DST1 Series - OMRON Industrial Automation

Safety I/O Terminals
DST1 Series
CSM_DST1 Series_DS_E_7_3
Distributed Safety Terminals That
Reduce Wiring.
• Lineup includes four models to accommodate various
I/O types and number of I/O points.
• Monitor the safety system from Standard Controllers
across the network.
• EN954-1 (Cat.4), ISO13849-1 (PLe), and
IEC 61508 SIL3 certification.
• The DST1-XD0808SL-1 also supports logic operation
functions for high-speed processing in applications
requiring partial stopping of the safety system.
Ordering Information
List of Models
Name
No. of I/O points
Model
Safety inputs: 12, test outputs: 4
Safety I/O Terminals
DST1-ID12SL-1
Safety inputs: 8, safety outputs (semiconductor): 8, test outputs: 4
Safety inputs: 4, safety outputs (relay): 4, test outputs: 4
DST1-MD16SL-1
DST1-XD0808SL-1 *
DST1-MRD08SL-1
Note: The standard DS1T Safety I/O Terminals are equipped with spring-cage terminal blocks, but screw terminal blocks are available if desired,
e.g., to replace previous terminals. Refer to DeviceNet Safety Accessories.
*Use the Network Configurator Ver. 2.0 or later to make DST1-XD0808SL-1 settings.
Specifications
Certified Standards
Certification
body
Specifications
NFPA 79-2012
EN ISO 13849-1:2008
IEC61131-2: 2007
EN ISO13849-2: 2012
EN61000-6-4: 2007
TÜV Rheinland
EN61000-6-2: 2005
EN60204-1: 2006
ISO 13850:2006 (EN418:1992)
ANSI RIA15.06-1999
ANSI B11.19-2010
UL
Model
Standard
UL508
ANSI/ISA 12.12.01 (excluding the DST1-MRD08SL-1)
UL1998
NFPA79
IEC61508
CSA22.2 No.142
CSA22.2 No.213 (excluding the DST1-MRD08SL-1)
Item
DST1ID12SL-1
DST1MD16SL-1
DST1MRD08SL-1
DST1XD0808SL-1
Communications
power supply
voltage
11 to 25 VDC supplied via communications connector
I/O power supply
voltage
20.4 to 26.4 VDC (24 VDC −15%/+10%)
Current
consumption
Communications 24 VDC
power
100 mA
supply
24 VDC
110 mA
24 VDC
100 mA
24 VDC
110 mA
I/O
power
supply *
24 VDC
50 mA
(Input)
130 mA
(Output)
24 VDC
80 mA
(Input)
130 mA
(Output)
24 VDC
50 mA
(Input)
130 mA
(Output)
24 VDC
70 mA
Overvoltage
category
II
Noise immunity
Conforms to IEC61131-2.
Vibration
resistance
10 to 57 Hz: 0.35-mm single amplitude, 57 to 150 Hz:
50 m/s2
Shock resistance
150 m/s2, 11 ms
Mounting method
35-mm DIN Track
Ambient operating
temperature
−10 to 55°C
Ambient operating
humidity
10% to 95% (with no
condensation)
Ambient storage
temperature
−40 to 70°C
Degree of protection
IP20
Weight
420 g
100 m/s2,
11 ms
150 m/s2,
11 ms
10% to 85%
10% to 95%
(with no
(with no
condensation) condensation)
600 g
420 g
*Not including power consumption for external devices.
1
DST1 Series
Safety Input Specifications
Safety Output Specifications
(Relay Output)
(Common with the DST1 Series)
Input type
Sinking inputs (PNP)
ON voltage
11 VDC min.
OFF voltage
5 VDC max.
OFF current
Input current
(DST1-MRD08SL-1)
Applicable relays
G7SA-2A2B, EN50205 Class A
1 mA max.
Failure rate P level *
(Reference value)
5 VDC, 1 mA
6 mA
Rated load (resistive) 2 A at 240 VAC, 2 A at 30 VDC
Safety Output Specifications
(Semiconductor output)
Durability
(Common with the DST1-MD16SL-1/XD0808SL-1)
Output type
1.2 V max.
0.1 mA max.
Electrical
100,000 operations min.
(at 1,800 operations/h with a resistive load)
CIP Safety on DeviceNet Communications
Rated output current 0.5 A max./output
Leakage current
5,000,000 operations min.
(at 7,200 operations/h)
*This value is equivalent to 300 operations/minute.
Sourcing outputs (PNP)
ON residual voltage
Mechanical
Safety Slave
communications
Max. 4 connections
(Max. 2 connections for the DST1-XD0808SL-1)
Test Output Specifications
DeviceNet Slave Communications
(Common with the DST1 Series)
(Common with the DST1 Series)
Output type
Standard Slave
communications
Sourcing outputs (PNP)
Rated output current 0.7 A max./output
ON residual voltage
1.2 V max.
Leakage current
0.1 mA max.
Max. 2 connections
Internal Circuit Configuration
DST1-ID12SL-1
DC-DC Converter
(Non-insulated)
Internal Circuits
DeviceNet
Physical Layer
V+
CAN H
Shield
CAN L
1
V
11
G
Terminal
No.
Name
Safety Input Circuit
(Sink input)
Input Power
Supply Circuit
V−
2
V
12
G
3
4
5
6
7
8
9
IN0
IN1
IN2
IN3
IN4
IN5
IN6
13
T0
14
T1
15
T0
16
T1
17
T0
18
T1
19
T0
10
IN7
20
T1
Test Output Circuit
(Source output)
21
IN8
31
T0
22
IN9
32
T1
23
IN10
33
T0
24
IN11
34
T1
25
T2
35
G
26
T2
36
G
27
T2
37
G
28
T3
38
G
29
T3
39
G
30
T3
40
G
Function
1, 2
V
11, 12
G
35 to 40
G
Common terminal
(Terminal No. 11, 12 and 35 to
40 are internally connected.)
3 to 10
21 to 24
IN0 to
IN11
Safety input terminal
13 to 20
25 to 30
31 to 34
T0 to T3
Test output terminal
Power supply terminal (24 VDC)
for input device and test output
2
DST1 Series
DST1-MD16SL-1
DC-DC Converter
(Non-insulated)
DST1-XD0808SL-1
Internal Circuits
DeviceNet
Physical Layer
V+
CAN H
Shield
CAN L
Input Power
Supply Circuit
V−
1
2
V0
V0
11
12
G0
Terminal
No.
Name
G0
Test Output
Circuit
(Source output)
Safety Input Circuit
(Sink input)
3
IN0
13
T0
4
5
IN1
14
IN2
15
T1
T0
6
7
IN3
16
IN4
17
T1
T0
8
IN5
18
T1
9
IN6
19
T2
10
IN7
20
T3
Output Power
Supply Circuit
21
V1
31
G1
22
V1
32
G1
Safety Output Circuit
(Source output)
23
OUT0
33
G1
24
OUT1
34
G1
25
OUT2
35
G1
26
OUT3
36
G1
27
OUT4
37
G1
28
OUT5
38
G1
29
OUT6
39
G1
30
OUT7
40
G1
Function
1, 2
V0
11, 12
G0
Power supply terminal (24 VDC) for input device
and test output
3 to 10
IN0 to IN7
Safety input terminal
13 to 20
T0 to T3
Test output terminal
21, 22
V1
31, 32
G1
23 to 30
OUT0 to OUT7 Safety output terminal
33 to 40
G1
Power supply terminal (24 VDC) for output device
Common terminal
(Terminal Nos. 31 to 40 are internally connected.)
DST1-MRD08SL-1
DC-DC Converter
(Non-insulated)
Internal Circuits
CAN H
Shield
CAN L
DeviceNet
Physical Layer
V+
V−
1
V0
11
G0
Terminal
No.
Name
2
V0
12
G0
3
IN0
13
T0
4
14
IN2
15
T1
T0
6
IN3
16
T1
7
T2
17
G0
8
T2
18
G0
9
T3
19
G0
10
T3
20
G0
Ry0
Output Power
Supply Circuit
21
V1
31
G1
22
V1
32
G1
23
OUT0
33
C0
24
OUT0e
34
C0e
Ry1
25
OUT1
35
C1
26
OUT1e
36
C1e
Ry2
27
OUT2
37
C2
28
OUT2e
38
C2e
Ry3
29
OUT3
39
C3
30
OUT3e
40
C3e
Function
V0
11, 12
G0
17 to 20
G0
Common terminal
(Terminal Nos. 11, 12 and 17 to 20 are internally
connected.)
3 to 6
IN0 to IN3
Safety input terminal
7 to 10
13 to 16
T0 to T3
Test output terminal
21, 22
V1
31, 32
G1
Power supply terminal (24 VDC) for driving the
safety relay of the internal circuit
OUT0 to OUT3
C0 to C3
OUT0e to
OUT3e
C0e to C3e
5
IN1
1, 2
23 to 30
33 to 40
Test Output
Circuit
(Source output)
Safety Input Circuit
(Sink input)
Input Power
Supply Circuit
Power supply terminal (24 VDC) for input device,
test output, and monitoring the safety relay NC
contact of the internal circuit
Safety output terminal
(The outputs of terminal No. 23/33 (OUT0) and 24/
34 (OUT0e) are the same.)
(The outputs of terminal No. 25/35 (OUT1) and 26/
36 (OUT1e) are the same.)
(The outputs of terminal No. 27/37 (OUT2) and 28/
38 (OUT2e) are the same.)
(The outputs of terminal No. 29/39 (OUT3) and 30/
40 (OUT3e) are the same.)
Refer to the CIP Safety on DeviceNet DST1-series Safety I/O
Terminals Operation Manual (Cat. No. Z904) for wiring examples.
3
DST1 Series
Dimensions
(Unit: mm)
DST1-ID12SL-1
DST1-MD16SL-1
DST1-XD0808SL-1
(68.15) 65
35.5
170
42.75
71.4
DST1-MRD08SL-1
35.5
(94.7) 90
63
170
83.2
Safety Precautions
Refer to the "Safety Precautions for All CIP Safety on DeviceNet Systems" for precautions.
Be sure to read the following user's manual for other details required for correct use of the Safety I/O
Terminals
Safety I/O Terminals User's Manual (Cat. No. Z904)
4
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2013.12
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2013 All Right Reserved.