REC7.5-S_DRW

●
●
●
●
●
Features
Regulated
Converters
●
●
●
●
●
7.5W DIP24 Package
1KVDC, 2KVDC and 3kVDC Isolation Options
Approved for Medical Applications (/H)
UL and EN Safety Approvals
Continuous Short Circuit Protection
(power limiting)
5 Side Shielded Metal Case
Full SMD design
2 Case Style Options
Remote Pin Option
Efficiency to 86 %
Description The REC7.5-xxxxSRW/DRW-series offer single and dual regulated outputs in a DIP24 package
with 1kV, 2kV or 3kV options and are suitable for higher power industrial or medical
applications. Remote on/off control is possible with the /CTRL option and SMD pinning is
offered with the /SMD option. The converters can deliver 140% rated power for short periods
of time to cope with applications with large capacitive loads or high start up currents.
ECONOLINE
DC/DC-Converter
with 3 year Warranty
7.5 Watt
DIP24 & SMD
Single & Dual
Output
Selection Guide
Part
Number
Input
Voltage
(VDC)
Output
Voltage
(VDC)
Output
Current
(mA)
Efficiency
(%)
Max
Capacitive
Load (1)
REC7.5-xx3.3SRW/H*/A/M
9-18, 18-36, 36-72
3.3
1800
78
6800µF
REC7.5-xx05SRW/H*/A/M
9-18, 18-36, 36-72
5
1500
79-82
6800µF
REC7.5-xx09SRW/H*/A/M
9-18, 18-36, 36-72
9
833
81-84
6800µF
REC7.5-xx12SRW/H*/A/M
9-18, 18-36, 36-72
12
625
82-85
6800µF
REC7.5-xx15SRW/H*/A/M
9-18, 18-36, 36-72
15
500
83-86
6800µF
REC7.5-xx05DRW/H*/A/M
9-18, 18-36, 36-72
±5
±750
79-82
±2200µF
REC7.5-xx09DRW/H*/A/M
9-18, 18-36, 36-72
±9
±417
81-84
±2200µF
REC7.5-xx12DRW/H*/A/M
9-18, 18-36, 36-72
±12
±312
82-85
±2200µF
REC7.5-xx15DRW/H*/A/M
9-18, 18-36, 36-72
±15
±250
83-86
±2200µF
2:1
xx = 9-18Vin = 12,
xx = 18-36Vin = 24,
xx = 36-72Vin = 48
* add suffix /H1 for 1kVDC Isolation, /H2 for 2kVDC isolation or /H3
for 3kVDC Isolation (not available in H3/A/M/SMD combination)
* add suffix “/SMD” for SMD package, e.g. REC7.5-2405DRW/H1/A/M/SMD
* add suffix “/CTRL” for Remote Pin option
* add suffix „-R“ for Tape and Reel Packaging (only for SMD type available)
e.g. REC7.5-2405DRW/H1/A/M/SMD/CTRL-R
no plastic case is available for REC7.5
80
80
60
0
4812
0% 20%
40%
60%
Total Output current (%)
80%
100%
20
0
60
40
30
20
0
Safe Operating Area
-40
0
50
85 100
150
71
Operating Temperature °C
2405D
40
Efficiency %
Efficiency %
40
20
4815D
2409D
60
483.3
Derating-Graph
Output Power (%)
4805
2412
REC 7.5
80
Efficiency / Load
100
EN-60950-1 Certified
EN-60601-1 Certified
UL-60950-1 Certified
100
Dual
Efficiency / Load
100
E-358085
(Ambient Temperature)
Specifications (measured at TA = 25°C, nominal input voltage, full load and after warm-up)
Single
RoHS
2011/65/EU
6/6
2412D
0% 20%
40%
60%
Total Output current (%)
80%
100%
**Any data referred to in this datasheet are of indicative nature
and based on our practical experience only. For further details,
please refer to our Application Notes.
Refer to Application Notes
www.recom-power.com
REV: 0/2015
E-157
REC7.5-S_DRW/H*/A/M
Series
ECONOLINE
DC/DC-Converter
Specifications (measured at TA = 25°C, nominal input voltage, full load and after warm-up)
Input Voltage Range
2:1
Output Voltage Accuracy
±2% max.
Line Voltage Regulation
0.4% max.
Load Voltage Regulation (25% to 100% full load )
0.8% max.
Minimum Load
Output Ripple and Noise (at 20MHz BW)
10% (2)
100mVp-p max.
50mVp-p max.
3.3V output type
5, 9, 12 and 15V output types
Operating Frequency (Full Load)
150kHz min. / 240kHz max.
Input Filter
PI Network
Efficiency at Full Load
see Selection Guide
No Load Power Consumption
Isolation Voltage
H1-Suffix
H2-Suffix
H3-Suffix
300mW max.
1000VDC
500VAC / 60Hz
2000VDC
1000VAC / 60Hz
3000VDC
1500VAC / 60Hz
(tested for 1 second)
(rated for 1 minute**)
(tested for 1 second)
(rated for 1 minute**)
(tested for 1 second)
(rated for 1 minute**)
Isolation Capacitance
50pFtyp.
Isolation Resistance
1 GΩ min.
Short Circuit Protection (Max temp. = 50°C during short circuit conditions)
Continuous, Auto Restart
Operating Temperature Range (free air convection)
-40°C to +71°C (see Graph)
Storage Temperature Range
-55°C to +125°C
Relative Humidity
95% RH
Case Material
Thermal Impedance
Nickel Plated Metal with Non-Conductive Base
12°C/W
Natural convection
MTBF (+25°C)
(+71°C)
}
16g
15 pcs per Tube
Certifications
UL General Safety
Report: E358085
EN General Safety
EN Medical Safety
Notes
Note 1:
Note 2:
800 x 103hours
>200 x 103hours
using MIL-HDBK 217F
using MIL-HDBK 217F
Detailed Information see
Application Notes chapter "MTBF"
Report: SPCLVD1212007
Report: MDD1205098-3 + RM1205098-3
IEC/EN 60601-1 3rd Edition; Medical Report + ISO14971 Risk Assessment
UL 60950-1 1st Ed.
C22.2 No. 60950-1-03
EN60950-1:2006 +A12:2011
Maximum capacitive load is defined as the capacitive load that will allow start up in under 1 second without damage to the converter.
The REC 7.5 series requires a minimum of 10% load on the output to maintain specified regulation. Operating under no-load conditions
will not damage these devices; however, they may not meet all listed specifications.
Typical Characteristics
Overload Response
100
Vout (% nominal)
REC 7.5
Package Weight
Packing Quantity
75
50
25
0
0
50
100
120
140
160
180
200
% of Rated Load
E-158
REV: 0/2015
www.recom-power.com
REC7.5-S_DRW/H*/A/M
Series
ECONOLINE
DC/DC-Converter
Package Style and Pinning (mm)
24 PIN DIP Package
20.30
32.00
Pin Connections DIP24
Pin #
10.50
1
3.8+0.5 /-0.25
15.24
0.51
4.60
Recommended Footprint Details
1.00 ø+0.15/–0
(1) 2 3
9
11
16
14
Single
Dual
CTRL/No Pin CTRL/No Pin
2
–Vin
3
–Vin
–Vin
–Vin
9
NC
Com
11
NC
–Vout
14
+Vout
+Vout
16
– Vout
Com
22
+Vin
+Vin
23
+Vin
+Vin
Bottom View
23 22
2.54
XX.X ± 0.5 mm
XX.XX ± 0.25 mm
Top View
2.54
/H3/A/M/SMD combination is not allowed
24 PIN SMD Package
32.00
19.90
31.40
11.20
3.81
20.30
6.35
25.40
Recommended Footprint Details
Pin area
0.1 x 0.50
2.54
0.50
1.54
2.03
9 10 11 12
1 2 3 4 5
23.40
Bottom View
26.67
Top View
24.64
24 23 22 21 20
16 15 14 13
1
Pin #
Single
Dual
1
CTRL/NC
CTRL/NC
2
–Vin
–Vin
3
–Vin
–Vin
9
NC
Com
11
NC
–Vout
14
+Vout
+Vout
16
– Vout
Com
22
+Vin
+Vin
23
+Vin
+Vin
1,4,5,10,12
NC
13,15,20,21,24
NC
REC 7.5
2.54
Pin Connections DIP24 SMD
10.90
NC = No Connection
XX.X ± 0.5 mm
XX.XX ± 0.25 mm
27.94
11 x 2.54
CTRL Option
Vin+
ON = Open or 0V< Vctrl <1.2V
OFF = 2.2V< Vctrl <12V
Fuse
22,23
2,3
0V
TTL Input
Off
On
RECx-xxxx/CTRL
CTRL
1
1kW
1N4148
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit
written consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.
www.recom-power.com
REV: 0/2015
E-159