REMOTETRAKTM

PRODUCT DATASHEET
RM-8DO2
REMOTETRAKTM
Select RM-8DO2 when you need 8 discrete outputs that can drive up to 3 Amp loads with the benefits
of short circuit protection
PRODUCT HIGHLIGHTS
„
„
„
„
„
Amp high-current outputs drive inductive loads
Short circuit protection at full rated load
Thermal overload protection and shutdown
Time Proportioned Outputs for low cost control
Direct field wiring with two terminals per output
PERFORMANCE SPECIFICATIONS
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
„
8 channels
Output range 10-30 VDC
Max. output current per channel 3 Amps
(derate linearly to 2A from 50 to 70°C)
Max. output current (entire module) 10 Amps
Max. OFF state leakage current 0.05 mA
Min. load current per channel 0.1 mA
Inrush current (100 mS surge) 10 Amps
Max. inductive load 0.2 H (3 Amp load at 24
VDC)
Typical ON resistance 0.1 Ohms
Typical ON voltage drop (@ 1 Amp) 0.1 VDC
Short circuit protection At full rated load
Thermal shutdown protection 150° C
Serial communication information
RS485 isolation 1200 Volts RMS 1 minute
Required supply voltage 10-30 VDC
(0.5 watt typical)
Operating temperature range -30 to 70°C
Storage temperature range -40 to 85°C
Humidity (non-condensing) 5 to 95%
Note: Time Proportioned Outputs control the duty cycle of the
output in proportion to an analog output register value. The
cycle time and minimum pulse width are configurable.
ORDERING INFORMATION
RM-8DO2-F - Module with field wiring base
RM-8DO2-M - Replacement module only
All specifications are subject to change. Consult factory for latest info.
SIXNET Technology Park • 331 Ushers Road • Ballston Lake, NY 12019 USA
+1 518.877.5173 • Fax +1 518.877.8346 • [email protected]
SOLUTIONS FOR TODAY’S INDUSTRIAL NETWORKING CHALLENGES
RM-8DO2 DATASHEET
28-FEB-09
WWW.SIXNET.COM