ±12 V 1.7 A or ±15 V 1.5 A; or -5 V 0.7 A
F1,F3=3 A/250 V; F4,F6=1 A/250 V
3
F1,F3=4 A/125 V; F4,F6=2.5 A/250 V
3
F1,F3=7 A/125 V; F4,F6=2 A/250 V
3
F1,F3=7 A/125 V; F4,F6=3.5 A/250 V
3
NOTE: All fuses are Littlefuse 2AG Slo-Blo type.