Safety I/O Terminals DST1 Series CSM_DST1 Series_DS_E_7_3 Distributed Safety Terminals That Reduce Wiring. • Lineup includes four models to accommodate various I/O types and number of I/O points. • Monitor the safety system from Standard Controllers across the network. • EN954-1 (Cat.4), ISO13849-1 (PLe), and IEC 61508 SIL3 certification. • The DST1-XD0808SL-1 also supports logic operation functions for high-speed processing in applications requiring partial stopping of the safety system. Ordering Information List of Models Name No. of I/O points Model Safety inputs: 12, test outputs: 4 Safety I/O Terminals DST1-ID12SL-1 Safety inputs: 8, safety outputs (semiconductor): 8, test outputs: 4 Safety inputs: 4, safety outputs (relay): 4, test outputs: 4 DST1-MD16SL-1 DST1-XD0808SL-1 * DST1-MRD08SL-1 Note: The standard DS1T Safety I/O Terminals are equipped with spring-cage terminal blocks, but screw terminal blocks are available if desired, e.g., to replace previous terminals. Refer to DeviceNet Safety Accessories. *Use the Network Configurator Ver. 2.0 or later to make DST1-XD0808SL-1 settings. Specifications Certified Standards Certification body Specifications NFPA 79-2012 EN ISO 13849-1:2008 IEC61131-2: 2007 EN ISO13849-2: 2012 EN61000-6-4: 2007 TÜV Rheinland EN61000-6-2: 2005 EN60204-1: 2006 ISO 13850:2006 (EN418:1992) ANSI RIA15.06-1999 ANSI B11.19-2010 UL Model Standard UL508 ANSI/ISA 12.12.01 (excluding the DST1-MRD08SL-1) UL1998 NFPA79 IEC61508 CSA22.2 No.142 CSA22.2 No.213 (excluding the DST1-MRD08SL-1) Item DST1ID12SL-1 DST1MD16SL-1 DST1MRD08SL-1 DST1XD0808SL-1 Communications power supply voltage 11 to 25 VDC supplied via communications connector I/O power supply voltage 20.4 to 26.4 VDC (24 VDC −15%/+10%) Current consumption Communications 24 VDC power 100 mA supply 24 VDC 110 mA 24 VDC 100 mA 24 VDC 110 mA I/O power supply * 24 VDC 50 mA (Input) 130 mA (Output) 24 VDC 80 mA (Input) 130 mA (Output) 24 VDC 50 mA (Input) 130 mA (Output) 24 VDC 70 mA Overvoltage category II Noise immunity Conforms to IEC61131-2. Vibration resistance 10 to 57 Hz: 0.35-mm single amplitude, 57 to 150 Hz: 50 m/s2 Shock resistance 150 m/s2, 11 ms Mounting method 35-mm DIN Track Ambient operating temperature −10 to 55°C Ambient operating humidity 10% to 95% (with no condensation) Ambient storage temperature −40 to 70°C Degree of protection IP20 Weight 420 g 100 m/s2, 11 ms 150 m/s2, 11 ms 10% to 85% 10% to 95% (with no (with no condensation) condensation) 600 g 420 g *Not including power consumption for external devices. 1 DST1 Series Safety Input Specifications Safety Output Specifications (Relay Output) (Common with the DST1 Series) Input type Sinking inputs (PNP) ON voltage 11 VDC min. OFF voltage 5 VDC max. OFF current Input current (DST1-MRD08SL-1) Applicable relays G7SA-2A2B, EN50205 Class A 1 mA max. Failure rate P level * (Reference value) 5 VDC, 1 mA 6 mA Rated load (resistive) 2 A at 240 VAC, 2 A at 30 VDC Safety Output Specifications (Semiconductor output) Durability (Common with the DST1-MD16SL-1/XD0808SL-1) Output type 1.2 V max. 0.1 mA max. Electrical 100,000 operations min. (at 1,800 operations/h with a resistive load) CIP Safety on DeviceNet Communications Rated output current 0.5 A max./output Leakage current 5,000,000 operations min. (at 7,200 operations/h) *This value is equivalent to 300 operations/minute. Sourcing outputs (PNP) ON residual voltage Mechanical Safety Slave communications Max. 4 connections (Max. 2 connections for the DST1-XD0808SL-1) Test Output Specifications DeviceNet Slave Communications (Common with the DST1 Series) (Common with the DST1 Series) Output type Standard Slave communications Sourcing outputs (PNP) Rated output current 0.7 A max./output ON residual voltage 1.2 V max. Leakage current 0.1 mA max. Max. 2 connections Internal Circuit Configuration DST1-ID12SL-1 DC-DC Converter (Non-insulated) Internal Circuits DeviceNet Physical Layer V+ CAN H Shield CAN L 1 V 11 G Terminal No. Name Safety Input Circuit (Sink input) Input Power Supply Circuit V− 2 V 12 G 3 4 5 6 7 8 9 IN0 IN1 IN2 IN3 IN4 IN5 IN6 13 T0 14 T1 15 T0 16 T1 17 T0 18 T1 19 T0 10 IN7 20 T1 Test Output Circuit (Source output) 21 IN8 31 T0 22 IN9 32 T1 23 IN10 33 T0 24 IN11 34 T1 25 T2 35 G 26 T2 36 G 27 T2 37 G 28 T3 38 G 29 T3 39 G 30 T3 40 G Function 1, 2 V 11, 12 G 35 to 40 G Common terminal (Terminal No. 11, 12 and 35 to 40 are internally connected.) 3 to 10 21 to 24 IN0 to IN11 Safety input terminal 13 to 20 25 to 30 31 to 34 T0 to T3 Test output terminal Power supply terminal (24 VDC) for input device and test output 2 DST1 Series DST1-MD16SL-1 DC-DC Converter (Non-insulated) DST1-XD0808SL-1 Internal Circuits DeviceNet Physical Layer V+ CAN H Shield CAN L Input Power Supply Circuit V− 1 2 V0 V0 11 12 G0 Terminal No. Name G0 Test Output Circuit (Source output) Safety Input Circuit (Sink input) 3 IN0 13 T0 4 5 IN1 14 IN2 15 T1 T0 6 7 IN3 16 IN4 17 T1 T0 8 IN5 18 T1 9 IN6 19 T2 10 IN7 20 T3 Output Power Supply Circuit 21 V1 31 G1 22 V1 32 G1 Safety Output Circuit (Source output) 23 OUT0 33 G1 24 OUT1 34 G1 25 OUT2 35 G1 26 OUT3 36 G1 27 OUT4 37 G1 28 OUT5 38 G1 29 OUT6 39 G1 30 OUT7 40 G1 Function 1, 2 V0 11, 12 G0 Power supply terminal (24 VDC) for input device and test output 3 to 10 IN0 to IN7 Safety input terminal 13 to 20 T0 to T3 Test output terminal 21, 22 V1 31, 32 G1 23 to 30 OUT0 to OUT7 Safety output terminal 33 to 40 G1 Power supply terminal (24 VDC) for output device Common terminal (Terminal Nos. 31 to 40 are internally connected.) DST1-MRD08SL-1 DC-DC Converter (Non-insulated) Internal Circuits CAN H Shield CAN L DeviceNet Physical Layer V+ V− 1 V0 11 G0 Terminal No. Name 2 V0 12 G0 3 IN0 13 T0 4 14 IN2 15 T1 T0 6 IN3 16 T1 7 T2 17 G0 8 T2 18 G0 9 T3 19 G0 10 T3 20 G0 Ry0 Output Power Supply Circuit 21 V1 31 G1 22 V1 32 G1 23 OUT0 33 C0 24 OUT0e 34 C0e Ry1 25 OUT1 35 C1 26 OUT1e 36 C1e Ry2 27 OUT2 37 C2 28 OUT2e 38 C2e Ry3 29 OUT3 39 C3 30 OUT3e 40 C3e Function V0 11, 12 G0 17 to 20 G0 Common terminal (Terminal Nos. 11, 12 and 17 to 20 are internally connected.) 3 to 6 IN0 to IN3 Safety input terminal 7 to 10 13 to 16 T0 to T3 Test output terminal 21, 22 V1 31, 32 G1 Power supply terminal (24 VDC) for driving the safety relay of the internal circuit OUT0 to OUT3 C0 to C3 OUT0e to OUT3e C0e to C3e 5 IN1 1, 2 23 to 30 33 to 40 Test Output Circuit (Source output) Safety Input Circuit (Sink input) Input Power Supply Circuit Power supply terminal (24 VDC) for input device, test output, and monitoring the safety relay NC contact of the internal circuit Safety output terminal (The outputs of terminal No. 23/33 (OUT0) and 24/ 34 (OUT0e) are the same.) (The outputs of terminal No. 25/35 (OUT1) and 26/ 36 (OUT1e) are the same.) (The outputs of terminal No. 27/37 (OUT2) and 28/ 38 (OUT2e) are the same.) (The outputs of terminal No. 29/39 (OUT3) and 30/ 40 (OUT3e) are the same.) Refer to the CIP Safety on DeviceNet DST1-series Safety I/O Terminals Operation Manual (Cat. No. Z904) for wiring examples. 3 DST1 Series Dimensions (Unit: mm) DST1-ID12SL-1 DST1-MD16SL-1 DST1-XD0808SL-1 (68.15) 65 35.5 170 42.75 71.4 DST1-MRD08SL-1 35.5 (94.7) 90 63 170 83.2 Safety Precautions Refer to the "Safety Precautions for All CIP Safety on DeviceNet Systems" for precautions. Be sure to read the following user's manual for other details required for correct use of the Safety I/O Terminals Safety I/O Terminals User's Manual (Cat. No. Z904) 4 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2013.12 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2013 All Right Reserved.