RxxPxx/R - recom

Features
Unregulated
Converters
●
●
●
●
●
●
●
UL/CSA and EN Safety certified
EN-61010 for Test, Measurement and Lab Use
EN-60601 for Medical Applications
Reinforced Isolation 6.4kVDC or 8kVDC
Optional Continuous Short Circuit Protected
Unique Reinforced Isolation Transformer System
/X2 Option for >9mm Input/Output Clearance
ECONOLINE
DC/DC-Converter
with 3 year Warranty
The RxxPxxS_D Series of DC/DC Converters are certified to UL/CSA-60950. This makes
them ideal for safety applications where approved or reinforced isolation is required. The
reinforced versions are also EN61010-1 certified for Lab Equipment Safety.
Description
1 Watt
SIP 7 Single
& Dual Output
Selection Guide
Part
Number
SIP 7
Reinforced
Isolation
(kVDC)
Input
Voltage
(VDC)
Output
Voltage
(VDC)
Output
Current
(mA)
Efficiency
Std
(%)
Max
Capacitive
Load(1)
RxxP3.3S*
/R6.4 & /R8
5, 9, 12, 15, 24
3.3
303
70~80
2200µF
RxxP05S*
/R6.4 & /R8
5, 9, 12, 15, 24
5
200
75-80
1000µF
RxxP09S*
/R6.4 & /R8
5, 9, 12, 15, 24
9
111
75-82
1000µF
RxxP12S*
/R6.4 & /R8
5, 9, 12, 15, 24
12
84
75-82
470µF
RxxP15S*
/R6.4 & /R8
5, 9, 12, 15, 24
15
66
75-83
470µF
RxxP3.3D*
/R6.4 & /R8
5, 9, 12, 15, 24
±3.3
±151
72-79
±1000µF
RxxP05D*
/R6.4 & /R8
5, 9, 12, 15, 24
±5
±100
75-82
±470µF
RxxP09D*
/R6.4 & /R8
5, 9, 12, 15, 24
±9
±55
75-82
±470µF
RxxP12D*
/R6.4 & /R8
5, 9, 12, 15, 24
±12
±41
75-82
±220µF
RxxP15D*
/R6.4 & /R8
5, 9, 12, 15, 24
±15
±33
75-83
±220µF
xx = Input Voltage. Other input and output voltage combinations available on request.
* add Suffix “P” for Continuous Short Circuit Protection, e.g. R05P05S/P, R05P05D/P
* add Suffix “/X2” for single output with alternative pinout, e.g. R05P05S/X2, R05P05S/P/X2
* add Suffix “/R6.4” or “/R8” for Reinforced Isolation, e.g. R05P05D/R6.4, R05P05S/P/X2/R8
RoHS
2011/65/EU
6/6
E314885
EN-60950-1 Certified
EN-60601-1 Certified
UL/CSA 60950-1 Certified
UL-60601-1 Certified
EN-61010-1 Certified
IEC-60601-1 CB Report
Specifications (measured at TA = 25°C, nominal input voltage, full load and after warm-up)
Input Voltage Range
±10%
Output Voltage Accuracy
±5%
1.2%/1% of Vin typ.
Load Voltage Regulation
3.3, 5V output types
15% max.
(10% to 100% full load)
other output types
10% max.
Output Ripple and Noise (20MHz BW)
200mVp-p max.
Operating Frequency
20kHz min. / 50kHz typ. / 85kHz max.
Efficiency at Full Load
65% min. / 75% typ.
Minimum Load = 0%
Specifications valid for 10% minimum load only.
Reinforced Isolation /R6.4
Reinforced Isolation /R8
(tested for 1 second)
6400VDC
(rated for 1 minute**)
3200VAC / 60Hz
(tested for 1 second)
8000VDC
(rated for 1 minute**)
4000VAC / 60Hz
Isolation Capacitance
4pF min. / 10pF max.
Isolation Resistance
15 GΩ min.
Short Circuit Protection
1 Second
P-Suffix
Operating Temperature Range (free air convection)
Continuous
-40°C to +85°C (see Graph)
Case Temperature
Storage Temperature Range
(Ambient Temperature)
100
80
60
40
Safe Operating Area
20
0
-40
0
50
85
Operating Temperature °C
100
150
105°C max.
-55°C to +125°C
Relative Humidity
95% RH
Package Weight
4.3g
Packing Quantity
25 pcs per Tube
continued on next page
www.recom-power.com
Derating-Graph
Output Power (%)
Line Voltage Regulation
RxxPxx/R
REV: 1/2015
**Any data referred to in this datasheet are of indicative
nature and based on our practical experience only. For
further details, please refer to our Application Notes.
Refer to Application Notes
E-73
RxxPxxS_D
/Rx Series
ECONOLINE
DC/DC-Converter
Specifications (measured at TA = 25°C, nominal input voltage, full load and after warm-up))
Potting Material
MTBF (+25°C)
(+85°C)
Silicone Rubber Compound (UL94V-0)
}
Detailed Information see
Application Notes chapter "MTBF"
using MIL-HDBK 217F
2974 x 103 hours
using MIL-HDBK 217F
728 x 103 hours
Reinforced Isolation
Transformer Clearance
Reinforced Types
5.5 mm min.
PCB Creepage & Clearance
Reinforced Types
4.6 mm min.
Certifications
Measurement, Control and Laboratory Use Safety
Report: T1301251-313
EN61010-1 : 2010
CSA General Safety
Report: 2207629
UL 60950-1 1st Ed.
UL/cUL Medical Safety
Report: E314885-A5
CSA Medical Safety
Report: 2207629
EN General Safety
Report: SPCLVD1310079-1
CB/EN Medical Safety
Report: CA-10169-A1-UL
ANSI/AAMI Medical Safety
Report: E314885-A5
C22.2 No. 60950-1-03
Notes
Note 1
UL60601-1 1st Edition
CAN/CSA-22.2 No 601.1-M90
EN60950-1 : 2006
IEC/EN 60601-1 3rd Edition
ES60601-1 3rd Edition
Maximum capacitive load is defined as the capacitive load that will allow start up in under 1 second without damage to the converter.
Tolerance Envelope
+10%
Typical L
o
+5%
+5%
ad Line
V Nom.
– 1.5%
RxxPxx/R
Output Voltage
– 5%
10%
50%
100%
Output Load Current (%)
Typical Characteristics - Reinforced Version
RxxP05S/R6.4
RxxP05S/R8
Efficiency / Load
Deviation / Load
100
80
25.000
R05P05S/R6.4
20.000
Deviation from Nominal (%)
R12P05S/R6.4
60
R24P05S/R6.4
Efficiency %
40
20
0
0%
20%
40%
60%
80%
100%
15.000
10.000
5.000
0.000
-5.000
-10.000
Total Output current (%)
E-74
R12P05S/R6.4
R24P05S/R6.4
REV: 1/2015
R05P05S/R6.4
0% 20%
40%
60%
Total Output current (%)
80%
100%
www.recom-power.com
RxxPxxS_D
/Rx Series
ECONOLINE
DC/DC-Converter
Typical Characteristics - Reinforced Version
RxxP05D/R6.4
RxxP05D/R8
Efficiency / Load
Deviation / Load
100
R05P05D/R6.4
20.000
Deviation from Nominal (%)
R12P05D/R6.4
80
25.000
60
Efficiency %
40
R24P05D/R6.4
20
0
0%
20%
40%
60%
80%
100%
R12P05D/R6.4
15.000
R24P05D/R6.4
10.000
5.000
0.000
-5.000
-10.000
Total Output current (%)
R05P05D/R6.4
0%
40%
20%
60%
Total Output current (%)
80%
100%
Package Style and Pinning (mm)
7 PIN SIP Package
12.5
RECOM
R05P05D/R6.4 or
R05P05D/R8
5 tc
****
5
4.1
7.62
0.5
0.5
pin clearance
Bottom View
RECOM
RxxPxxS/R8
****
RECOM
RxxPxxS/X2/R6.4
****
5 6 7
1 2
5
7
1 2
6 7
Pin Connections
15.24
2.54
/X2 Bottom View
RECOM
RxxPxxD/R6.4
****
1.00ø+0.15/–0
0.25
Top View
1.00ø+0.15/–0
2.54
19.5
Single Output
Recommended Footprint Details
2.4
1.9
Single Output
1 2
2.54
19.5
Dual Output
RxxPxx/R
9.8
Pin #
1
2
5
6
7
Single
+Vin
-Vin
–Vout
No Pin
+Vout
Dual
+Vin
–Vin
–Vout
Com
+Vout
/X2
+Vin
–Vin
No Pin
–Vout
+Vout
XX.X ± 0.5 mm
XX.XX ± 0.25 mm
0.25
2.4
1.9
10.16
pin clearance
2.54
/X2 Top View
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit
written consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.
www.recom-power.com
REV: 1/2015
E-75