glm75 single output series installation instructions

CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
GLM75 SINGLE OUTPUT SERIES
INSTALLATION INSTRUCTIONS
MODEL NUMBERS: Model GLM75–X where X represents the output voltage, which may be any
number from 5 thru 28. Models may be followed by suffix –L for chassis bracket.
RATINGS:
Input:
100-240 V ac, 3.0 A, 50/60 Hz
Output: 5 thru 28 V, 20 thru 4 A
70 W maximum for output voltages from 5 thru 11 V with convection cooling
75 W maximum for output voltages from 12 thru 28 V with convection cooling
100 W maximum for output voltages from 5 thru 11 V with 26 CFM forced air cooling
110 W maximum for output voltages from 12 thru 28 V with 26 CFM forced air cooling
Notes:
1. Maximum operating ambient temperature is 50 °C.
2. Maximum Relative Humidity 96 %, no condensation.
3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before application of
power.
CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of
UL 2601-1 2nd Edition, CSA 22.2 No. 601.1-M90, EN 60601-1: 1990, and IEC 60601-1 (1988).
CLASSIFICATION:
(In accordance with
sub-clause 5
of IEC 60601-1)
(5.1) Protection against electric shock = Class I
(5.2) Degree of protection against electric shock = Signal output or intermediate
(5.3) Protection against harmful ingress of water = Ordinary (no protection)
(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic
mixture with air, oxygen, or nitrous oxide. This evaluation is to be made on the
end equipment by the OEM.
(5.6) Mode of operation = Continuous
SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole
responsibility that all models listed above are in conformity with the applicable requirements
of EN 60950 following the provisions of the Low Voltage Directive 73/23/EEC.
GROUNDING: The Earth (ground) terminal J1, pin 1, must be bonded to Protective Earth in the end
application to preserve the intended safety. Using the Earth terminal on the supply for grounding the end
product’s protective earthing terminal is not recommended. A separate dedicated protective earthing
point should be used.
OUTPUT: Output common should be connected to Protective Earth in the end application. The output
is intended for Protectively Earthed Signal Output and Intermediate Circuits only. The output is not
acceptable for patient connection without additional isolation. The DC output is SELV under normal
and single fault conditions.
OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some
applications where an overvoltage condition could result in a hazard as defined in applicable safety
standards, redundant or additional overvoltage protection may be required. Consult factory for details.
41-34470-0001 Rev. F
Page 1 of 2
CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary
circuits. The components providing isolation from primary to secondary cannot be tested while installed
in the power supply without overstressing basic (primary to ground) insulation. All isolating
components are individually 100 % tested at 4800 V ac prior to installation.
ISOLATION: The creepage distance between primary and ground is 4 mm minimum; between primary
and secondary circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled.
The output common is bypassed to ground using a 0.01 µF 1 kV capacitor. The required creepage and
clearance distances from primary circuits to ground and secondary circuits must be maintained after
installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse is located in the phase lead only. UL 2601-1,
CSA 22.2 No. 601.1, EN 60601-1, and IEC 60601-1 requires that both supply leads (phase and neutral)
be protected against overcurrent except for permanently installed equipment. Complete overcurrent
protection must be provided in the end equipment. Fuse ratings must not exceed that specified for the
internal fuse, must be acceptable for the country in which the end equipment is to be installed.
WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit
component(s). Repair must be performed by Condor authorized personnel. Refer to fuse marking on the
supply for rating.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, and printed
wiring traces.
EXPLANATION OF SYMBOLS
J1 Pin
1
3
5
AC Input
Ground
Neutral
Line
J2 Pin
1
2
3
4
5
DC Output
+ Output
+ Output
+ Output
+ Output
- Output
J2 Pin
6
7
8
9
MATING CONNECTORS
J1 Amp Housing 640250-5 Pin 770522-1
J2 Amp Housing 640250-9 Pin 770522-1
DC Output
- Output
- Output
- Output
Power Fail
Alternating Current
Direct Current
Attention, Consult
Accompanying Documents
Attention, Dangerous Voltages
Earth (Ground)
CAUTION: Do not exceed 5 A per contact.
Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or
repairs are carried out by other than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the supply is not in accordance with these
installation instructions and the applicable UL, CSA, and EN/IEC safety standards.
41-34470-0001 Rev. F
Page 2 of 2