Features Unregulated Converters ● ● ● ● ● ● ● UL/CSA and EN Safety certified EN-61010 for Test, Measurement and Lab Use EN-60601 for Medical Applications Reinforced Isolation 6.4kVDC or 8kVDC Optional Continuous Short Circuit Protected Unique Reinforced Isolation Transformer System /X2 Option for >9mm Input/Output Clearance ECONOLINE DC/DC-Converter with 3 year Warranty The RxxPxxS_D Series of DC/DC Converters are certified to UL/CSA-60950. This makes them ideal for safety applications where approved or reinforced isolation is required. The reinforced versions are also EN61010-1 certified for Lab Equipment Safety. Description 1 Watt SIP 7 Single & Dual Output Selection Guide Part Number SIP 7 Reinforced Isolation (kVDC) Input Voltage (VDC) Output Voltage (VDC) Output Current (mA) Efficiency Std (%) Max Capacitive Load(1) RxxP3.3S* /R6.4 & /R8 5, 9, 12, 15, 24 3.3 303 70~80 2200µF RxxP05S* /R6.4 & /R8 5, 9, 12, 15, 24 5 200 75-80 1000µF RxxP09S* /R6.4 & /R8 5, 9, 12, 15, 24 9 111 75-82 1000µF RxxP12S* /R6.4 & /R8 5, 9, 12, 15, 24 12 84 75-82 470µF RxxP15S* /R6.4 & /R8 5, 9, 12, 15, 24 15 66 75-83 470µF RxxP3.3D* /R6.4 & /R8 5, 9, 12, 15, 24 ±3.3 ±151 72-79 ±1000µF RxxP05D* /R6.4 & /R8 5, 9, 12, 15, 24 ±5 ±100 75-82 ±470µF RxxP09D* /R6.4 & /R8 5, 9, 12, 15, 24 ±9 ±55 75-82 ±470µF RxxP12D* /R6.4 & /R8 5, 9, 12, 15, 24 ±12 ±41 75-82 ±220µF RxxP15D* /R6.4 & /R8 5, 9, 12, 15, 24 ±15 ±33 75-83 ±220µF xx = Input Voltage. Other input and output voltage combinations available on request. * add Suffix “P” for Continuous Short Circuit Protection, e.g. R05P05S/P, R05P05D/P * add Suffix “/X2” for single output with alternative pinout, e.g. R05P05S/X2, R05P05S/P/X2 * add Suffix “/R6.4” or “/R8” for Reinforced Isolation, e.g. R05P05D/R6.4, R05P05S/P/X2/R8 RoHS 2011/65/EU 6/6 E314885 EN-60950-1 Certified EN-60601-1 Certified UL/CSA 60950-1 Certified UL-60601-1 Certified EN-61010-1 Certified IEC-60601-1 CB Report Specifications (measured at TA = 25°C, nominal input voltage, full load and after warm-up) Input Voltage Range ±10% Output Voltage Accuracy ±5% 1.2%/1% of Vin typ. Load Voltage Regulation 3.3, 5V output types 15% max. (10% to 100% full load) other output types 10% max. Output Ripple and Noise (20MHz BW) 200mVp-p max. Operating Frequency 20kHz min. / 50kHz typ. / 85kHz max. Efficiency at Full Load 65% min. / 75% typ. Minimum Load = 0% Specifications valid for 10% minimum load only. Reinforced Isolation /R6.4 Reinforced Isolation /R8 (tested for 1 second) 6400VDC (rated for 1 minute**) 3200VAC / 60Hz (tested for 1 second) 8000VDC (rated for 1 minute**) 4000VAC / 60Hz Isolation Capacitance 4pF min. / 10pF max. Isolation Resistance 15 GΩ min. Short Circuit Protection 1 Second P-Suffix Operating Temperature Range (free air convection) Continuous -40°C to +85°C (see Graph) Case Temperature Storage Temperature Range (Ambient Temperature) 100 80 60 40 Safe Operating Area 20 0 -40 0 50 85 Operating Temperature °C 100 150 105°C max. -55°C to +125°C Relative Humidity 95% RH Package Weight 4.3g Packing Quantity 25 pcs per Tube continued on next page www.recom-power.com Derating-Graph Output Power (%) Line Voltage Regulation RxxPxx/R REV: 1/2015 **Any data referred to in this datasheet are of indicative nature and based on our practical experience only. For further details, please refer to our Application Notes. Refer to Application Notes E-73 RxxPxxS_D /Rx Series ECONOLINE DC/DC-Converter Specifications (measured at TA = 25°C, nominal input voltage, full load and after warm-up)) Potting Material MTBF (+25°C) (+85°C) Silicone Rubber Compound (UL94V-0) } Detailed Information see Application Notes chapter "MTBF" using MIL-HDBK 217F 2974 x 103 hours using MIL-HDBK 217F 728 x 103 hours Reinforced Isolation Transformer Clearance Reinforced Types 5.5 mm min. PCB Creepage & Clearance Reinforced Types 4.6 mm min. Certifications Measurement, Control and Laboratory Use Safety Report: T1301251-313 EN61010-1 : 2010 CSA General Safety Report: 2207629 UL 60950-1 1st Ed. UL/cUL Medical Safety Report: E314885-A5 CSA Medical Safety Report: 2207629 EN General Safety Report: SPCLVD1310079-1 CB/EN Medical Safety Report: CA-10169-A1-UL ANSI/AAMI Medical Safety Report: E314885-A5 C22.2 No. 60950-1-03 Notes Note 1 UL60601-1 1st Edition CAN/CSA-22.2 No 601.1-M90 EN60950-1 : 2006 IEC/EN 60601-1 3rd Edition ES60601-1 3rd Edition Maximum capacitive load is defined as the capacitive load that will allow start up in under 1 second without damage to the converter. Tolerance Envelope +10% Typical L o +5% +5% ad Line V Nom. 1.5% RxxPxx/R Output Voltage 5% 10% 50% 100% Output Load Current (%) Typical Characteristics - Reinforced Version RxxP05S/R6.4 RxxP05S/R8 Efficiency / Load Deviation / Load 100 80 25.000 R05P05S/R6.4 20.000 Deviation from Nominal (%) R12P05S/R6.4 60 R24P05S/R6.4 Efficiency % 40 20 0 0% 20% 40% 60% 80% 100% 15.000 10.000 5.000 0.000 -5.000 -10.000 Total Output current (%) E-74 R12P05S/R6.4 R24P05S/R6.4 REV: 1/2015 R05P05S/R6.4 0% 20% 40% 60% Total Output current (%) 80% 100% www.recom-power.com RxxPxxS_D /Rx Series ECONOLINE DC/DC-Converter Typical Characteristics - Reinforced Version RxxP05D/R6.4 RxxP05D/R8 Efficiency / Load Deviation / Load 100 R05P05D/R6.4 20.000 Deviation from Nominal (%) R12P05D/R6.4 80 25.000 60 Efficiency % 40 R24P05D/R6.4 20 0 0% 20% 40% 60% 80% 100% R12P05D/R6.4 15.000 R24P05D/R6.4 10.000 5.000 0.000 -5.000 -10.000 Total Output current (%) R05P05D/R6.4 0% 40% 20% 60% Total Output current (%) 80% 100% Package Style and Pinning (mm) 7 PIN SIP Package 12.5 RECOM R05P05D/R6.4 or R05P05D/R8 5 tc **** 5 4.1 7.62 0.5 0.5 pin clearance Bottom View RECOM RxxPxxS/R8 **** RECOM RxxPxxS/X2/R6.4 **** 5 6 7 1 2 5 7 1 2 6 7 Pin Connections 15.24 2.54 /X2 Bottom View RECOM RxxPxxD/R6.4 **** 1.00ø+0.15/0 0.25 Top View 1.00ø+0.15/0 2.54 19.5 Single Output Recommended Footprint Details 2.4 1.9 Single Output 1 2 2.54 19.5 Dual Output RxxPxx/R 9.8 Pin # 1 2 5 6 7 Single +Vin -Vin –Vout No Pin +Vout Dual +Vin –Vin –Vout Com +Vout /X2 +Vin –Vin No Pin –Vout +Vout XX.X ± 0.5 mm XX.XX ± 0.25 mm 0.25 2.4 1.9 10.16 pin clearance 2.54 /X2 Top View The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit written consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications. www.recom-power.com REV: 1/2015 E-75